13
(3) Unscrew the four attachment screws
located at the top and bottom of the
front module.
(4) Detach the control box from the front
module.
2.
Installing the front module and the
control box
Install the control box to the front module
in the reverse order of the uninstallation
steps. The necessary torque is 0.5N•m to
0.6N•m in every step.
Wiring
• To avoid an electric shock, prior to con-
necting the PL unit’s power cord terminals
to the power terminal block, confirm that
the PL unit’s power supply is completely
turned OFF, via a breaker, or similar unit.
• Any other power level can damage
both the PL and the power supply.
• Since DC type has no power ON/OFF
switch, be sure to attach a breaker-
type switch to its power cord.
• When the FG terminal is connected, be
sure the wire is grounded.
1.
Wiring the AC type power supply cable
• When the FG terminal is connected, be
sure the wire is grounded. Not
grounding the PL unit will result in
excessive noise. Use your country’s
applicable standard for grounding.
Power Cord Specifications
Use copper conductors only.
Wiring
When connecting the power code, use the
following items when performing wiring.
(Items are made by Phoenix Contact.)
• Accompanying power supply connector is
a CA7-ACCNL-01 of Pro-face or FKC2,5/
3-STF-5,08 of Phoenix Contact.
Connecting the Power Cord
(1) Confirm that the power is not supplied to
the PL unit.
Power Cord
Diameter
0.75 to 2.5mm
2
(18 - 12 AWG)
Conductor Type Simple or Stranded Wire
*1
*1 If the Conductor’s end (individual) wires are not
twisted correctly, the end wires may either short
against each other, or against an electrode.
Conductor
Length
Recommended
Driver
SZS 0.6x3.5 (1205053)
Recommended
Pin Terminals
AI 0.75-10GY(3201288)
AI 1-10RD (3200182)
AI 1.5-10BK (3200195)
AI 2.5-12BU (3200962)
Recommended
Pin Terminal
Crimp Tool
CRIMPFOX ZA3
(1201882)
10mm [0.39in]
Содержание APL3600-TA
Страница 18: ...18 ...