background image

 #4 -13511 Crestwood Place, Richmond, BC, V6V 2E9, Canada 

+ 1.778.776.3288 

                 [email protected]

discoverbattery.com

3.6 Ripple Currents

• 

During recharging (up to 2.40VPC) the effective value of the 
AC ripple current may temporarily reach a maximum 10A per 
100Ah of C

10

 nominal capacity. 

• 

After recharging and at float charge in stand-by operation or 
buffer operation the effective value of the AC ripple current 
must not exceed 5A per 100 Ah of C

10

 nominal capacity.

4. Battery Maintenance

4.1 Visual Inspection and Cleaning Instructions

Check for any visible defects such as cracked jars, loose terminal 
posts and oxidized connectors. To avoid leakage currents and the 
asSoCiated risk of fire, keep the battery dry and clean. Clean with 
clear water. Do not use any solvents or detergents. Avoid electrostatic 
charges.

4.2 Bi-annual Maintenance

• 

Battery voltage

• 

Voltage of some cells/bloc batteries (pilot cells)

• 

Temperature of the container in some cells/bloc batteries (pilot 
cells)

• 

Confirm daily DoD per cell

• 

Confirm max DoD per cell does not exceed the allowed limit

• 

Confirm charging factor is within acceptable limits

• 

Confirm that charge settings correspond to recommendations

• 

Check if corrective equalizing is applied according to 3.2.2.2 

4.3 Annual Maintenance 

Further to the bi-annual maintenance, do the following:
• 

Check/record if connectors are firmly tightened.

• 

Inspect/record the racks for corrosion or loss of integrity.

• 

Check/record if ventilation is sufficient.

• 

Check/record voltage of all cells/blocks

• 

Check/record surface temperature of all cells/blocks

• 

Check/record battery room temperature

• 

Check/record ventilation

3.3 Operation at Very Low or No Load

When there is little or no load connected to the system for long 
periods (more than 1 month) while the battery remains connected, 
the normal charging settings in Sec. 3.2 are too high and result in 
unwanted overcharging. The same applies to Stand-alone systems 
with oversized PV array and very low MDDoD (<5%) (e.g. remote 
telecom transmitters). In these circumstances use the following 
settings. The temperatures are average over one month.

Stand-Alone Systems

Hybrid Systems
• 

When only the PV is engaged: use settings shown in “Constant 
Voltage One Step.”

• 

When only the diesel is engaged (continuously): use “Constant 
Voltage Two Step”, and reduce the settings by 0.05V each. 
 

3.4 Temperature  Limits

• 

The ideal operating temperature range is 25°C/77°F ± 5°C/41°F. 

• 

The recommended operating temperature range is 15°C to 
35°C (60°F to 95°F). 

• 

Higher temperatures reduce operating life. A maximum 
ambient operating temperature of 45°C/113°F must not be 
exceeded. 

• 

In hybrid applications the yearly average ambient temperature 
should be less than 30°C/86°F.

• 

Sub-zero temperatures may cause electrolyte freezing and 
irreversible damage when the battery’s state of charge (SoC) 
is low. 

• 

The minimum safe temperature versus the cell/block state of 
charge (SoC)% of C

10

 nominal capacity:

To counter low temperature operation the system designer 
shall consider thermal insulation, increasing battery capacity or 
increasing the minimum system voltage. In Stand-alone systems 
it is recommended to use controllers with adjustable Low Voltage 
Disconnect (LVD) settings for the battery temperature (higher LVD 
for lower temperature). During operation the temperature difference 
between individual cells/block should be below 3°C/37°F.

3.5 Current Limits

The maximum charging current during the bulk charging is 3 x I

10

 (30% 

of the batteries C

10

 nominal capacity) while the battery voltage is below 

the gassing voltage of 2.40 VPC.

Controller 

type

Setting

-20°C to 

0°C

0°C to 

15°C

15°C to 

35°C

>35°C

Constant 

Voltage 

One Step

Voltage 

Regulation

2.37VPC

2.35VPC

2.30VPC

2.27VPC

Constant 

Voltage 

Two Step

Absorption 

time up to 

2 hrs per 

day

2.40VPC

2.40VPC

2.35VPC

2.30VPC

Float

2.35VPC

2.30VPC

2.25VPC

2.25VPC

On-Off

High 

Voltage

2.40VPC

2.35VPC

2.30VPC

2.30VPC

Low 

Voltage

2.20VPC

2.20VPC

2.20VPC

2.20VPC

State of 

charge (SoC)

<20%

20%-40%

40%-60%

60%-80%

Freezing point

-40°C / -40°F

-30°C / -22°F

-

20°C / -4°F

-15°C / 5°F

Содержание Tubular Gel OPzV

Страница 1: ...1 Crestwood Place Richmond BC V6V 2E9 Canada 1 778 776 3288 info discoverbattery com discoverbattery com RE Stationary Applications Tubular OPzV Gel 2V 6V and 12V Cells Blocks Tubular Gel OPzV Operating Manual ...

Страница 2: ...re secure installation Use only suitable handling equipment and lifting gear Dangerous Voltage Batteries with this symbol can be recycled Do not mix with other industrial or household waste Contact your servicing Discover dealer for proper battery return and recycling Use protective glasses gloves and clothing when working on batteries Always make safe working practices a priority No Smoking Do no...

Страница 3: ...Discharge Protection 6 Array to Load Ratios for Stand alone Systems 6 Low voltage Re Connect LVR for Stand alone Systems 6 3 2 Charging 6 3 2 1 Balance or Complete Charge 6 3 2 2 Equilizing charge 7 3 2 2 1 Functional Equalizing 7 3 2 2 2 Corrective Equalizing 7 3 2 3 Normal Operation Charging 7 3 2 3 1 Settings for Stand Alone Systems 7 3 2 3 2 Settings for Hybrid Systems 8 3 3 Operation at Very ...

Страница 4: ...een cells or blocks The layout of the battery room or installation area must allow for easy access to the batteries The recommended minimum distance between battery rows is 1 5 times the depth of the row Racks or cabinets shall be located 100mm 4in from the wall Be sure to provide adequate space and lighting for inspection maintenance testing and cell block replacement Space should also be provide...

Страница 5: ...voltage directive 73 23 EEC which confirms that the CE marking is applied to the battery The company installing the battery is responsible for the declaration and applying the CE marking For future identification apply individual cell block numbers in sequence starting from one end of the series string Also apply identification letters or numbers for the parallel strings Only connect the battery t...

Страница 6: ...the supervisor nearby It lasts until certain charge criteria are fulfilled but not outside certain minimum and maximum time limits It is mainly used as Commissioning charge after installation Sec 2 8 Corrective equalizing charge Sec 3 2 2 2 Preparation charge before a capacity test Sec 6 Refresh charge during long storage period Sec 1 2 7 The battery temperature must be monitored during charge It ...

Страница 7: ...l generators mainly telecom hybrid systems the charging source is always available but the boost charging time is restricted to favor a more efficient utilization of the diesel In both cases a scheduled functional equalizing charge shall be performed at regular intervals Sec 3 2 3 to protect the battery from acid stratification sulphation and loss of capacity Functional Equalizing frequency is adj...

Страница 8: ...and alone systems with oversized PV array and very low MDDoD 5 e g remote telecom transmitters In these circumstances use the following settings The temperatures are average over one month Stand Alone Systems Hybrid Systems When only the PV is engaged use settings shown in Constant Voltage One Step When only the diesel is engaged continuously use Constant Voltage Two Step and reduce the settings b...

Страница 9: ...phs BatteryVoltage in relation to DoD as guidance for the initial LVD settings first try settings 25 C 77 F reference temperature 25ºC reference temperature DoD100 DoD90 DoD80 DoD70 DoD60 DoD50 DoD40 DoD30 DoD20 Minimum for Standby use MINIMUM FOR SOLAR USE 1 75 1 80 1 85 1 90 1 95 2 00 2 05 2 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Battery Voltage Vpc Extracted Amperhours per 100A...

Страница 10: ...ischarge or how deeply the battery has been dis charged Like the fuel gauge of your car DoD is the measure of how much fuel you have used I10 The constant current I discharge rate that can be maintain for 10 hours 10 MDDoD Maximum Daily Depth of Discharge allowable MDoD Maximum allowable Depth of Discharge OCV Open Circuit Voltage The voltage across the cell block or battery terminals with no load...

Отзывы: