DSE Model 5220 Automatic Mains Failure & Instrumentation System Operators Manual
42
057-012 5220 OPERATING MANUAL ISSUE 5.1 18/06/2007 AM
Generator settings – Voltage/frequency
Trip
Return
Under volts trip
#
184V AC
N/A
Under volts pre-alarm
#
196V AC
207V AC
Over volts pre-alarm
#
253V AC
265V AC
Over volts trip
#
276V AC
N/A
Under frequency trip
#
40.0 Hz
N/A
Under frequency pre-alarm
#
42.0 Hz
45.0 Hz
Over frequency pre-alarm
#
55.0 Hz
52.0 Hz
Over frequency trip
#
57.0 Hz
N/A
Generator settings – Current/power
Value
Generator CT primary
600 A
Generator full load rating
500 A
Delayed overcurrent
#
100% ( 500 A )
Trip Curve
36
Engine settings – Crank disconnect
Value
Crank disconnect on generator frequency
21.0 Hz
Crank disconnect oil pressure
<Disabled>
Check oil pressure prior to starting
Yes
Engine settings – speed
Value
Underspeed trip
#
1250 RPM
Underspeed prealarm
#
1350 RPM
Overspeed prealarm
#
1650 RPM
Overspeed trip
#
1750 RPM
Overspeed overshoot
0%
Plant battery settings
Trip
Return
Under volts warning
#
8.0 V DC
9.0 V DC
Over volts warning
#
33.0 V DC
32.0 V DC
Charge alternator warning
#
8.0 V DC
N/A
Exercise scheduler settings
Value
Enable exercise scheduler
No
Comms
Value
Site identity
Genset ID
Modem mode
No modem
Modem init (not auto answer)
+MS=11,1,,S7=60S0=0&S0&C1&D3
Modem init (auto answer)
+MS=11,1,,S7=60S0=2&S0&C1&D3
Modem Hang
H0
Master inactivity timeout
0