4/14
Control signal adjustment
DA-088N024PAXXP and DA-088N024PA2XP:
For sequencing and
the electronic limitation of the angle of rotation.
-
Use the Uo potentiometer to set the offset (start point) between 0
to 5 Vdc.
-
Use the
U potentiometer to set the slope (span) between 2 to 30
Vdc.
The Y input is limited to a maximum of 10 Vdc. If the
sum of the offset and slope setting is greater than 10V,
the angle of rotation is reduced providing the feature of
electronic limitation of the angle of rotation.
Figure 10.
Ys:
Actuator position (100% = angle of rotation
90°*)
Y:
Control input signal
Uo:
Offset (start point)
U:
Slope
Uw:
Active voltage range (Ys changes)
*When the mechanical limitation of the angle of
rotation and self-adapt function are ON, 100% does
not equal 90°.
Setting
for
10V
slope
0 Vdc offset
Figure 11.
Examples
in
Figure 10
Uo
Offset
Vdc
U
Slope
Vdc
Active Voltage
Range
Vdc
Ys
Actuator
Position
Minimum slope
0
2
0 to 2
0 to 100%
Limitation
of
rotation
5
30
5 to 10
0 to 16.7%
Limitation
of
rotation
0
30
0 to 10
0 to 33.3%
Setting shown in
Figure 14
0
10
0 to 10
0 to 100%
Control signal adjustment example:
Determine the setting needed to electronically limit the angle of
rotation between 0 to 50% (0 to 45°) using a 2 to 10 Vdc input.
Calculating the value of
U:
Vdc
Vdc
Vdc
Vdc
Uo
Vdc
[%]
U
16
)
2
10
(
%
50
%
100
])
[
]
[
10
(
[%]
Ys
rotation
of
angle
working
100
Settings: Uo = 2 Vdc;
U = 16 Vdc
Electronic limitation:
-
Angle of rotation: Ys = 50% (45°)
-
Slope:
U = 16V
-
Active voltage range:
Uw = 2 to 10 Vdc