11
©
Dinel, s.r.o. CLS–23
8 . s
ensor
settings
The setting is done by placing magnetic pen MP–8 to sensitive
spot M located on the front of the sensor. Short time attaching
(up to 2 sec.) of the magnetic pen to the sensitive spot M
makes the sensor open. Long time attaching (at least 4 sec.) of
the pen when the level is changed, defines closed state of the
sensor. In this way is set the sensitivity for the measured medi
-
um and switching modes SO (normally open) or SC (normally
closed).
Sensitive spot
FACTORY DEFAULT SETTINGS:
Types
CLS–23_–10; –20; –30
are set to detect mineral oil,
CLS–23_–11; –12; –21
to detect water.
The mode O is set (sensor closes when immersed).
When the level is low (the container is empty), attach the magnetic pen
MP–8 to the sensitive spot M for long time (min. 4 sec.). When the level
is high (the container is full), attach the magnetic pen MP–8 to the sensitive
spot M for short time (max. 2 sec.)..
When the level is low (the container is empty), attach the magnetic pen
MP–8 to the sensitive spot M for short time (max. 2 sec.). When the
level is high (the container is full), attach the magnetic pen MP–8 to the
sensitive spot M for long time (min. 4 sec.).
mode O
(normally open)
mode C
(normally close)
9 . s
tatUs
signalization
(only with LED state indicator variant)
Indicator
Function
Orange LED
Continuous light
– Sensor is closed (switched ON)
Dark
– Sensor is open (switched OFF)
Rapid flashing (period 0.2 s)
– Unrecognized upper and lower limits or setting mistake
Slow flashing (period 0.8 s)
– Short circuit at sensor output
Sensors of type
CLS–23E
are produced
without signaling indicator LED
. For control of correct
settings it is necessary to interconnect the sensor to related evaluation unit or load.
In the case of the vertical mounting for detection of
non-conductive
liquids by sensors
CLS–23_–20;
–30
and for detection of
conductive
and
non-conductive
liquids by sensors
CLS–23_–21
it neces
-
sary to set limits ON and OFF when electrode of the sensor is immersed to medium.