42
ECL-PTU-207 Preloaded Applications
HVAC Mode Management
The nvoHeatCool is computed according to nviApplicModeTerminalLoad (nvoFP06)nvoWindowCon-
tact, nviSpaceTemp and FreezepProtSp (nviFP44)
A ChgOverDelay (nviFP44) prevents the nvoHeatCool from switching between cooling and heating too
often.
nviSpaceTemp
nvoWindowContact
nviApplicMode
TerminalLoad
(nvoFP06)
nvoHeatCool
>FreezepProtSp
(nviFP44)
Open
Any
Any
Off
Closed
Auto
>0
Cool mode
<0
Heat mode
=0
Unchanged
Other than Auto
Any
nviApplicMode
<FreezepProtSp
(nviFP44)
Any
Any
Any
Heat mode, the fan and
the heating outputs are
overriden to 100%
untilnviSpaceTempreac
hes FreezepProtSp
(nviFP44) +2°C.
Table 6: HVAC modes
Temperature Management
Cooling Mode
The cooling or change-over valve is controlled in sequence with the fan speed to maintain the space
temperature to the actual cooling setpoint nvoEffectCoolSp.
The cooling or change-over valve is:
£
rescaled
between 0% to 100% when the TerminalLoad (nvoFP06) is between 0% and 100%.
£
disabled
when the fan is not running unless the nciFanSettings.FanCtrlType (nviFP39) is set to
None.
£
disabled
while in cooling mode if a condensation sensor input is active on DI5 or received from a
master controller.
The fan speed request is rescaled between 0% and CoolMaxFan (nviFP39) when the TerminalLoad
(nvoFP06) is between FanCoolLow and FanCoolHigh.
Heating Mode
The heating or change-over valve is controlled in sequence with the electric heater and the fan speed
to maintain the space temperature to the actual cooling setpoint nvoEffectHeatSp.
£
If the system is not equipped with an electric heater, the heating or change-over valve is rescaled
between 0% and 100% when TerminalLoad (nvoFP06) is between 0% and 100%.
£
If the system is equipped with an electric heater, the heating or change-over valve is rescaled be-
tween 0% to 100% when TerminalLoad (nvoFP06) is between 0% and 50% while the electric
heater is rescaled between 0% to 100% when TerminalLoad (nvoFP06) is between 50% and
100%.
The heating or change-over valve and the electric heater are disabled when the fan is not running un-
less the nciFanSettings.FanCtrlType (nviFP39) is set to None.
The fan speed request is rescaled between 0% and HeatMaxFan (nviFP39) when TerminalLoad
(nvoFP06) is between FanHeatLow and FanHeatHigh.
Sequence of Operation