Installing and Operating Instructions

R1.0 1592007271

1592007271 XR80C-D GB r1.0 20.05.2005.doc

XR80C – XR80D

2/4

6.

 

MAIN FUNCTIONS

6.1

 

HOW TO SEE THE SETPOINT

Push and immediately release the 

SET 

key: the display will show the

Set point value;

6.2

 

HOW TO CHANGE THE SETPOINT

1.

 

Push the 

SET 

key for more than 2 seconds to change the Set

point value;

2.

 

The value of the set point will be displayed and the 

 LED starts

blinking;

3.

 

To change the Set value push the 

o

or 

n

 arrows.

4.

 

To memorise the new set point value push the 

SET

 key again or

wait 15s.

6.3

 

HOW TO START A MANUAL AGITATION CYCLE

6.4

 

HOW TO CHANGE A PARAMETER VALUE

To change the parameter’s value operate as follows:
1.

 

Enter the Programming mode by pressing the Set and UP key for

3s (

 and 

 start blinking).

2.

 

Select the required parameter.

3.

 

Press the “

SET

” key to display its value (

 LED starts blinking).

4.

 

Use “

UP

” or “

DOWN

” to change its value.

5.

 

Press “

SET

” to store the new value and move to the following

parameter.

To exit

: Press 

SET + UP 

or wait 15s without pressing a key.

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to

expire.

6.5

 

THE HIDDEN MENU

The hidden menu Includes all the parameters of the instrument.

6.5.1  HOW TO ENTER THE HIDDEN MENU

1.

 

Enter the Programming mode by pressing the Set + 

n

 key for 3s

(

 and 

 start blinking).

2.

 

When a parameter is displayed keep pressed the Set+

n

  for more

than 7s. The Pr2 label will be displayed immediately followed from the
HY parameter. 

NOW YOU ARE IN THE HIDDEN MENU.

3.

 

Select the required parameter.

4.

 

Press the “

SET

” key to display its value (Now only the 

 LED is

blinking).

5.

 

Use 

o

or 

n

 to change its value.

6.

 

Press “

SET

” to store the new value and move to the following parameter.

To exit

: Press 

SET + 

o

or wait 15s without pressing a key.

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to

expire.

6.5.2  HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO

THE FIRST LEVEL AND VICEVERSA.

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST
LEVEL” (user level) by pressing 

“SET + 

n

.

In HIDDEN MENU when a parameter is present in Fisrt Level the decimal point is on.

6.6

 

HOW TO LOCK THE KEYBOARD

1. 

 

Keep pressed for more than 3 s the UP and DOWN keys.

2. 

 

The “POF” message will be displayed and the keyboard will be locked. At this point it
will be possible only to see the set point or the MAX o Min temperature stored

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed.

6.7

 

TO UNLOCK THE KEYBOARD

Keep pressed together for more than 3s the UP and DOWN keys.

7.

 

LIST OF PARAMETERS

NOTE: the parameters preceded by  dots usually are only in the Hidden Menu.
REGULATION
Hy Differential

: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point.

Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when
the temperature reaches the set point.

 

LS  Minimum set point

: (- 50°C÷SET / -58°F÷SET): Sets the minimum acceptable

value for the set point.

 

US  Maximum set point

: (SET÷ 150°C / SET÷302°F). Set the maximum acceptable

value for set point.

Ot  Thermostat probe calibration

: (-12.0÷12.0°C;

-120÷120°F) allows the adjustment of possible offset of the thermostat probe.

 

OdS Outputs 

activation 

delay at start up: 

(0÷255min) This function is enabled at

the initial start up of the instrument and inhibits any output activation for the period of
time set in the parameter.

AC  Anti-short cycle delay

: (0÷50 min) minimum interval between the compressor stop

and the following restart.

 

COn  Compressor ON time with faulty probe

: (0÷255 min) time during which the

compressor is active in case of faulty thermostat probe. With COn=0 compressor is
always OFF.

