GB
23
GLOBE - IP1839
Output
Description
TC
Automatic closing time.
From 0 to 120 s, with TC<MAX.
With TC=MAX automatic closing is disabled.
The count starts with door stopped for time set with TC.
After the intervention of a safety (1-8), the countdown begins with the open door and lasts for the whole
time set with TC.
With TC=MAX or contact 1-9 open, automatic closing is disabled.
If disabled with 1-9, automatic closing is re-enabled, once the contact 1-9 has been closed again, only
after a control 1-5 or a remote control.
R1
Obstacle thrust adjustment.
The control panel is equipped with a safety device that stops the opening
operation and stops and inverts the closing operation in the presence of an obstacle.
With R1=MIN there is maximum obstacle sensitivity (minimum thrust).
With R1=MAX the detection function is deactivated (maximum thrust).
5. SETTINGS
5.1 Trimmer
MIN
MAX=disabled
Description
OFF
ON
DIP1 Control 1-5 function.
Step by step.
Opening.
DIP2 Selection of direction.
Opening towards gearmotor.
Closing towards gearmotor.
DIP3
Disengagement on the closing
stop with JR2=ON
2 mm
0,5 mm
Note: use this selection to prevent an incom-
plete closing of the sectional doors.
Disengagement on the closing
stop with JR2=OFF
5 mm
5 mm
DIP4 State of door at start
.
Indicates how the electronic panel
considers the door at the time of
start.
Open.
With DIP1=OFF the first control 1-5 closes
the door.
With DIP1=ON the first control 1-5 opens
the door.
Close.
The first control 1-5 opens the door.
Note: automatic closing cannot be the first
control even if enabled.
DIP5 Electric lock release.
Disabled.
Enabled.
Before opening from closed door, a thrust
is included in closing to facilitate electric
lock release.
DIP6
Pre-flashing light.
Disabled during opening.
Enabled only with automatic closure with
TC>3 s.
Enabled for both opening and closing.
5.4 Signals
LED
ON
Flashing
POWER ALARM
24 V= power supply.
Encoder / automation fault.
SA
Indicates that at least one of the N.C. safety contacts
is open.
Upon starting the LED flashes indicating the count of
the operations which have been carried out:
each quick flashing = 1000 operations
each slow flashing = 10000 operations
SIG
During radio transmitter enabling/storing phase.
During radio transmission reception.
71R
5.2 Dip-Switches
Description
OFF
ON
SO Safety operation.
The opening of contact 1-8 with door stopped
enables opening manoeuvre. In the last 30
mm before closing stop, this causes stop.
The opening of contact 1-8 with door
stopped prevents any operation.
JR2 Automation type.
Up and over door with counterweight.
Sectional and up and over door with
springs.
JR3
Maximum limit manoeuvering
forces.
Normal closing force.
Reduced closing force.
JR4 Built-in radio receiver
.
Disabled.
Enabled.
5.3 Jumpers
MIN=0 s
MAX=disabled
120 s
Содержание GLOBE IP1839
Страница 4: ...4 GLOBE IP1839 Fig 5a Fig 5b Fig 5c Y K 3000 GLOBEGF GLOBEGA Fig 5e Fig 5d E H Fig 5f...
Страница 5: ...5 GLOBE IP1839 30 10 100 M 45 Fig 6 min 680 30...
Страница 6: ...6 GLOBE IP1839 min 900 GLOBEC 30 Fig 7 30 min 20 max 210 GLOBEC...
Страница 7: ...7 GLOBE IP1839 DOOR TYPE YEAR OF MANU FACTUR E VOL TAGE SUPPL Y SERIA L NUMB ER Fig 8...
Страница 8: ...8 GLOBE IP1839 GLOBESI 30 8 75 42 220 30 8 75 42 220 Fig 9a Fig 9b Fig 9c...