Installing and Operating Instructions

R1.0 1592007271

1592007271 XR80C-D GB r1.0 20.05.2005.doc

XR80C – XR80D

1/4

Milk tank controllers

XR80C – XR80D

CONTENTS

1. GENERAL WARNING______________________________________________ 1
2. GENERAL DESCRIPTION __________________________________________ 1
3. CONTROLLING LOADS ____________________________________________ 1
4. FRONT PANEL COMMANDS________________________________________ 1
5. MAXIMUM AND MINIMUM TEMPERATURE FUNCTIONS _________________ 1
6. MAIN FUNCTIONS ________________________________________________ 2
7. LIST OF PARAMETERS ____________________________________________ 2
8. INSTALLATION AND MOUNTING ____________________________________ 2
9. ELECTRICAL CONNECTIONS_______________________________________ 3
10. HOW TO USE THE HOT KEY _______________________________________ 3
11. ALARM SIGNALS _________________________________________________ 3
12. TECHNICAL DATA ________________________________________________ 3
13. CONNECTIONS __________________________________________________ 3
14. DEFAULT SETTING VALUES _______________________________________ 4

1.

 

GENERAL WARNING

1.1

 

PLEASE READ BEFORE USING THIS MANUAL

 

This manual is part of the product and should be kept near the instrument for easy
and quick reference.

 

The instrument shall not be used for purposes different from those described
hereunder. It cannot be used as a safety device.

1.2

 

 SAFETY PRECAUTIONS

 

Check the supply voltage is correct before connecting the instrument.

 

Do not expose to water or moisture: use the controller only within the operating limits
avoiding sudden temperature changes with high atmospheric humidity to prevent
formation of condensation

 

Warning: disconnect all electrical connections before any kind of maintenance.

 

The instrument must not be opened.

 

Fit the probe where it is not accessible by the end user.

 

In case of failure or faulty operation send the instrument back to the distributor or to
“Dixell S.p.A.” (see address) with a detailed description of the fault.

 

Consider the maximum current which can be applied to each relay (see Technical
Data).

 

Ensure that the wires for probes, loads and the power supply are separated and far
enough from each other, without crossing or intertwining.

 

In case of applications in industrial environments, the use of mains filters (our mod.
FT1) in parallel with inductive loads could be useful.

2.

 

GENERAL DESCRIPTION

Models 

XR80C

, 32x 74 format, and 

XR80D

, DIN format,  are a microprocessor based

controllers suitable for application in the milk preservation / refrigeration sector. They are
equipped with one thermostat probe and two relay outputs to control the compressor and
agitator.
The XR80C and XR80D allow a very accurate control of all the main functions required
during the "milk-tank preservation" cycles, including the timed cycles of agitator functions.
The operator can also manually start a timed agitation cycle by pushing the 

o

 

key on the

instrument's front panel.
Each instrument is fully configurable through special parameters that can be easily
programmed through the keypad.

3.

 

CONTROLLING LOADS

3.1

 

THE COMPRESSOR

The regulation is performed according to the temperature measured by the thermostat
probe with a positive differential from the set point: if the temperature increases and
reaches set point plus differential the compressor is started and then turned off when the
temperature reaches the set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are timed
through parameters “

COn

” and “

COF

”.

3.2

 

AGITATION CYCLE

The functions of the agitator can be selected by means of the AgC parameter.

AgC = EL

 (parallEL)the agitator always operates when the compressor is running and

continues to do so for a length of time - which can be set in parameter 

“Agt”

(Duration of agitation cycle)- even after the compressor stops. If the compressor does
not run longer than the time set in parameter 

“IAG” 

(Interval between agitation

cycles), the agitator will start to function anyway for the length of time set in parameter

Agt

.

AgC= in 

independent agitator. The agitator is switched ON and OFF according to the IAg

parameter independently from the state of the compressor. It operates for the time set
in the Agt parameter.

3.3

 

MANUAL AGITATION CYCLE

It can be started by means of the 

o

 key, by holding it pressed for 3 seconds. Agitator

remains ON for the time set in Agt parameter. The compressor keeps with the normal
regulation.

4.

 

FRONT PANEL COMMANDS

  

SET

: To display target set point; in programming mode it  selects a parameter  or confirm

an operation.

o

  (

UP)

: To see the max. stored temperature; in programming mode it browses the

parameter codes or increases the displayed value.

TO START A MANUAL AGITATION CYCLE:

 in normal operation, by holding it

pressed for 3s the agitation  cycle is started.

n

  (

DOWN

) To see the min stored temperature; in programming mode it browses the

parameter codes or decreases the displayed value.

KEY COMBINATIONS:

o

n

 

To lock & unlock the keyboard

.

SET +

 

n

To enter in programming mode.

SET + 

o

To return to the room temperature display.

4.1

 

MEANING OF LEDS

Each LED function is described in the following table.

LED

MODE

FUNCTION

ON

Compressor enabled

Flashing

-Programming Phase (flashing with 

)

- Anti-short cycle delay enabled

ON

Agitator enabled

Flashing

- Programming Phase (flashing with 

)

5.

 

MAXIMUM AND MINIMUM TEMPERATURE FUNCTIONS

5.1

 

HOW TO SEE THE MIN TEMPERATURE

1. 

 

Press and release the 

n

 key.

2. 

 

The “Lo” message will be displayed followed by the minimum
temperature recorded.

3. 

 

By pressing the 

n

 key again or by waiting 5s the normal display will be restored.

5.2

 

HOW TO SEE THE MAX TEMPERATURE

1. 

 

Press and release the 

o

 key.

2. 

 

The “Hi” message will be displayed followed by the maximum
temperature recorded.

3. 

 

By pressing the 

o

 key again or by waiting 5s the normal display will be restored.

5.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED

1.

 

Hold press the SET key for more than 3s, while the max. or min temperature is
displayed. (rSt message will be displayed)

2.

 

To confirm the operation the “rSt” message starts blinking and the normal
temperature will be displayed.

XR80C signals and records temperature alarms, together with their duration and max
value reached. See drawing:

Содержание XR80C

Страница 1: ...al parameters that can be easily programmed through the keypad 3 CONTROLLING LOADS 3 1 THE COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point va...

Страница 2: ...le value for the set point US Maximum set point SET 150 C SET 302 F Set the maximum acceptable value for set point Ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows the adjustment of possible offset of the thermostat probe OdS Outputs activation delay at start up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for the period...

Страница 3: ...emp alarm Output unchanged LA Minimum temp alarm Output unchanged 11 1 ALARM EE The instrument is provided with an internal check verifying memory integrity Alarm EE flashes when a failure in the internal memory is detected In such case call the service 11 2 ALARM RECOVERY Probe alarm P1 start some seconds after the fault in the related probe it automatically stops some seconds after the probe res...

Страница 4: ...ON time with faulty probe 0 255 min 15 COF Compressor OFF time with faulty probe 0 255 min 30 CF Temperature measurement unit C F C rES Resolution in dE dE AgC Agitator configuration EL with compressor in independent EL tIC Resolution for the Agt parameter nP minutes Pb seconds nP IAg Interval between agitation cycle 1 120min 15 Agt Length for agitation cycle 0 255min 3 APO First agitation cycle a...

Отзывы: