22
3. Insert the male end of the cable into the female end of the
950-0038
DLP T Connector
and vice versa.
4. Repeat until all nodes have been attached.
5. Network with other devices and accessories as needed.
8.8.3 Testing and Verification of the LYNK Network
Network verification must be completed with one of
950-0006 SOC GAUGE
TYPE A
,
950-0039 SOC GAUGE TYPE B
,
950-0025 LYNK II
, or
950-0040 LYNK
LITE Communication Gateway
.
If a
SOC GAUGE TYPE A
or
B
is networked:
• If the display illuminates, power can be confirmed as ON for the LYNK
Network.
• If the display is showing SOC, communications are confirmed as active
for the LYNK Network.
If an
LYNK II
or
LYNK LITE Communication Gateway
is networked:
• If the LYNK Network Bus indication LED is illuminated, power and
communications are confirmed as active for the LYNK Network.
• LYNK Access Software can be used via a computer to confirm the number
of batteries in the LYNK Network.
9. OPERATION
The BMS prevents battery operation outside of specified operating conditions.
Make sure to understand each of these protections and how to set up the
system accordingly. Refer to
Table 2-4
DLP GC2 Protection Specifications
.
NOTICE
Intentional bypassing of the BMS to operate the battery outside maximum and
minimum limits will void the warranty.
9.1 Low Voltage Cut-Off
As controlled by the application, the low voltage cut-off should be
programmed at or above the Low Voltage Disconnect in
Table 2-1
DLP-GC2
Electrical Specifications
. This ensures the load will disconnect before the BMS is
forced to enter low voltage protection.
NOTICE
Storing or leaving the battery at 0% SOC will lead to irreversible damage and
invalidate the warranty.
Figure 12. Network
Installation.
Figure 13. Complete Network Installation.