Operating Manual 

 

3/3 

 

Mounting: 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20; 

Frontal protection: 

IP65 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply: 

according to the model 230Vac 

±

10%, 50/60Hz --- 110Vac 

±

10%, 50/60Hz

 

Power absorption: 

3.5VA max

 

Display

: 2 digits, red LED, 14,2 mm high; 

Inputs

: Up to 2 NTC.

 

Digital input: 

 free voltage contact 

Relay outputs:  compressor 

SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac or 20(8)A 250Vac

 

 

 

defrost: 

SPDT 8(3) A, 250Vac 

 

 

fan: 

SPST 8(3) A, 250Vac or SPST 5(2) A 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

2;

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0÷60 °C;

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range: NTC 

-40÷110°C;

 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable); 

Accuracy (ambient temp. 25°C)

:  ±0,1 °C ±1 digit 

15. CONNECTIONS 

15.1

 

XR06CX – 20+8+5A OR 16+8+5A – 110VAC OR 230VAC 

 

 

NOTE: 

The compressor relay is 20(8)A or 16(6)A depending on the model.

 

NOTE: 

Connect the 120Vac power supply to 4-5 

15.2

 

XR06CX -- 8+8+8A -- 110VAC OR 230VAC 

 

 

 

NOTE: 

Connect the 120Vac power supply to 6-7 

16. DEFAULT SETTING VALUES 

 

LAB

EL

 

DESCRIPTION 

RANGE 

DEFAULT 

REGULATION

 

Hy 

Differential 

0.1 ÷ 25°C/1 ÷ 45°F 

2.0°C / 4 °F 

LS 

Minimum Set Point 

-55°C÷SET/-67°F÷SET 

-55 °C /-

55°F 

US 

Maximum Set Point 

SET÷99°C/ SET÷99°F 

99 °C / 

99°F 

ot 

First probe calibration 

-9.9÷9.9°C/-17÷17°F  

0.0 

P2 

Second probe presence 

n – Y 

oE 

Second probe calibration 

-9.9÷9.9°C/-17÷17°F 

0.0 

od 

Outputs activation delay at start up 

0 ÷ 99 min 

AC 

Anti-short cycle delay 

0 ÷ 50 min 

Cy 

Compressor ON time faulty probe 

0 ÷ 99 min 

15 

Cn 

Compressor OFF time faulty probe 

0 ÷ 99 min 

30 

DISPLAY

 

CF 

Measurement units 

°C - °F 

°C / °F 

rE 

Resolution (only for °C) 

dE – in 

dE 

Ld 

Default Display 

P1 - P2 - SP  

P1 

dy 

Display delay 

0 ÷ 15 min 

DEFROST

 

td 

Defrost type 

EL – in 

EL 

dE 

Defrost termination temperature 

-55÷50°C/-67÷99°F 

8.0 °C / 46 

°F 

id 

Interval between defrost cycles 

0 ÷ 99 hours 

Md 

Maximum length for defrost 

0 ÷ 99 min. 

30 

dd 

Start defrost delay 

0 ÷ 99 min. 

dF 

Display during defrost 

rt – in – SP – dF 

it 

dt 

Drip time 

0 ÷ 99 min 

dP 

Defrost at power-on 

y - n 

FANS

 

FC 

Fans operating mode 

cn – on – cY – oY 

on 

Fd 

Fans delay after defrost 

0 ÷ 99 min 

10 

FS 

Fans stop temperature 

-55÷50°C/-67÷99°F 

2.0 °C / 36 

°F  

ALARMS

 

AU 

Maximum temperature alarm 

ALL÷99°C / ALL÷99°F 

99 °C / 99 

°F 

AL 

Minimum temperature alarm 

-55°C÷ALU/-

67°F÷ALU 

-55 °C / -

55 °F 

Ad 

Temperature alarm delay 

0 ÷ 99 min 

15 

dA 

Exclusion of temperature alarm at 
startup 

0 ÷ 99 min 

90 

DIGITAL INPUT

 

iP 

Digital input polarity 

cL – oP 

cL 

iF 

Digital input configuration 

EA – bA – do – dF – Au 

– Hc 

EA 

di 

Digital input delay 

0 ÷ 99 min 

dC 

Compressor and fan status when open 
door 

no /Fn / cP / Fc 

FC 

rd 

Regulation with door open 

n - Y 

OTHER 

d1 

Thermostat probe display  

Read Only 

- - -  

d2 

Evaporator probe display 

Read Only 

- - -  

Pt 

Parameter code table 

Read Only 

- - -  

rL 

Firmware release 

Read Only 

- - -  

 
 

 