GENERAL VIEW OF THE ATS UNITS
KS ATS 3/18 HD, KS ATS 1/40 HD, KS ATS 4/63 HD
3
OPERATING THE ATS UNIT
4
OPERATING PROCEDURE
5
1. Main power indicator
2. Load connection indicator
3. Generator power indicator
4. ATS unit main switch
5. Control cable connector
6. Cable entry openings
7. Programmable controller
8. Fuse
9. Generator emergency stop button
Img. 1
ATS UNIT FUNCTION
ATS UNIT FUNCTION
The ATS unit automatically starts the generator and switches over power consumers to it when the main
power supply is deenergized.
Connect the ATS unit as shown in Figs. 3-6 and according to the diagrams in the Appendix.
AUTOMATIC MODE
AUTOMATIC MODE
Set the “POWER SWITCH” to the “ON” position, and then press the “AUTO” button. The “AUTO” light
indicator indicates that the ATS system is in automatic mode.
When the main power supply is disconnected, the ATS system automatically starts the generator in 12
seconds (time can be programmed). After 6 seconds (the time can be programmed) following the generator
startup, the system will switch over power consumers to the backup power source (generator).
In case of unsuccessful startup, the ATS system attempts to start the generator three times with an interval
of 6 seconds between the attempts. If all three attempts are unsuccessful, the ATS unit will stop trying to
start the engine and signal an error.
When the main power supply is turned on, the ATS system switches over power consumers to the main
power supply and turns off the power generator in 12 seconds (time can be programmed).
Use the control cable to connect the ATS unit to the power
generator; the generator must have a special connector
for connecting the ATS.
PLEASE NOTE!
1
7
9
8
2
3
4
5
6
GE
GENERATOR STOP IN THE “AUTO” POSITION
NERATOR STOP IN THE “AUTO” POSITION
If the generator was started in the “AUTO” position, set the “POWER SWITCH” to the “OFF” position to stop
it. The generator will stop immediately, or press the emergency stop button.
MANUAL MODE
MANUAL MODE
If it becomes necessary to start the generator without using the ATS automatic mode, press the manual
mode button first and then press the “START” button to start the generator. To stop the generator, press
the “STOP” button.
BATTERY
BATTERY
The ATS unit battery is charged automatically. The maximum charging current is 2A.
www.ks-power.de/en
|
3