37
ECL-PTU-207 Preloaded Applications
Boolean Constants
FreeCoolingEnable (ConstantBool1)
This variable is used to enable free cooling via the fresh air damper.
ID
Units
Valid Range
Default Value
Constant Boolean 1
TRUE/FALSE
N/A
FALSE
EnableRoomUnocc (ConstantBool2)
This variable is used to configure the behavior of RoomOccupancy when the OccupancyCmd is set to
unoccupied.
When this variable is set to TRUE, the RoomOccupancy (BV2), will be set to Unoccupied on the re-
ception of an unoccupied command from nviSchedule_1.
ID
Units
Valid Range
Default Value
Constant Boolean 2
TRUE/FLSE
N/A
TRUE
nviFanSpeedCmdDigital (ConstantBool3)
This variable is used to configure the behavior of the fan speed signal when receiving fan speed com-
mand override from nviFanSpeedCmd.
When this value is set to TRUE, the value received from nviFanSpeedCmd will be considered 3 fan
speed operation commands.
See nviFanSpeedCmd for more information on this configuration parameter.
ID
Units
Valid Range
Default Value
Constant Boolean 3
TRUE/FALSE
N/A
TRUE
HeatValveConfig (ConstantBool4)
This variable is used to configure the operating mode of the heating valve.
ID
Units
Valid Range
Default Value
Constant Boolean 4
NormOpen/NomClose
N/A
NormClose (FALSE)
CoolValveConfig (ConstantBool5)
This variable is used to configure the operating mode of the cooling or change-over valve
ID
Units
Valid Range
Default Value
Constant Boolean 5
NormOpen/NomClose
N/A
NormClose (FALSE)