2 Purpose of the Heat 

Pump

2.1 Application

The water-to-water heat pump is to be used exclusively for the
heating of heating water. It can be used in newly built or previ-
ously existing heating systems. Water is used as the heat carrier.
It can be supplied by wells or other water systems.
In order to eliminate the risk of corrosion at the evaporator, the
well water must be evaluated regarding the corrosion behaviour
of metallic materials according to DIN 50930.
Details can be found in the project planning and installation man-
ual for heat pumps for heating purposes.

ATTENTION!

The well water must comply with the required water quality standards.

2.2 Operating Principle

A well pump conveys the water to the evaporator of the heat
pump. There the heat is transferred to the refrigerant in the refrig-
erating circuit.
The refrigerant is drawn in by the electrically driven compressor,
compressed and “pumped” to a higher temperature level. The
electrical power needed to run the compressor is not lost in this
process. Most of it is absorbed by the refrigerant as well.
Subsequently, the refrigerant is passed through the condenser
where it transfers its heat energy to the heating water.
Depending on the set operating point (thermostat setting), the
heating water is thus heated up to a max. of 60 °C.

3 Basic Device

The basic device consists of a ready-to-use heat pump for indoor
installation, complete with casing, switch box and integrated heat
pump manager. The refrigerant circuit is hermetically sealed. It
contains the Kyoto protocol approved refrigerant R407C with a
GWP value of 1525. It is CFC-free, does not deplete ozone and
is non-flammable.
All components required for the operation of the heat pump are
located in the switch box. An external wall temperature sensor in-
cluding fixing accessories and a dirt trap are supplied with the
heat pump. The power feed for the load current and the control
current must be installed by the customer.
The supply lead of the well pump (to be provided by the cus-
tomer) must be connected to the switch box. It is important to en-
sure that the integrated motor protection is sufficient for the pump
provided by the customer.

1)

Evaporator

2)

Switch box

3)

Liquifier

4)

Compressor

Содержание WI 14ME

Страница 1: ...t Pump for Indoor Installation Pompe chaleur eau eau pour installation int rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Installation and...

Страница 2: ......

Страница 3: ...E 5 6 Aufstellung DE 5 6 1 Allgemeine Hinweise DE 5 6 2 Schallemissionen DE 5 7 Montage DE 6 7 1 Allgemein DE 6 7 2 Heizungsseitiger Anschluss DE 6 7 3 W rmequellenseitiger Anschluss DE 6 7 4 Temperat...

Страница 4: ...falls f r die Benutzung durch Laien zur Beheizung von L den B ros und anderen hnlichen Arbeitsum gebungen von landwirtschaftlichen Betrieben und von Hotels Pensionen und hnlichen oder anderen Wohneinr...

Страница 5: ...zugef hrte elektrische Antriebs leistung geht nicht verloren sondern wird gr tenteils ebenfalls dem K ltemittel zugef hrt Daraufhin gelangt das K ltemittel in den Verfl ssiger und ber tr gt hier wied...

Страница 6: ...m Vor und R cklauf der W rmetauscherleitungen und ein Elektronikmodul erfassen die gemessenen Werte und bertragen ein Signal an den W rmepumpenmanager der ab h ngig von der aktuellen Betriebsart der W...

Страница 7: ...ur in nicht feuchten Innenr umen auf einer ebe nen glatten und waagrechten Fl che aufzustellen Dabei sollte der Rahmen rundum dicht am Boden anliegen um eine geeig nete Schallabdichtung zu gew hrleist...

Страница 8: ...berstr mventils ist nur bei Fl chenheizungen und einem max Heizwasserdurchsatz von 1 3 m h ratsam Bei Nichtbeachten kann es zu St rungen der Anlage f hren Frostschutz bei frostgef hrdeter Aufstellung...

Страница 9: ...evtl auch dem Warmwasserspeicher Dabei wird statt vieler Einzelkomponen ten ein kompaktes System verwendet um die Installation zu ver einfachen Weitere Informationen sind der jeweiligen Montage anwei...

Страница 10: ...er Punkte 3 4 5 werden in die Elektroverteilung eingebaut Die Lastleitungen f r die Heizk rper sind entsprechend DIN VDE 0100 auszulegen und abzusichern 7 Alle installierten Leitungen m ssen als dauer...

