background image

 

 

12/14 

 

Dimensions 

 

Figure 24.  Dimensions of the DA-ASK75.7U Weather Shield in Inches (Millimeters). 

 

 

Содержание DA-088N Series

Страница 1: ...Avoid areas where corroding deteriorating or explosive vapors fumes or gases may be present Ensure that all equipment is installed according to local regional and national regulations Personal injury...

Страница 2: ...lever to the right Return the switch to automatic See Figure 17 To mount a modulating DA 088N024Pxxxx set the Dual In line Package DIP switches to the required positions 1 To access the DIP switches...

Страница 3: ...g Actuator to Damper Shaft Figure 8 Installing the Position Indicator b Figure 9 Attaching the Mounting Bracket Operation A continuous 0 to 10 Vdc signal from a controller to wire 8 Y operates the dam...

Страница 4: ...e Ys changes When the mechanical limitation of the angle of rotation and self adapt function are ON 100 does not equal 90 Setting for 10V slope 0 Vdc offset Figure 11 Examples in Figure 10 Uo Offset V...

Страница 5: ...the feature on the actuator will enter a five minute calibration cycle as the actuator adjusts to the rotation limits of the system A software reset happens after power on or may be caused by electros...

Страница 6: ...slope and offset features this example assumes Offset Uo 0 Vdc Slope U 10 Vdc Mechanical Range Limitation and Self Adapt Feature 1 To use the entire 0 to 10V input signal to control the adjusted range...

Страница 7: ...formance Installations requiring Conformance All wiring for CE rated actuators must only be separated extra low voltage SELV or protective extra low voltage PELV per HD384 4 41 Use safety isolating tr...

Страница 8: ...lue S6 Switch B N O Q24 Black pink P1 Feedback Potentiometer 0 to 100 P1 P2 a White red P2 Feedback Potentiometer Common b White blue P3 Feedback Potentiometer 100 to 0 P3 P2 c White pink Each wire ha...

Страница 9: ...9 14 Figure 23 0 to 10 Vdc Modulating Control...

Страница 10: ...or shaft coupling returns to the 0 position Check the Auxiliary Switch A 1 Set the DMM dial to ohms resistance or continuity check 2 Connect wires S1 and S3 to the DMM The DMM should indicate open cir...

Страница 11: ...able precabled Numbers listed associate with terminal positions M9109 Series is not available precabled Numbers listed associate with terminal positions Floating Control Distech Controls DA 088N Serie...

Страница 12: ...12 14 Dimensions Figure 24 Dimensions of the DA ASK75 7U Weather Shield in Inches Millimeters...

Страница 13: ...13 14 Dimensions cont d Figure 25 Dimensions of the DA 088N Actuator and Mounting Bracket in Inches mm...

Страница 14: ...cialist installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change delete...