background image

20

8  Maintenance

The maintenance of this appliance covers the critical ar-

eas of the Domestic Hot Water Cylinder, the Heat Pump 

Module, Air Connections and Electrical Connections. 

All maintenance on this product must 

be undertaken by a suitably qualified 

and trained technician.

!

8.1   DHW Cylinder

After servicing, complete the relevant Service Re-

cord section of the Benchmark Checklist located on 

the inside back pages of this document. To meet 

with warranty requirements the cylinder must be 

serviced annually. 

When draining the tank, ensure that 

there is a large enough air inlet at the 

top to avoid any depression in the tank; 

failure to do so will invalidate the war-

ranty.

!

1.

 

Draw some water from cold water tap and retain 

in container. 

2. 

Isolate cold water mains supply from cylinder. 

3. 

Briefly open temperature and pressure relief valve 

to assure safe discharge and check that valve is 

not dripping when closed. 

4. 

Briefly open the expansion relief valve to assure 

safe discharge and check that valve is not dripping 

when closed. The expansion relief valve should be 

operated regularly to remove lime deposits and to 

verify that it is not blocked. 

5. 

Open hot water tap and release remaining pres-

sure from unit. 

6. 

If the system is drained completely for an inter-

nal inspection, ensure the hot water tap remains 

open, connect a hose to the drain valve and en-

sure a safe discharge. 

7. 

Note the set pressure of the pressure reducing 

valve. Remove cartridge and clean strainer in wa-

ter provided in container. Re-assemble pressure 

reducing valve ensuring the correct pressure is 

set. 

8. 

Periodically the immersion heater should be re-

moved  cleaned  and  the  unit  flushed  out.  If  the 

system is drained for internal inspection Check 

the O-ring seal for damage and replace if neces-

sary. A torque of 40 Nm is recommended when 

tightening up the immersion after it has been re-

moved and refitted.

9. 

Check electrical wiring connections and the condi-

tion of the cable of the immersion heater and the 

thermostat. 

10. 

The immersion heater boss can also be used for 

access to view the internal components of the cyl-

inder. 

11. 

Re-commission unit (see chapter 7.1).

8.2   Heat Pump

Any work on the refrigerant circuit 

must be carried out by a qualified 

professional with an F Gas Category 1 

certificate of aptitude. 

It is strictly prohibited to release refrig-

erant into the atmosphere. The refriger-

ant must be collected before any work is 

carried out on the circuit.

1.  

Remove insulation from ducting as well as the duct-

ing itself and thus remove the hood from the unit to 

expose the compressor, heat exchanger etc.

2.  

Check the compressor for ice formation. 

3.  

Check the circuit for leak-tightness by carrying out 

a test of the refrigeration components with an ap-

propriate R290 sniffer.

4.  

Check whether the components of the refrigerant 

circuit show any signs of rust or traces of oil. 

5. 

Check the unit’s components for wear or defective 

items. 

6. 

Inspect for build-up of debris in ducting and hood, 

remove if necessary. 

7. 

The heat exchanger should be examined for dirt 

and dust and cleaned with warm water carefully to 

avoid damaging the fins. Make sure that the air can 

circulate between the fins and around the product. 

8. 

Check that the cables are securely seated on the 

connection terminals. 

9. 

Check that the fan runs freely.

!

!

8.3  Air intake & Exhaust

1. 

Both the exhaust and air intake vents must be 

inspected and cleared of any debris stuck in the 

vents.  

2. 

Ensure the evaporator is checked at least once a 

year, more depending on the cleanliness of the air 

8.4  Heat Pump Condensation

1. 

To check that condensation is draining correctly: 

    -  Remove upper cover (see Section 6.9.1). 

    -  Check for blockages in the drainage hole. 

    -  Clean the condensate recovery container, were de-

posits from air intake may have gathered. 

    -  Clean the flexible draining hose. 

2. 

The pressure limiting device must be switched 

on regularly to eliminate limescale and check for 

blockages. 

3. 

Check that all hydraulic connections on the heat 

pump water heater are watertight.

4. 

The condensate drain should be inspected to en-

sure the red plug has been removed and unre-

stricted draining of condensation is allowed.

Содержание EDL200UK-630RF

Страница 1: ...Air Source Heat Pump Water Heater Installation and User Instructions RD01144 2 Important This manual must be left with user after Installation Edel RF...

Страница 2: ...ture reference Installers are required to carry out installation commissioning and ser vicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot Water I...

Страница 3: ...Electrical Connections 11 6 9 1 1 Electricity Provider Contact 11 6 9 1 2 Connecting the PV Function 11 7 Set Up and Use 12 7 1 Commissioning 12 7 2 Using your Hot Water Heat Pump 13 7 3 Control Box 1...

Страница 4: ...and or user This appliance can be used by children aged 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given s...

Страница 5: ...installation If in any doubt please call the appropriate help desk Disregarding the instructions given in this manual in its entirety and any relevant regulations standards and codes of practice will...

Страница 6: ...must be taken when placing the water heater in a garage or outbuilding All exposed pipework must be correctly insulated to avoid frost damage The position and orientation of the water heater should b...

Страница 7: ...2 15 22 9 0 8 28 18 1 0 35 27 1 4 G3 4 22 28 9 1 0 35 18 1 4 42 27 1 7 G1 28 35 9 1 4 42 18 1 7 54 27 2 3 Dimplex recommend an annual maintenance inspection is carried out on the water heater In hard...

Страница 8: ...on vessel membrane before filling the cylinder The pre charge should be greater than or equal to 3 bar 6 2 Cold Water Inlet with Inlet Group The discharge pipe should not be connected to a soil discha...

Страница 9: ...dwellings occupied by people with impaired vision or mobility con sideration should be given to the installation of a suita ble safety device to warn when discharge takes place e g electronically oper...

Страница 10: ...2 5 25 0 External terminal X 1 51 0 51 0 Total System Calculated Pressure Drop 320m3 hr 207 7 Pa 6 7 1 Worked Example The pressure drop information provided is for 160mm semi rigid Ubbink ducting othe...

Страница 11: ...hoose load shedding level 1 the electrical back up is prevented from running If you choose load shedding level 0 both the electrical back up and the heat pump will be prevented from running see Sectio...

Страница 12: ...ischarge and check after closing that valve is not dripping 9 Open expansion relief valve to ensure proper discharge and check after closing that valve is not dripping 10 Check all shower outlets toil...

Страница 13: ...ature remains in the authorised 7 C to 35 C range Outside of this range electrical backup ensures that the domestic hot water is heated The domestic hot water temperature provided by the heat pump is...

Страница 14: ...This function can be programmed to run between 1 and 99 days and is effective as soon as the number of days has been confirmed HOLIDAYS HOLI RETURN 8 Set number of days in standby mode Enter HOLIDAY...

Страница 15: ...exisitng programme MONDAY Set Up and Use Frost PT Frost Protection Mode ECO Heat Pump Only Running CONF Heat Pump Only Running electrical back up if needed 7 10 Programming Heating time for the tank v...

Страница 16: ...al until the screen displays Inst Menu Press the Clock and Menu buttons simultaneously Keep both buttons pressed down until the screen goes blank 7 11 1 PV Mode Setting Description Unit Range Factory...

Страница 17: ...emperature reaches 43o C The heat pump will complete the remaining charge to set temperature 7 11 2 3 Minimum Temperature To C Min No To C Min 43 o c Select Mode Enter It is possible to allow the oper...

Страница 18: ...f locking for accessing the menus In the Installer menu turn the dial to Locking LOCKING LOCKING NO Select No Enter NO Locking is not activated but manual locking is possible by pressing Menu for 3 se...

Страница 19: ...ers The Counters menu shows the number of start ups from the heat pump and the electrical backup In the Installer menu turn the dial to Counters Counter No 1 Number of start ups from the heat pump Cou...

Страница 20: ...heater and the thermostat 10 The immersion heater boss can also be used for access to view the internal components of the cyl inder 11 Re commission unit see chapter 7 1 8 2 Heat Pump Any work on the...

Страница 21: ...ich would reduce the cross sectional area of the conductor 4 Ensured the conductors are tightly and securely connected to the controls or immersion heater 5 Ensured the bared conductors are correctly...

Страница 22: ...higher than the volume in the tank The time period the appliance operates is not too short 12hrs minimum if connected to piping The water temperature is not set too low Condensates are not drain ing T...

Страница 23: ...045 2 Expansion vessel fixing kit R00094 2 DN16 3 4 BSP x 1000 flex pipe R00095 1 1 2 BSP T P valve R00020 1 15 x 22 straight PE tundish R00047 1 Temp sensor 25 C 1243950 C3S PCB Controller 1244096 70...

Страница 24: ...aintained continuously at the standard set temperature if no signal or control is connected to the external control switch OVER PRESS Heat pump pressure too high No water in tank Water is too hot 75 C...

Страница 25: ...being in contact with a part which vibrates Replace expansion valve The compressor is not working and safety temperature is activated Weakness in compressor Replace compressor ERR 02 Incorrect temper...

Страница 26: ...mation 9 1 Warranty Limits Please read the following statements carefully as it affects your warranty Please ensure that the installer has fully completed the Benchmark Checklist on the inside back pa...

Страница 27: ...d Water supply being other than cold domestic water such as rainwater or water from a well or which has particularly hostile or abnormal properties which do not comply with the national rules and curr...

Страница 28: ...28 B C D E A 152 Figure 11 Edel Air Source Water Heater Dimensions for reference only Technical Data and Product Fiche 10 Technical Data and Product Fiche Air Intake Air Discharge...

Страница 29: ...d Product Fiche Cylinder is tested in accordance with EN12897 2006 GDC Group Ltd Edel Air Source Water Heater Product Fiche Reference EDL200UK 630RF EDL270UK 630RF Load Profile Primary M L Energy Rati...

Страница 30: ...2 kW 240V Ventilation Air flow rate 320 to 400 m3 h Air temperature 7 C to 35 C Max air pipe length rigid piping 20m in total intake and rejection Condensates flow rate 0 3 L h Condensates drainage p...

Страница 31: ...31 Power Supply Green Yellow Black Blue Brown Black Blue Blue Black Sensors Black Black Black Black Blue Black Blue Brown Black Brown Communication Bus Display 1 2 Red Fan B1244454 F HPS DV...

Страница 32: ...Red Blue Blue Black Brown Blue Green Yellow Blue Black Blue Blue Red Red Blue HTS WTS HPS High Pressure Switch C25 Compressor Start Capacitor C2 Fan Capacitor C4 Valve F Fan DV Defrost Valve RE Immer...

Страница 33: ...33 Notes...

Страница 34: ...and pressure relief valve and expansion valve been fitted and discharge tested Yes No The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes A...

Страница 35: ...mments Signature SERVICE 3 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 4 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 5 Date Engineer Nam...

Страница 36: ...plex reserve the right to revise products literature and guarantee terms without prior notice due to a policy of continuous improvement www KIWA co uk www HWA co uk To speak to customer services pleas...

Отзывы: