FP-570T User's Manual
3-2
Installation and Wiring
• For easier maintenance and operation, and improved ventilation, be
sure the FP unit is mounted at least 100 mm away from any adjacent
structures or objects.
• The FP uses natural ventilation through its outer shell for cooling.
When installing the unit horizontally or sideways (portrait style), use a
fan or air conditioning unit to prevent overheating.
Vertical Installation
Front
Side
Horizontal Installation
•
When installing the FP sideways, place it so that the Power Terminals point
upwards.
•
Check that heat from surrounding equipment will not cause the FP to overheat.
•
Do not use the 100V FP-570-TC11 in an environment that exceeds 40
o
C,
and the 24V FP-570-TC21-24V in an environment that exceeds 45
o
C.
•
Ensure this unit is located as far away as possible from electromagnetic
circuits, non-fuse type breakers, and other equipment that can cause arcing.
•
When installing the FP unit in a panel with an angled face, the face should
not incline either backwards or forwards more than 30
o
.
less than 30
o
Sideways Installation