Rev 1.3 22.07.09
Dingo Reference Manual
18
Settings Used in Programs 0-3
When programs 0-3 are selected, the Dingo
automatically uses the values below in its
regulation. These are not visible on the screen
and are not adjustable by the user. For adjustable
settings, choose program 4.
The voltage settings are shown correct for 12V
operation. For higher voltages, scale these up (eg.
for a 24V system, multiply each voltage figure by
2.)
Settings for Program 4
If program 4 is selected, then all settings can be
accessed and adjusted.
After TIME, VOLT and PROG, there are entry
points for three further sub menus:
REG
Allows the user to customise the
regulation settings (see below for details).
MODE
Allows the user to adjust other
configuration options.
EVNT
Settings for the event controller.
CHRG
Setting for program number
Parameter
0
1
2
3
GMOD
0
G ON (V)
11.5
GOFF (V)
13.8
GDEL (Min)
10
GEXD (Day)
30
GRUN (Hr)
1.0
LOAD
Setting for program number
Parameter
0
1
2
3
LOFF (V)
11.3
L ON (V)
12.8
LDEL (Min)
10
SET/REG
Setting for program number
Parameter
0
1
2
3
BMAX (V)
15.0
14.2
15.0
14.2
EMAX (V)
16.0
14.0
16.0
14.0
ETIM (Hr)
1.0
0
1.0
0
EFRQ (day)
45
ABSV (V)
14.0
ATIM (Hr)
2.0
FLTV (V)
13.8
HYST (V)
0.4
BRTN (V)
12.3
CHRG (A)
20
BFRQ (Day)
15
TCMP
0
SET/MODE
Setting for program number
Parameter
0
1
2
3
LSET
1
1
4
4
GSET
2
2
9
9
ESET
Default or Prog 4 settings
BSET
0
0
2
2
BAT2 (V)
14.0
PWM
1
ALRM (V)
11.4
SET/MODE/
ESET
Default Settings
(see section 7.5.2)
SW 1 to C
0 (charge switch -on to charge)
SET/EVNT
Setting for program number
Parameter
0
1
2
3
STRT
12
TIME (Hr)
0
STOP
12
TIME (Hr)
25.5
EMOD
2
TMOD
0
7