Installing and Operating Instructions

 

release  7.0

 

9.2 Alarm “EE” 

The instruments in the Dixell range are provided with an internal check verifying data and memory integrity. 
Alarm “

EE

” flashes when a failure in data or in the internal memory is detected. In such case the alarm output 

is enabled. 

 

WHAT TO DO 

1.  Cancel the alarm by pressing a key.  
2.  Check the value of all parameters and restore correct values when wrong. 
3.  Check the correct instrument operation and in case of further errors replace it. 

9.3  Alarm reset through keyboard 

It is referred to alarms “

EE

”, “

dEA

” and “

FF

”. Reset is performed by pressing any key while the alarm is being 

signalled, then message “

rES

” is displayed for about 3s before normal operation is restored. 

9.4  Alarm recovery  

Probe alarms “

P1

” and “

P2

” start 30 seconds after the fault in the related probe; they automatically stop 30 

seconds after the probe restarts normal operation. Check connections before replacing the probe. 
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns to 

normal values and when defrost starts. 
Alarms “

dEA

” and “

FF

” automatically stop after 30 minutes. 

10. TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case  
 

XR160C,  XR162C, XR172C: 

frontal 32x74 mm; depth 60mm; 

 

XR170C: 

frontal 32x74 mm; depth 70mm 

 

XR160D, XR170D, XR30SL, XR40SL:

 4 DIN modules 70x85 mm; depth 61mm.  

Mounting 

 

XR160C, XR170C, XR162C, XR172C 

panel mounting in a 71x29 mm panel cut-out. 

 

XR160D, XR170D, XR30SL, XR40SL:

 DIN RAIL mounted in a omega (3) din rail .   

Frontal protection 
 

XR160C, XR170C, XR162C, XR172C:

 IP65 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

 

XR162C

 is connected to the slave module 

XR30SL

 through a multipolar connector. 

 

XR172C

 is connected to the slave module 

XR40SL

  through a multipolar connector. 

Power supply 

  

XR160C, XR170C:

 12Vac/dc, -10% +15%

 XR160D,

 

XR170D, XR30SL, XR40SL:

 110/230Vac, 

±

 10%  50/60Hz (opt. 24Vac, 

±

 10% 50/60Hz)

 

 XR162C:

 by the slave XR30SL. 

 

XR172C:

 by the slave XR40SL. 

Power absorption: 

3VA max.

 

Display

: 3 digits, red LED, 14,2 mm high.  

Inputs

: 2 PTC probes.

 

Relay outputs

 

 compressor

 

 

XR160C, XR170C, XR160D, XR170D:

  SPDT relay  8(3)A, 250Vac

 

 

XR162C, XR172C

  SPST relay 16(6)A, 250Vac 

 

defrost 

 

XR160C, XR170C, XR162C, XR172C:

  SPDT relay 8(3) A, 250Vac

 

 

XR160D, XR170D:

  SPST relay 5(2)A, 250Vac 

 fans 

 

XR160C, XR170C, XR162C, XR172C:

 SPST 8(3)A, 250Vac

 

 

XR160D, XR170D:

  SPST relay 5(2)A, 250Vac 

 

 

952057-58

 

XR160C - XR170C - XR160D - XR170D - XR162C - XR172C 

8/

י

 

 

Содержание XR160C

Страница 1: ...________________ 4 5 1 Function Menu_______________________________________________________ 4 5 2 List of functions ______________________________________________________ 4 5 3 Exit Timeout___________...

Страница 2: ...eful 2 GENERAL DESCRIPTION Models XR160C and XR170C 32x74 mm format are microprocessor based controllers suitable for applications on medium or low temperature refrigerating units They are provided wi...

Страница 3: ...ing defrost After defrost there is a timed fan delay allowing for drip time set by means of the Fnd parameter FnC 2 fans will switch ON and OFF with the compressor and run during defrost FnC 3 fans wi...

Страница 4: ...le LED MODE Function ON Compressor enabled FLASHING Programming Phase flashing with LED Anti short cycle delay enabled ON Fan enabled FLASHING Programming Phase flashing with LED ON Defrost enabled FL...

Страница 5: ...put into Pr1 user level by pressing SET DOWN When a parameter is present in Pr1 LED is on 5 5 Changing a parameter s value Each parameter is identified by a special alphanumeric code label To change...

Страница 6: ...hich causes the end of defrost dFd Temperature displayed during defrost 0 real temperature 1 temperature at defrost start 2 set point 3 dEF label dAd MAX display delay after defrost 0 120 min Sets the...

Страница 7: ...iquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins...

Страница 8: ...starts Alarms dEA and FF automatically stop after 30 minutes 10 TECHNICAL DATA Housing self extinguishing ABS Case XR160C XR162C XR172C frontal 32x74 mm depth 60mm XR170C frontal 32x74 mm depth 70mm X...

Страница 9: ...172C buzzer for an acoustic signal of alarms Data storing on the non volatile memory EEPROM Operating temperature 0 60 C Relative humidity 20 85 no condensing Storage temperature 30 85 C Measuring and...

Страница 10: ...F 1 120 Pr2 6 dSd 1 120 Pr2 0 MdF 0 120 Pr2 30 dtE 57 50 C o 196 F Pr2 8 46 dFd 0 Real 1 Start 2 Set 3 dEF Pr2 1 dAd 0 120 Pr2 30 tdF 0 Eletrical 1 Hot gas Long Time 2 Relay OFF 3 Relay ON Short time...

Отзывы: