8
2.5 Internal Heating Specifications
Table 2-5.
DLP-GC2 Internal Heating Specifications
Internal Heating Spec.
DLP-GC2-12V
DLP-GC2-24V
DLP-GC2-36V
DLP-GC2-48V
Heating Power
50 W
50 W
50 W
50 W
Heating On
Charge detected and < 0°C (32°F)
Heating Off
Temperature > 2°C (36°F)
2.6 Specifications for Parallel System Sizing
Table 2-6.
DLP-GC2-12V System Size Specifications - Examples
Parallel
System
Peak Current
Constant
Discharge
Constant
Charge
Energy/Usable
Capacity
Reserve Capacity
at 25A
2 Batteries
720 A
400 A
240 A
3072 Wh
576 minutes
3 Batteries
1080 A
600 A
360 A
4608 Wh
864 minutes
4 Batteries
1440 A
800 A
480 A
6144 Wh
1152 minutes
Table 2-7.
DLP-GC2-24V System Size Specifications - Examples
Parallel
System
Peak Current
Constant
Discharge
Constant
Charge
Energy/Usable
Capacity
Reserve Capacity
at 25A
2 Batteries
360 A
240 A
120 A
3072 Wh
288 minutes
3 Batteries
540 A
360 A
180 A
4608 Wh
432 minutes
4 Batteries
720 A
480 A
240 A
6144 Wh
576 minutes
Table 2-8.
DLP-GC2-36V System Size Specifications - Examples
Parallel
System
Peak Current
Constant
Discharge
Constant
Charge
Energy/Usable
Capacity
Reserve Capacity
at 25A
2 Batteries
180 A
120 A
60 A
2304 Wh
144 minutes
3 Batteries
270 A
180 A
90 A
3456 Wh
216 minutes
4 Batteries
360 A
240 A
120 A
4608 Wh
288 minutes
Table 2-9.
DLP-GC2-48V System Size Specifications - Examples
Parallel
System
Peak Current
Constant
Discharge
Constant
Charge
Energy/Usable
Capacity
Reserve Capacity
at 25A
2 Batteries
180 A
120 A
60 A
3072 Wh
144 minutes
3 Batteries
270 A
180 A
90 A
4608 Wh
216 minutes
4 Batteries
420 A
240A
120 A
6144 Wh
288 minutes
2.7 Regulatory
Table 2-10.
DLP-GC2 Regulatory
Regulatory
UN38.3 Transportation
UL 2271 (pending)
IEC 62619 (pending)
CE
UL 1973 (pending)