Dixell

 

Installing and Operating Instructions

 

release  7.0

 

3.2  Fast freezing  

When defrost is not in progress, it can be activated the keypad by holding the “

UP

” key pressed for about 3 

seconds. The compressor operates in continuous mode for the time set through the “

CCt

” parameter. The 

cycle can be terminated before the end of the set time using the same activation key, “

UP

” for about 3 

seconds. 

3.3 Defrost 

Two defrost modes are available through the “

tdF

” parameter: defrost through electrical heater (tdF = 0) and 

hot gas  defrost (tdF = 1). Other parameters are used to control the interval between defrost cycles and its 
maximum length.The defrost end is controlled by the evaporator’s probe. 
At the end of defrost the drip time starts - it is controlled through the “

Fdt

” parameter.  

3.4  “Air dryer” applications 

The 

tdF

 parameter can be set also for “Air dryer” applications. In this case (tdF=2 or 3) the defrost relay is 

energised according to the “Short Time” mode. The following parameter table describes the cycle times when 
the 

tdF

 parameter is selected for Long or Short time. 

 

Parameters 

Long time (tdF = 0; 1) 

Short time (tdF = 2; 3) 

dAF, dSd, MdF, Fdt 

minutes  

seconds 

IdF  

hours  

minutes  

3.5  Control of evaporator fans 

The fan control mode is selected by means of the “

FnC

” parameter: 

 

FnC=0

   fans will switch ON and OFF with the compressor and

 not run

 during defrost

:

 

FnC=1

   fans will run continuously, but not during defrost  

After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter. 
 

FnC=2

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC=3

   fans will run continuously also during defrost 

 

An additional parameter “FSt” provides the setting of temperature, detected by the evaporator probe, above 
which the fans are always OFF. This can be used to make sure circulation of air only if his temperature is 
lower than set in “FSt”. 

3.6  Fan relay used as 2° compressor 

If 

FnC=4 

the fan relay is programmed to control a second compressor, in this case the 

Fnd 

parameter value is 

defined as time delay, in seconds, between turning on compressors 1 and 2. 

4.  FRONT PANEL COMMANDS 

SET

:

 

TO DISPLAY TARGET SET POINT

: by pressing and releasing this key the set point is displayed 

for 5s. 

TO MODIFY SET POINT: b

y holding the key pressed for at least 2s set point change mode is entered: the set 

point is displayed and the LEDs of the first and third digits blink. To change the value use the “

UP

” 

and “

DOWN

” keys. The new value can be stored either by pressing the 

“SET”

 key (the instrument 

restores temperature display) or by waiting the exit time-out to expire (15s). 

 

 (

UP

):  in programming mode or in “

Function Menu

” it browses the parameter codes or increases the 

value of the displayed variable. Hold pressed for a faster change.  

 

TO START A FAST FREEZING CYCLE:

 in normal operation, by holding it pressed for 3s the fast 

freezing  cycle is started. Such cycle can be interrupted by holding the “

UP

” key pressed for 3s. 

 
 
 
 

 

952057-58

 

XR160C - XR170C - XR160D - XR170D - XR162C - XR172C 

3/

י

 

 

Содержание XR160C

Страница 1: ...________________ 4 5 1 Function Menu_______________________________________________________ 4 5 2 List of functions ______________________________________________________ 4 5 3 Exit Timeout___________...

Страница 2: ...eful 2 GENERAL DESCRIPTION Models XR160C and XR170C 32x74 mm format are microprocessor based controllers suitable for applications on medium or low temperature refrigerating units They are provided wi...

Страница 3: ...ing defrost After defrost there is a timed fan delay allowing for drip time set by means of the Fnd parameter FnC 2 fans will switch ON and OFF with the compressor and run during defrost FnC 3 fans wi...

Страница 4: ...le LED MODE Function ON Compressor enabled FLASHING Programming Phase flashing with LED Anti short cycle delay enabled ON Fan enabled FLASHING Programming Phase flashing with LED ON Defrost enabled FL...

Страница 5: ...put into Pr1 user level by pressing SET DOWN When a parameter is present in Pr1 LED is on 5 5 Changing a parameter s value Each parameter is identified by a special alphanumeric code label To change...

Страница 6: ...hich causes the end of defrost dFd Temperature displayed during defrost 0 real temperature 1 temperature at defrost start 2 set point 3 dEF label dAd MAX display delay after defrost 0 120 min Sets the...

Страница 7: ...iquid infiltration It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature Place the defrost termination probe among the evaporator fins...

Страница 8: ...starts Alarms dEA and FF automatically stop after 30 minutes 10 TECHNICAL DATA Housing self extinguishing ABS Case XR160C XR162C XR172C frontal 32x74 mm depth 60mm XR170C frontal 32x74 mm depth 70mm X...

Страница 9: ...172C buzzer for an acoustic signal of alarms Data storing on the non volatile memory EEPROM Operating temperature 0 60 C Relative humidity 20 85 no condensing Storage temperature 30 85 C Measuring and...

Страница 10: ...F 1 120 Pr2 6 dSd 1 120 Pr2 0 MdF 0 120 Pr2 30 dtE 57 50 C o 196 F Pr2 8 46 dFd 0 Real 1 Start 2 Set 3 dEF Pr2 1 dAd 0 120 Pr2 30 tdF 0 Eletrical 1 Hot gas Long Time 2 Relay OFF 3 Relay ON Short time...