LA 60S-TU

1

Safety  notes

1.1 Symbols and markings

Particularly important information in these instructions is
marked with CAUTION! and NOTE.

CAUTION!

!!

Immediate danger to life or danger of severe personal injury or
significant damage to property.

NOTE

ººººº

Risk of damage to property or minor personal injury or
important information with no further risk of personal injury
or damage to property.

1.2 Intended use

This device is only intended for use as specified by the manu-
facturer. Any other use beyond that intended by the manufac-
turer is prohibited. This requires the user to abide by the rele-
vant project planning documents. Please refrain from
tampering with or altering the device.

1.3 Legal regulations and directives

This heat pump is designed for use in a domestic environment
according to Article 1, Paragraph 2 k) of EU directive 2006/42/
EC (machinery directive) and is thus subject to the require-
ments of EU directive 2014/35/EU (low-voltage directive). It is
thus also intended for use by non-professionals for heating
shops, offices and other similar working environments, in agri-
cultural establishments and in hotels, guest houses and similar
/ other residential buildings.
The construction and design of the heat pump complies with all
relevant EU directives, DIN/VDE regulations (see CE declaration
of conformity).
When connecting the heat pump to the power supply, the rele-
vant VDE, EN and IEC standards are to be adhered to. Any fur-
ther connection requirements stipulated by the network opera-
tor must also be observed.
When connecting the heating system, all applicable regulations
must also be adhered to.
This unit can be used by children aged 8 and over and by per-
sons with limited physical, sensory or mental aptitude or lack of
experience and/or knowledge, providing they are supervised or
have been instructed in the safe use of the unit and understand
the associated potential dangers.
Children must not play with the device. Cleaning and user
maintenance must not be carried out by children without su-
pervision.

CAUTION!

!!

When operating or maintaining a heat pump, the legal
requirements of the country where the heat pump is operated
apply. Depending on the refrigerant quantity, the heat pump
must be inspected for leaks at regular intervals by a certified
technician, and these inspections must be recorded.

More information can be found in the accompanying log book.

1.4 Energy-efficient use of the heat 

pump

By operating this heat pump, you are helping to protect the en-
vironment. A prerequisite for energy-efficient operation is the
correct design of the heat source system and heating system.
It is particularly important for the efficiency of a heat pump to
keep the temperature difference between heating water and
heat source as small as possible. For this reason, it is advisable
to design the heat source and heating system very carefully. 

A

temperature difference of approx. one Kelvin (one °C) in-
creases the power consumption by around 2.5 %.

 When de-

signing the heating system, it should be borne in mind that spe-
cial consumers such as e.g. domestic hot water preparation
should also be taken into consideration and dimensioned for
low temperatures. 

Underfloor heating systems (panel heating)

are optimally suited for heat pump use on account of the low
flow temperatures (30 °C to 40 °C).
It is important to ensure that the heat exchangers are not con-
taminated during operation because this increases the temper-
ature difference, in turn reducing the COP.
Correct adjustment of the heat pump manager is also impor-
tant for energy-efficient use of the heat pump. Further informa-
tion can be found in the operating instructions of the heat
pump manager.

Содержание LA 60S-TU

Страница 1: ...Order no 452163 66 89 EN EN FD 0103 LA 60S TU Installation and Operating Instruction Air to Water Heat Pump for Outdoor Installation Glen Dimplex Deutschland Dimplex ...

Страница 2: ......

Страница 3: ...N 6 6 2 Connection on heating side EN 6 6 3 Electrical connection EN 7 7 Start up EN 8 7 1 General EN 8 7 2 Preparation EN 8 7 3 Procedure EN 8 8 Cleaning maintenance EN 8 8 1 Maintenance EN 8 8 2 Cleaning the heating system EN 8 8 3 Cleaning the air system EN 9 9 Faults troubleshooting EN 9 10 Decommissioning disposal EN 9 11 Device information EN 10 12 Product information as per Regulation EU No...

Страница 4: ...cal sensory or mental aptitude or lack of experience and or knowledge providing they are supervised or have been instructed in the safe use of the unit and understand the associated potential dangers Children must not play with the device Cleaning and user maintenance must not be carried out by children without su pervision CAUTION When operating or maintaining a heat pump the legal requirements o...

Страница 5: ...rrounding air is drawn in by the fan and fed through the evap orator heat exchanger The evaporator cools the air i e it ex tracts heat from it This extracted heat is then transferred to the working medium refrigerant in the evaporator The heat is brought to a higher temperature level by increasing its pressure with the aid of the electrically driven compressor It is then transferred to the heating...

Страница 6: ...e swung out after removing the lower front cover and loosening the fasten ing screw located in the upper left hand corner The switch box contains the supply connection terminals as well the power contactors and the soft starter unit 3 3 Heat pump manager Use the heat pump manager included in the scope of supply to operate the air to water heat pump The heat pump manager is a convenient electronic ...

Страница 7: ...xample Furthermore the heat pump should be set up so that the air outlet direction of the ventilator is perpendicular to the main wind direction to allow unrestricted defrosting of the evaporator The heat pump is designed for installation on even ground If the installation conditions differ installation on a platform or flat roof or there is a greater risk of the heat pump tipping over due to an e...

Страница 8: ... system must be flushed to remove any impurities residue from sealants etc Any accumulation of deposits in the liquefier could cause the heat pump to completely break down Once the heat pump has been connected to the heating sys tem it must be filled de aerated and pressure tested Consideration must be given to the following when filling the system Untreated filling water and make up water must be...

Страница 9: ...nection 3 lines cables must be routed to the heat pump in total A standard 5 core cable is used to connect the heat pump to the power supply The cable must be provided on site The conductor cross section is selected in accordance with the power con sumption of the heat pump see attachment Device Infor mation and the applicable VDE EN and VNB regulations An all pole disconnecting device with a cont...

Страница 10: ...y time 7 When all heat circuits are fully open and a return tempera ture of at least 22 C is maintained the heat pump start up is complete CAUTION Operating the heat pump at low system temperatures may cause the heat pump to break down completely 8 Cleaning maintenance 8 1 Maintenance To protect the paintwork avoid leaning anything against the device or putting objects on the device External heat ...

Страница 11: ...ved in the vicinity of the air intake and air outlet grids to ensure that the minimum air flow is maintained To ensure proper drainage from the condensate tray it must be regularly inspected and cleaned if necessary All panelling can be removed to allow accessing the inside of the device The two sash fasteners must be opened for this purpose The cover must then be slightly tilted forward and lifte...

Страница 12: ...g quantities 5 1 Device dimensions without connections5 H x W x L mm 2300 x 1900 x 1000 5 2 Weight of the transportable unit s incl packaging kg 870 5 3 Device connections for heating Inches Rp 2 5 4 Refrigerant total filling weight Type kg R407C 15 7 5 5 GWP value CO2 equivalent t 1774 27 5 6 Refrigeration circuit hermetically sealed yes 5 7 Lubricant total filling quantity Type litres POE RL32 3...

Страница 13: ...ow temperature applies to a set minimum heating water flow 3 The heat output and COP is reduced by approx 5 in lower operation 4 The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 55 C The specified sound pressure level represents the free sound area level The measured value can deviate by up to 16 dB A depending o...

Страница 14: ... Emissions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency ηwh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not determined by measurement nthen the default degradation is Cdh 0 9 not applicable For air to water heat pumps Rated air flow rate outdoors For water brine to water heat pumps Rated brine or water fl...

Страница 15: ...asservorlauf Ausgang aus Wärmepumpe R 2 2 Heizwasserrücklauf Eingang in Wärmepumpe R 2 3 Durchführungsbereich Elektroleitungen Kondensat 4 Optionale Durchführung Elektroleitungen 5 Optionale Durchführung Kondensat Frostschutz erforderlich Heating water flow Output from heat pump R 2 Heating water return flow Input into the heat pump R 2 Feedthrough area Electrical lines condensate Optional feedthr...

Страница 16: ...on en Pa Verflüssiger Condenser Condenseur 0 1 2 3 4 5 6 7 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 Lufteintrittstemperatur in C Air inlet temperature in C Température d entrée d air en C 35 Leistungszahl incl Pumpenleistungsanteil Coefficient of performance incl power input to pump Coefficient de performance y compris part de consommation de la pompe 45 55 0 5 10 15 20 25 30 35 40 45 50 55 60 65...

Страница 17: ...K Water outlet 0 2 K Sortie d eau 0 2 K Die maximalen Vorlauftemperaturen werden beim geforderten Mindestheizwasserdurchfluss erreicht The maximum flow temperatures are achieved at the specified minimum heating water flow Les températures départ maximales sont atteintes en cas de débit minimum d eau de chauffage donné Wassereintritt Water inlet Entrée d eau Bei Luft Wasser Wärmepumpen stellt die m...

Страница 18: ...EN 16 452163 66 89 EN FD 0103 www glendimplex de English LA 60S TU 15 Integration diagram 15 1 Hydraulic integration diagrams R2 2 ...

Страница 19: ...lve Temperature sensor Flexible connection hose Check valve Three way mixer Air to water heat pump Heat pump manager Buffer tank connected in series Hot water cylinder E9 Flange heater hot water E10 1 Immersion heater K20 Contactor for HG2 K21 Contactor for flange heater M15 Heat circulating pump for heating circuit 2 M16 auxiliary circulating pump M18 Hot water loading pump M22 Mixer for heating ...

Страница 20: ...nical support After sales service technical support and spare parts Assistance before and after installation of your equipment T 49 9221 709 545 F 49 9221 709 924545 Mon Thu 7 30 to 16 30 Fri 7 30 to 15 00 service dimplex glendimplex de Our 24 hr hotline is available for emergencies outside normal opening times Request after sales service on the internet www glendimplex de dienstleistungen dimplex...

Отзывы: