DSP-100 User Manual
Page 19 of 25
DSP100_MAN_A
For the eight sensitivities, the thresholds, switch settings, and response times are:
Level -
∆L/L
S1
S2
S3
Response Time
Lowest
0
1.28% Off Off Off
88ms ±12ms
1
.64%
On Off Off
88ms ±12ms
2
.32%
Off On Off
88ms ±12ms
3
.16%
On On Off
88ms ±12ms
Normal
4
.08%
Off Off On
88ms ±12ms
5
.04%
On Off On
88ms ±12ms
6
.02%
Off On On
88ms ±12ms
Highest
7
.01%
On On On
176ms ±24ms
Delay DIP Switches
Delay is the time added after a vehicle arrives in the detection area but before the output is activated. During the
delay interval the output relay will remain de-activated, requiring that the vehicle stay in the detection area for
the full delay time before activating the output. This is useful at sites where right turns on red are allowed. This
allows a vehicle to arrive at a red signal, come to a full stop, and proceed to make a right turn without the detector
ever activating and placing a call into a phase. This interval is indicated by the red Detect LED blinking slowly at
200 milliseconds on followed by 200 milliseconds off repeatedly until the interval is complete. Delay time can be
set from 1 second to 63 seconds in 1 second increments. The following table shows the switch settings for the
various possible time values.
1
2
4
8
16 32
1
2
4
8
16 32
1
2
4
8
16 32
1
2
4
8
16 32
0
Off Off Off Off Off Off
16
Off Off Off Off On Off
32
Off Off Off Off Off On
48
Off Off Off Off On On
1
On Off Off Off Off Off
17
On Off Off Off On Off
33
On Off Off Off Off On
49
On Off Off Off On On
2
Off On Off Off Off Off
18
Off On Off Off On Off
34
Off On Off Off Off On
50
Off On Off Off On On
3
On On Off Off Off Off
19
On On Off Off On Off
35
On On Off Off Off On
51
On On Off Off On On
4
Off Off On Off Off Off
20
Off Off On Off On Off
36
Off Off On Off Off On
52
Off Off On Off On On
5
On Off On Off Off Off
21
On Off On Off On Off
37
On Off On Off Off On
53
On Off On Off On On
6
Off On On Off Off Off
22
Off On On Off On Off
38
Off On On Off Off On
54
Off On On Off On On
7
On On On Off Off Off
23
On On On Off On Off
39
On On On Off Off On
55
On On On Off On On
8
Off Off Off On Off Off
24
Off Off Off On On Off
40
Off Off Off On Off On
56
Off Off Off On On On
9
On Off Off On Off Off
25
On Off Off On On Off
41
On Off Off On Off On
57
On Off Off On On On
10
Off On Off On Off Off
26
Off On Off On On Off
42
Off On Off On Off On
58
Off On Off On On On
11
On On Off On Off Off
27
On On Off On On Off
43
On On Off On Off On
59
On On Off On On On
12
Off Off On On Off Off
28
Off Off On On On Off
44
Off Off On On Off On
60
Off Off On On On On
13
On Off On On Off Off
29
On Off On On On Off
45
On Off On On Off On
61
On Off On On On On
14
Off On On On Off Off
30
Off On On On On Off
46
Off On On On Off On
62
Off On On On On On
15
On On On On Off Off
31
On On On On On Off
47
On On On On Off On
63
On On On On On On
Extension DIP Switches
Extension is the time added after a vehicle leaves the detection area. During this interval, the output will remain
activated. If another vehicle arrives during this extension interval, the remainder of the extension time is canceled
and the detector returns to the normal presence state. This interval is indicated by the red Detect LED blinking
fast at 50 milliseconds on followed by 50 milliseconds off repeatedly until the interval is complete. Extension time
can be set from 0.25 seconds to 15.75 seconds in 0.25 second increments. The following table shows the switch
settings for the various possible time values.