 

COF  Compressor OFF time with faulty probe

: (0÷255 min) time during which the

compressor is OFF in case of faulty thermostat probe. With COF=0 

compressor is

always active.

DISPLAY

 

CF

Temperature measurement unit

:  °C = Celsius; °F= Fahrenheit. 

WARNING

:

When the measurement unit is changed the SET point and the values  of the
parameters Hy, LS, US, Ot, ALU and ALL have to be checked and modified if
necessary).

rES Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows the decimal point displaying.

AGITATION CYCLE

 

AgC Agitator configuration  EL 

= switched 

 

ON and OFF with the compressor;

in 

= switched 

 

ON according to parameter IAg.

 

tiC  Resolution for the Agt parameter

nP 

= the Agt parameter is in minutes

Pb 

= the Agt parameter is in seconds

iAG Interval between agitation cycles

: (1

÷

120 min) Determines the time interval

between the beginning of two agitation cycles. 

NOTE:

 When a continuous agitation

cycle is started, the time counting is reset and starts from zero.

Agt Length for agitation cycle

: (0

÷

255 min/sec) It sets the agitation cycle duration.

APO First agitation cycle after start-up

: (y = Immediately; n= after the IAG time)

ALARMS

 

ALC  Temperature alarms configuration

: (Ab; rE)

Ab

= absolute temperature: alarm temperature is given by the ALL or ALU values.  

rE

= temperature alarms are referred to the set point. Temperature alarm is enabled
when the temperature exceeds the “SET+ALU” or “SET-ALL” values.

ALU MAXIMUM temperature alarm

: (ALL÷150°C;

ALL ÷302°F) when this temperature is reached  the alarm is enabled, after the “ALd”
delay time.

ALL Minimum temperature alarm

: (-50.0°C ÷ ALU;

-58°F ÷ ALU) when this temperature is reached  the alarm is enabled, after the “ALd”
delay time.

 

ALd  Temperature alarm delay

: (0÷255 min) time interval between the detection of

an alarm condition and alarm signalling.

 

dAO Exclusion of temperature alarm at startup

: (from 0.0 min to 23.5h) time

interval between the detection of the temperature alarm condition after instrument
power on and alarm signalling.

OTHER

 

PbC Probe selection:

 (Ptc=PTC probe; ntc=NTC probe). It allows the selection of

the type of probe.

 

rEL Software release 

for internal use.

 

Ptb Parameter table code:

 readable only.

8.

 

INSTALLATION AND MOUNTING

Instrument 

XR80C

 shall be mounted on panel, in a 29x71

mm hole, and fixed using the special bracket supplied.
To obtain an IP65 protection grade use the front panel
rubber gasket (mod. RG-C) as shown in figure.

Push the 

UP 

key for more than 2 seconds and a manual agitation

cycle will start.

Содержание XR80C

Страница 1: ...al parameters that can be easily programmed through the keypad 3 CONTROLLING LOADS 3 1 THE COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point va...

Страница 2: ...le value for the set point US Maximum set point SET 150 C SET 302 F Set the maximum acceptable value for set point Ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows the adjustment of possible offset of the thermostat probe OdS Outputs activation delay at start up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for the period...

Страница 3: ...emp alarm Output unchanged LA Minimum temp alarm Output unchanged 11 1 ALARM EE The instrument is provided with an internal check verifying memory integrity Alarm EE flashes when a failure in the internal memory is detected In such case call the service 11 2 ALARM RECOVERY Probe alarm P1 start some seconds after the fault in the related probe it automatically stops some seconds after the probe res...

Страница 4: ...ON time with faulty probe 0 255 min 15 COF Compressor OFF time with faulty probe 0 255 min 30 CF Temperature measurement unit C F C rES Resolution in dE dE AgC Agitator configuration EL with compressor in independent EL tIC Resolution for the Agt parameter nP minutes Pb seconds nP IAg Interval between agitation cycle 1 120min 15 Agt Length for agitation cycle 0 255min 3 APO First agitation cycle a...