Страница 11: ...uellenseite Im W rmequelleneintritt der W rmepumpe ist ein Schmutzf n ger montiert um den Verdampfer gegen Verunreinigungen zu sch tzen Anfangs sollte das Filtersieb des Schmutzf ngers in relativ kurz...

Страница 12: ...22000 3 5 Kaltwasserdurchsatz bei interner Druckdifferenz W rmequelle m h Pa 2 0 6200 3 3 19000 3 6 K ltemittel Gesamt F llgewicht Typ kg R407C 1 7 R407C 1 9 3 7 Schmiermittel Gesamt F llmenge Typ Lit...

Страница 13: ...bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Na...

Страница 14: ...D 12 Deutsch 13...

Страница 15: ...ansport EN 5 6 Set up EN 5 6 1 General Information EN 5 6 2 Sound Emissions EN 5 7 Installation EN 6 7 1 General Information EN 6 7 2 Heating System Connection EN 6 7 3 Heat Source Connection EN 6 7 4...

Страница 16: ...rective It is thus also in tended for use by non professionals for heating shops offices and other similar working environments in agricultural establish ments and in hotels guest houses and similar o...

Страница 17: ...not lost in this process Most of it is absorbed by the refrigerant as well Subsequently the refrigerant is passed through the condenser where it transfers its heat energy to the heating water Dependi...

Страница 18: ...of the heat exchanger pipes and an electronics module acquire the measured values and transmit a signal to the heat pump manager which depending on the cur rent operating mode of the heat pump heatin...

Страница 19: ...only be installed indoors in rooms with low humidity on a level smooth and horizontal surface The entire base of the frame should lie directly on the floor to ensure a good soundproof seal If this is...

Страница 20: ...nd a max heating water flow of 1 3 m h System faults may result if this is not observed Antifreeze protection for installation locations prone to frost The antifreeze function of the heat pump manager...

Страница 21: ...cylinder A compact system is used to simplify the installation process so that a lot of different components do not have to be installed individually Further information can be found in the relevant i...

Страница 22: ...r It is con trolled 230 V AC by the heat pump manager via terminals N and N1 J16 NO 10 6 The contactors mentioned above in points 3 4 and 5 are in stalled in the electrical distribution system The mai...

Страница 23: ...t the manufacturer of the chemicals 9 3 Cleaning the Heat Source System A dirt trap is inserted in the heat source inlet of the heat pump to protect the evaporator against the ingress of impurities Wh...

Страница 24: ...old water flow rate at an internal pressure differential of heat source m h Pa 2 0 6200 3 3 19000 3 6 Refrigerant total filling weight type kg R407C 1 7 R407C 1 9 3 7 Lubricant total filling weight ty...

Страница 25: ...Installation FR 5 6 1 G n ralit s FR 5 6 2 Emissions sonores FR 5 7 Montage FR 6 7 1 Remarques d ordre g n ral FR 6 7 2 Branchement c t installation de chauffage FR 6 7 3 Raccordement c t source de ch...

Страница 26: ...on initi es des fins de chauf fage de boutiques bureaux et autres environnements de travail quivalents dans les entreprises agricoles et dans les h tels pensions et autres lieux r sidentiels La pompe...

Страница 27: ...contraire galement en grande partie au fluide frigorig ne Le fluide frigorig ne arrive alors dans le condenseur o son tour il transmet l nergie thermique l eau de chauffage Ainsi l eau de chauffage c...

Страница 28: ...ique et un module lectronique saisissent les donn es mesur es et transmettent un message au gestionnaire de pompe chaleur qui en fonction du mode ac tuel de la pompe chaleur chauffage eau chaude sanit...

Страница 29: ...ur dans des pi ces non humi des sur une surface plane lisse et horizontale Ici le ch ssis de la pompe chaleur doit adh rer au sol sur toute sa circonf rence afin de garantir une isolation acoustique a...

Страница 30: ...it tre garanti dans la pompe chaleur Cela peut par ex tre obtenu par l installa tion d un distributeur double sans pression diff rentielle ou d une soupape diff rentielle Vous trouverez des explicatio...

Страница 31: ...poser aux rayons directs du soleil quelle que soit la saison C ble de sonde longueur max 40 m section de fils min 0 75 mm diam tre ext rieur du c ble 4 8 mm 7 4 3 Montage des sondes d applique Le mont...

Страница 32: ...nchement de la pompe de puits Tous les composants lectriques n cessaires l utilisation de la pompe chaleur se trouvent sur le panneau de com mande Il faut pr voir une d connexion avec au moins 3 mm d...

Страница 33: ...service 9 Entretien nettoyage 9 1 Entretien Pour viter des dysfonctionnements dus des d p ts dans les changeurs thermiques de la pompe chaleur il faut veiller ce qu aucune sorte de d p t ne puisse s...

Страница 34: ...ne d passe pas une temp rature moyenne annuelle de 13 C Dans ce cas il suffit de respecter les valeurs limites de fer et de mangan se d p t d ocre 10 D faillances recherche de pannes Cette pompe chal...

Страница 35: ...e pression interne source de chaleur m h Pa 2 0 6200 3 3 19000 3 6 Fluide frigorig ne poids au remplissage total type kg R407C 1 7 R407C 1 9 3 7 Lubrifiant poids total au remplissage type litres Polyo...

Страница 36: ...FR 12 Fran ais 12...

Страница 37: ...II 3 4 Legende Legend L gende A VIII 4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique A IX 4 1 Monovalente W rmepumpenanlage mit einem Heizkreisen Monovalent heat pump syste...

Страница 38: ...HQJHZLQGH RQQHFWLRQV RQ WKH KHDWLQJ VLGH 0 H WHUQDO WKUHDG RQQHFWLRQV RQ WKH KHDW VRXUFH VLGH 0 H WHUQDO WKUHDG DWHU ILOWHU ZLWK H WHUQDO WKUHDG 5DFFRUGV F Wp FKDXIIDJH 0 LOHWDJH H WpULHXU 5DFFRUGV F...

Страница 39: ...VVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ HL ZDVVHUGXUFKIOXVV LQ P K HDWLQJ ZDWHU IORZ UDWH LQ P K pELW G HDX GH FKDXIIDJH HQ P K...

Страница 40: ...V LQ P K ROG ZDWHU IORZ UDWH LQ P K pELW G HDX IURLGH HQ P K HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRP...

Страница 41: ...www dimplex de A V Anhang Appendix Annexes 3 1 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande 1HW 0DLQV 5pVHDX...

Страница 42: ...A VI Anhang Appendix Annexes 3 2 3 2 Last Load Charge 3 3 3 UXQGIRV 0 63 0 63...

Страница 43: ...HTXLUHG UDFFRUGHU VL QpFHVVDLUH SDU OH FOLHQW 1HW DVW 0DLQV RDG 5pVHDX KDUJH RQWDNW RIIHQ 3 JHVSHUUW RQWDFW RSHQ 3 GLVDEOHG RQWDFW RXYHUW 3 EORTXpH LH XQNWLRQ YRQ LVW ZlKOEDU 7KH IXQFWLRQ RI FDQ EH VH...

Страница 44: ...lateur circuit M16 Zusatzumw lzpumpe Auxiliary circulating pump Circulateur suppl mentaire M18 Warmwasserladepumpe Hot water loading pump Pompe de suralimentation d eau chaude M19 Schwimmbadwasserumw...

Страница 45: ...raulisches Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique 4 1 Monovalente W rmepumpenanlage mit einem Heizkreisen Monovalent heat pump system with one heating circuits Installation monova...

Страница 46: ...mpenanlage mit einem Heizkreisen und Warmwasserbereitung Monovalent heat pump system with one heating circuits and domestic hot water preparation Installation monovalente de pompe chaleur avec une cir...

Страница 47: ...auch Flexible connection hose Tuyau de raccord flexible R ckschlagklappe Check valve Clapet anti retour Wasser Wasser W rmepumpe Water to water heat pump Pompe chaleur eau eau Reihen Pufferspeicher Bu...

Страница 48: ...E Type s EG Richtlinien Niederspannungsrichtlinie 2006 96 EG EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC directive 2004 108 EC Pressure...

Страница 49: ...www dimplex de A XIII Anhang Appendix Annexes 5...

Страница 50: ...A XIV Anhang Appendix Annexes 5...

Страница 51: ...www dimplex de A XV Anhang Appendix Annexes 5...

Страница 52: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Отзывы: