www.dimplex.de
E-9
English
12
12 Device Information
Device information for air-to-water heat pumps for heating purposes
1
Type and order code
LA 9K
LA 11K
LA 13K
LA 15K
2
Design
2.1
Model
Compact
Compact
Compact
Compact
2.2
Degree of protection according to EN 60 529 for compact devices
and heating components
IP24
IP24
IP24
IP24
2.3
Installation Location
Outdoors
Outdoors
Outdoors
Outdoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow/return flow
1
°C / °C
1. See operating limits diagram
Up to 65 / above
18
Up to 65 / above
18
Up to 65 / above
18
Up to 65 / above
18
Air
°C
-20 to +35
-20 to +35
-20 to +35
-20 to +35
3.2
Heat output / COP
at A-7 / W35
2
kW / ---
2. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting
capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: 2 °C external air temper-
ature and 55 °C heating water flow temperature.
5.5 / 2.6
6.6 / 2.7
7.7 / 2.7
9.4 / 2.7
at A2 / W35
2
kW / ---
7.2 / 3.1
8.0 / 3.1
9.2 / 3.1
12.1 / 3.1
at A2 / W50
2
kW / ---
6.6 / 2.4
7.6 / 2.4
8.7 / 2.4
11.0 / 2.4
at A7 / W35
2
kW / ---
9.3 / 3.6
10.3 / 3.8
11.8 / 3.7
15.4 / 3.6
at A10 / W35
2
kW / ---
9.8 / 3.8
10.9 / 3.9
12.5 / 3.9
16.4 / 3.7
3.3
Heating water flow
m³/h
0.8
1.0
1.1
1.4
3.4
Free compression of heat circulating pump (max. level)
Pa
46400
45000
42400
37300
3.5
Air flow rate
m³/h
3300
3300
3800
3800
3.6
Refrigerant; total filling weight
type / kg
R290 / 1.0
R290 / 1.0
R290 / 1.1
R290 / 1.25
3.7
Output of electric heating element (2nd heat generator)
kW
6.0
6.0
6.0
6.0
4
Dimensions, connections and weight
4.1
Device dimensions
H x W x L cm
112 x 127 X 73
112 x 127 X 73
112 x 127 X 73
112 x 127 X 73
4.2
Device connections to heating system
Inch
G 1'' external
G 1'' external
G 1'' external
G 1'' external
4.3
Weight of the transportable unit(s) incl. packing
kg
207
217
220
232
5
Electrical Connection
5.1
Nominal voltage; fuse protection
V / A
400 / 20
400 / 20
400 / 20
400 / 25
5.2
Nominal power consumption
2
A2 W35
kW
2.35
2.6
3.0
3.95
5.3
Starting current with soft starter
A
23
25
30
30
5.4
Nominal current
A2 W35 / cos
ϕ
A / ---
4.2 / 0.8
4.6 / 0.8
5.4 / 0.8
7.1 / 0.8
6
Complies with the European safety regulations
3
3. See CE declaration of conformity
3
3
3
7
Additional model features
7.1
Defrosting
Automatic
Automatic
Automatic
Automatic
Type of defrosting
Hot gas
Hot gas
Hot gas
Hot gas
Defrosting tray included
Yes (heated)
Yes (heated)
Yes (heated)
Yes (heated)
7.2
Heating water in device protected against icing
4
4. The heat circulating pump and the heat pump controller must always be ready for operation.
Yes
Yes
Yes
Yes
7.3
Performance levels
1
1
1
1
7.4
Control
Integrated
Integrated
Integrated
Integrated
7.5
Operation
Remote control
Remote control
Remote control
Remote control