7.3 Corrosion protection anode

The corrosion protection anode installed in the domestic hot
water cylinder should be electrically checked on a regular basis
(at least every two years after commissioning) and be replaced
as necessary. Electrical checking is carried out by means of a
suitable ammeter, without draining the cylinder.

Procedure:

1)

Unplug the PE cable from the protection anode tab.

2)

Connect the ammeter (0 to 50 mA) between the PE cable
and the tab.

3)

Evaluation of wear on the protection anode:
Measured value > 1 mA 

 protection anode is in working

order.
Measured value < 1 mA 

 protection anode must be tested

and/or replaced.

If electrical testing does not provide any clear results, a visual in-
spection of the protection anode by a technician is recom-
mended.
Should replacement of the protection anode [by a technician] be
necessary, the cylinder must be drained via the drainage valve
provided (to be fitted during installation - see Appendix).

ATTENTION!

Malfunctioning protection anodes reduce the service life of the device! 
(Electrically insulated magnesium anode with selenium complying with
DIN 4753 part 6)

8 Faults / troubleshooting 

(for the user)

ATTENTION!

Work on the domestic hot water heat pump is to be performed by
qualified personnel only!
Observe accident prevention regulations!

The heat pump will not operate!

Check the following:

Voltage is applied to the device

the intake air or ambient temperature is 

0 °C

The heat pump has not been switched off by the tempera-
ture controller

the hot water temperature has reached (or exceeds) 60 °C

Condensate cannot drain properly (there is water 

under the device)

Check the following:

The seal valve in the end of the condensate hose is contam-
inated or clogged, and clean if necessary; the valve can be
easily removed and replaced.

The air supply / air outlet is significantly reduced.

If the above suggestions cannot help you eliminate these faults,
please contact your technician or after-sales service partner.

9 Decommissioning

Tasks to be carried out:

Disconnect the domestic hot water heat pump from the
power supply.

Completely shut off the water circuit (domestic hot water,
cold water and circulation pipe) and drain the domestic hot

 

water cylinder

 through the drain valve.

10 Environmental 

requirements

During maintenance or decommissioning of the domestic hot
water heat pump, all environmental requirements regarding re-
covery, recycling and disposal of materials and components
must be observed in compliance with DIN EN378.

Содержание HPWH 300

Страница 1: ...HPWH 300 HPWH 300HE Hot Water Heat Pump for Outdoor Installation English Installation and Operating Instructions FD 9501...

Страница 2: ...N 4 4 Installation EN 5 4 1 Installation location EN 5 4 2 Installation EN 5 5 Assembly EN 5 5 1 Connecting the water pipes EN 5 5 2 Connecting the condensate hose EN 6 5 3 Electrical connection EN 6...

Страница 3: ...ealand a TEMPER ING VALVE must be fitted by the installer The following are not permitted It is not permissible to operate the device The refrigerating system meets the requirements of ISO 5149 3 2014...

Страница 4: ...mestic hot water temperature is higher than the temperature achievable by the heat pump approx 60 C it can be raised to a max of 85 C by means of the heating element NOTE When the domestic hot water t...

Страница 5: ...ts the evaporator from freezing 3 Storage and transport 3 1 General The domestic hot water heat pump should always be stored and transported packaged in an upright position without being filled with w...

Страница 6: ...e must be provided as shut off facility to avoid unnecessary energy losses Circulation is enabled according to use time or requirement control The nominal pipe widths for the on site sanitary installa...

Страница 7: ...If the supply cord is damaged it must be replaced by a special cord or assembly available for the manufacturer or its service agent 6 Commissioning 6 1 Domestic hot water system ATTENTION The domesti...

Страница 8: ...r heat pump possible fan coasting must be considered General The domestic hot water heat pump is virtually maintenance free Furthermore a one off visual inspection for possible leaks in the water syst...

Страница 9: ...4753 part 6 8 Faults troubleshooting for the user ATTENTION Work on the domestic hot water heat pump is to be performed by qualified personnel only Observe accident prevention regulations The heat pum...

Страница 10: ...nection 6 1 Degree of protection IP 24 IP 24 6 2 Connection voltage 1 N PE 230 V 50 Hz 1 N PE 230 V 50 Hz 6 3 Fuse max A C16 C16 6 4 Heat pump power consumption cos A 0 8 0 8 6 5 Supplementary electri...

Страница 11: ...EN 10 451903 66 18 FD 9501 www dimplex com au English HPWH 300 HPWH 300HE...

Страница 12: ...drawing A II 2 Integration Diagram A III 2 1 Process circuit diagram A III 2 2 Legend A III 2 3 Hydraulic integration diagram A IV 2 4 Legend A IV 2 5 Heat Exchanger Integration Diagram for Thermal S...

Страница 13: ...JHU RXWSXW 5 H WHUQDO WKUHDG HDW H FKDQJHU LQSXW 5 H WHUQDO WKUHDG LUFXODWLRQ SLSH 5 H WHUQDO WKUHDG RW ZDWHU RXWOHW FRQQHFWLRQ 5 H WHUQDO WKUHDG RQGHQVDWH KRVH LQQHQ 6HDO YDOYH OHFWULFDO KHDWLQJ HOHP...

Страница 14: ...3 14 15 Compressor Evaporator Hot water cylinder with Liquifier High pressure switch Check valve Air inlet temperature sensor R1 Filter dryer Expansion valve Cylinder temperature sensor Heating elemen...

Страница 15: ...ng line drain line of the valve must not be blocked 8 Circulation pump 9 Outlet No connections for second heat generator required i e no heating water flow and no heating water return flow for hot wat...

Страница 16: ...egration Diagram for Thermal Solar Installation HDW H FKDQJHU HDW H FKDQJHU ORZ 5HWXUQ IORZ KHFN YDOYH 7DS 7KHUPRPHWHU URP WKH FROOHFWRU 6DIHW YDOYH QWO IWXQJ H DHUDWLRQ 3XUJH 3UHVVXUH JDXJH DWFKPHQW...

Страница 17: ...A VI 451903 66 18 FD 9501 www dimplex com au Appendix HPWH 300 HPWH 300HE 3 Circuit Diagrams 3 1 Last Load...

Страница 18: ...www dimplex com au 451903 66 18 FD 9501 A VII Appendix HPWH 300 HPWH 300HE 3 2 Control...

Страница 19: ...essor F17 Safety temperature limiter E1 H1 Electric heater indicator lamp J1 Digital inputs outputs U 230 V J3 Analogue inputs screw terminals K1 Compressor load relay K2 Starting relay for M1 K4 Load...

Страница 20: ...www dimplex com au 451903 66 18 FD 9501 A IX Appendix HPWH 300 HPWH 300HE...

Страница 21: ...Glen Dimplex Australia Pty Ltd 1 21 Lionel Road Mount Waverley VIC 3149 www dimplex com au ph 1300 556 816 fax 1800 058 900 Subject to alterations and errors...

Отзывы: