background image

 

5/14 

 

 

 

Figure 12. 

Auxilliary Switches 

DA-088N024PA2XP and DA-088N024PX2XP 

Figure 13 shows the adjustable switching values for auxiliary switches 
A and B. 

 

 

Figure 13.  Adjustable Switching Values for the Dual 

Auxiliary Switches. 

 

 

The  auxiliary  switch  setting  shafts  rotate  with  the 
actuator.  The  scale  is  valid only when the actuator is in 
the "0" position on clockwise motion 

Use  the  long  arm  of  the  †  (AUX  SWITCH  ADJUSTMENT)  to  point  to 
the position of switch A. Use the narrower tab on the red ring to point to 
the position of switch B. 

Dual in-Line Package (DIP) Switches 

For:  DA-088N024PXXXP 

Raise the protective cover from left to right to locate the DIP switches. 
See Figure 2 for the location of the cover. 

The factory setting is 0 (OFF). 

When mechanical angle of rotation is limited, the self-adapt switch may 

be turned ON 

  so that the limited range will become the new 0 to 

100% for the actuator logic. In this case, 0 to 100% is not equal to 90°. 

 

Figure 14.  Self-adapt Switch. 

 

 

 

 

When  turning  the  self-adaptive  feature  on  or  after  the 
software  reset  with  the  feature  on,  the  actuator  will  enter  a 
five-minute  calibration  cycle  as  the  actuator  adjusts  to  the 
rotation limits of the system. A software reset happens after 
power on or may be caused by electrostatic discharge (ESD) 
at levels of 2kV and above. 

 

The  position  output  signal  U  is  not  influenced  by  the  self-adapt 
function. The 0 to 10V feedback signal U is always proportional to 0° to 
90° (or 90° to 0°). 

 

The factory setting is clockwise. 

The  direction  of  rotation  switch  should  match  the  damper  rotation 
movement. 

 

Figure 15.  Direction of Rotation Switch. 

 

The factory setting is direct acting.  

As  the  clockwise  angle  of  rotation  increases,  the  output  voltage 
increases. 

If the direction of rotation is counterclockwise, the output signal switch 
should  be  set  at  reverse  acting  to  match  the  direction  of  the  rotation 
switch. 

 

Figure 16.  Output Signal Switch. 

Manual Override 

To  move  the  damper  blades  and  lock  the  position  with  no  power 
present, do the following: 

1.  Slide the red manual override knob toward the back of the actuator. 

See Figure 17. 

2.  Make adjustments to the damper position. 
3.  Slide the red manual override knob toward the front of the actuator. 

Once power is restored, the actuator returns to automated control. 

 

Figure 17.  Manual Override. 

Содержание DA-088N Series

Страница 1: ...Avoid areas where corroding deteriorating or explosive vapors fumes or gases may be present Ensure that all equipment is installed according to local regional and national regulations Personal injury...

Страница 2: ...lever to the right Return the switch to automatic See Figure 17 To mount a modulating DA 088N024Pxxxx set the Dual In line Package DIP switches to the required positions 1 To access the DIP switches...

Страница 3: ...g Actuator to Damper Shaft Figure 8 Installing the Position Indicator b Figure 9 Attaching the Mounting Bracket Operation A continuous 0 to 10 Vdc signal from a controller to wire 8 Y operates the dam...

Страница 4: ...e Ys changes When the mechanical limitation of the angle of rotation and self adapt function are ON 100 does not equal 90 Setting for 10V slope 0 Vdc offset Figure 11 Examples in Figure 10 Uo Offset V...

Страница 5: ...the feature on the actuator will enter a five minute calibration cycle as the actuator adjusts to the rotation limits of the system A software reset happens after power on or may be caused by electros...

Страница 6: ...slope and offset features this example assumes Offset Uo 0 Vdc Slope U 10 Vdc Mechanical Range Limitation and Self Adapt Feature 1 To use the entire 0 to 10V input signal to control the adjusted range...

Страница 7: ...formance Installations requiring Conformance All wiring for CE rated actuators must only be separated extra low voltage SELV or protective extra low voltage PELV per HD384 4 41 Use safety isolating tr...

Страница 8: ...lue S6 Switch B N O Q24 Black pink P1 Feedback Potentiometer 0 to 100 P1 P2 a White red P2 Feedback Potentiometer Common b White blue P3 Feedback Potentiometer 100 to 0 P3 P2 c White pink Each wire ha...

Страница 9: ...9 14 Figure 23 0 to 10 Vdc Modulating Control...

Страница 10: ...or shaft coupling returns to the 0 position Check the Auxiliary Switch A 1 Set the DMM dial to ohms resistance or continuity check 2 Connect wires S1 and S3 to the DMM The DMM should indicate open cir...

Страница 11: ...able precabled Numbers listed associate with terminal positions M9109 Series is not available precabled Numbers listed associate with terminal positions Floating Control Distech Controls DA 088N Serie...

Страница 12: ...12 14 Dimensions Figure 24 Dimensions of the DA ASK75 7U Weather Shield in Inches Millimeters...

Страница 13: ...13 14 Dimensions cont d Figure 25 Dimensions of the DA 088N Actuator and Mounting Bracket in Inches mm...

Страница 14: ...cialist installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change delete...

Отзывы: