5
SCN Sensors Installation Instructions
SCN Sensors
ENGLISH
Install SCN Hardware
SCN-I Installation
Review SCN-I dimensional drawings (Illustration 5a).
Remove extra serial number label and place in correct
install location in the sticker map or book (Illustration 4).
Detach the lens assembly by turning it
counter-clockwise.
Remove the hex nut.
The SCN-I requires a 0.5 inch (pg-7) trade size knockout
(1.3 — 1.4 inch / 33 — 36 mm hole) for proper mounting
and sealing.
Install the SCN-I module inside the luminaire housing,
with the threaded nipple extending outside the
luminaire housing through the opening created in the
previous step.
Secure the housing using the supplied hex nut. Tighten
the hex nut (Illustration 5b).
Re-connect the lens assembly, turning it clockwise until
the lens assembly stops rotating.
Make power and data connections (see Make Power
and Data Connections section).
Install the third-party luminaire as per the
manufacturer’s instructions.
Note:
The SCN-I is designed to install within a
third-party luminaire housing, with the sensor optic
extending externally. Be sure to install the gasket and
hex nut in the correct order (Illustration 5b).
SCN-R Installation
Review SCN-R dimensional drawings (Illustration 6a).
Ceiling Mount (Illustration 6b)
•
Remove extra serial number label and place in
correct install location in the sticker map or book
(Illustration 4).
•
Remove the plastic bezel.
Note:
Place your thumb on the notch in the bezel
and pull away to release.
•
Using the metal mounting plate as a template, trace
the inner profile and the screw holes and then cut
the ceiling tile using an appropriate saw.
•
Insert the sensor housing up through the hole in the
ceiling tile, place the mounting plate on the back of
the ceiling tile around the sensor housing, and then
secure using the (2x) supplied Phillips screws.
Note:
Place the flat side of the collar against the tile.
•
Replace the bezel.
•
Make power and data connections (see Make Power
and Data Connections section).
Junction Box Mount (Illustration 6c)
•
Remove extra serial number label and place in
correct install location in the sticker map or book
(Illustration 4).
•
Remove the plastic bezel.
Note:
Place your thumb on the notch in the bezel
and pull away to release.
•
Discard the metal mounting plate.
•
Make power and data connections (see Make Power
and Data Connections section).
•
Insert the sensor housing into the 4 inch (101 mm)
round junction box and then secure using the (2x)
supplied Philips screws.
•
Replace the bezel.
SCN-S Installation
Review SCN-S dimensional drawings (Illustration 7a).
Note:
The SCN-S is IP65-rated and designed for use in
damp or wet environments. Ensure that the included
mounting gasket is intact before installation.
Ceiling Mount (Illustration 7b)
•
Remove extra serial number label and place in
correct install location in the sticker map or book
(Illustration 4).
•
Remove the plastic bezel.
Note:
Squeeze the two flat areas on the edge of the
bezel and pull away to release.
•
Cut a 0.5 inch (7 mm) or greater hole in the ceiling
panel and run the power and data wires through the
opening.
•
Make power and data connections (see Make Power
and Data Connections section).
•
Secure the housing using suitable fasteners
(supplied by installer).
•
Replace the bezel.