SAFETY STANDARDS

  

Safety important instructions. 

 

This symbol warns that failure to comply with the prescription leads 

to a risk of electric shocks. 

 

This symbol warns that failure to comply with the prescription leads to a 

risk of injury/damage to persons/objects. 

Before installation and use of the product: 

read this manual completely and thoroughly 

Check that the 

nameplate data

 are those desired and appropriate to the system, 

and in particular that the 

rated current of the motor

 is compatible with the 

rated 

current of the inverter

 

Installation and maintenance must be carried out by qualified staff, responsible 

for performing the hydraulic and electric connections according to the applicable 

Standards in force 

The manufacturer declines all responsibility for damage deriving from improper 

use of the product and is not liable for damage caused by maintenance or repairs 

that are carried out by unqualified staff and/or using non-original spare parts 

The use of non-original spare parts, tampering or improper use, make the 

product warranty null and void. 

During first installation or when carrying out maintenance make sure that:  

the electric power supply network is not live

 

The power supply network is equipped with protections and in particular of 

high-

sensitivity differential switch 

(30 mA in class A for domestic application, class 

B for industrial applications) and grounding comply with the 

Standards. 

Before removing the inverter cover

 or starting interventions on it, the system 

must be disconnected from the mains electricity and you must wait for 5 mins 

until the intermediate circuit condensers, have the time to discharge via the built-

in discharge resistors. 

do not disconnect the pumps if STEADYPRES is in operation; before you 

disconnect the pumps, stop the control and disconnect the power supply.

 

WARNING: out of service (flashing red LED) STEADYPRES remains in tension; 

prior to any work on the pump or inverter is required, cut off power from the 

group.

 

Emergency stop 

An emergency stop can be performed while the inverter is running, by pressing the 

START/STOP key. 
In parallel inverters installations, only the MASTER inverter stops the whole system. 

EN 

Содержание STEADYPRES 2.0 M/M 11

Страница 1: ...spare parts tampering or improper use make the product warranty null and void During first installation or when carrying out maintenance make sure that the electric power supply network is not live Th...

Страница 2: ...ASTER and SLAVE 36 o Alarms 37 PART 2 OPERATOR S AND MAINTENANCE MANUAL o General remarks 38 o Working limits 39 o Technical data 39 o Dimensions and weight 40 o Product identification code 40 o Surge...

Страница 3: ...the inverter in a place o protected from the elements o ventilated free from excessive humidity or excessive dust o as close as possible to the pump o make sure that does not receive harmful vibration...

Страница 4: ...sinusoidal filter It aids smooth running of motors eliminating negative effect of voltage peaks GND L N GND V W U LINE MOTOR N L SINGLE PHASE IN line SINGLE PHASE OUT motor M M Pump supply voltage 23...

Страница 5: ...ps 4 e 5 In applications with parallel inverters the wiring must be carried out on the MASTER RS485 SIGNAL CONNECTION 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 Connect the termina...

Страница 6: ...history etc TEST mode only in OFF mode TEST mode allows you to start and stop the pump in manual mode START STOP button and change the frequency in steps of 1 Hz It also allows to control the operatin...

Страница 7: ...Y FOR POWER FACTOR only T T models TP RESTART INTERVAL FOR DRY RUNNING TF STOP DELAY FOR NO FLOW RF INVERTER REACTIVITY FS MODULE SWITCHING FREQ US NO GRIP STARTUPS EI INPUT SIGNAL EO OUTPUT SIGNAL AI...

Страница 8: ...rent of the motor At low supply voltages the current set should leave a margin eg 15 to compensate for the low voltage m u Default Min Max Step M M 8 5 A 8 5 1 8 5 0 1 M M 11 A 11 1 11 0 1 M M 16 A 16...

Страница 9: ...nning conditions CAUTION high values of the stop delay may damage the pump sec 10 1 100 1 PF 50 MINIMUM POWER FACTOR only T T models Sets the minimum value for the power factor below which the inverte...

Страница 10: ...T there is at least one operating pump EO 3 recirculation activates the relay output time intervals defined by param AI AI 60 RECYCLE FUNCTION Sets the output activation interval clean contact type co...

Страница 11: ...FI Shows the instantaneous value of the power factor only T T models Tm 50 POWER MODULE TEMPERATURE Displays the inverter s electronic module temperature C Ti 30 INVERTER BOX INTERNAL TEMP Displays th...

Страница 12: ...he operating parameters by pressing the keys To stop the TEST press the A START STOP button PRIMING AND STARTING UP Do not run pumps dry Before starting the pump make the filling of all pumps In the p...

Страница 13: ...rive continues to run the error is reset below 60 C OVER TEMP BOX only T T mod The temperature inside the inverter has reached 80 C the inverter stops the pump the error is reset below 60 C and the dr...

Страница 14: ...s during starts and operation energy saving Allows the selection of the power supply and output voltage PART LIST 1 control system 2 removable electric connector 3 I O power cable bushing 4 power boar...

Страница 15: ...nverter to vary the flow rate TECHNICAL DATA main voltage supply 230 10 Vac single phase models M M e M T WARNING IN CASE OF LOW VOLTAGE NOMINAL VALUE 10 OVERCURRENTS CAN OCCUR DURING STARTING OR FULL...

Страница 16: ...under pressure to minimize the start up of the pumps it is essential in the presence of small system leakages absorbs overpressures from the system the minimum tank volume in liters for diaphragm mode...

Страница 17: ...cable and the motor cable must be sized to curb any power voltage drop within 3 The power supply cable and the motor cable must be suitably shielded to comply with EMC standards In case of long cable...

Страница 18: ...you can view the status parameters For visualization of the operating parameters see QUICK INSTALLATION GUIDE LIGHT SIGNALS keyboard ON OFF BLINKING POWER STATUS STEADYPRES does not detect power supp...

Страница 19: ...rrect direction of rotation check the correct sizing of the wires CURRENT LIMIT Serious overcurrent absorption which inverter cannot cope with Make sure the motor pump is not blocked reduce the motor...

Страница 20: ...connect the inverter main power supply and wait 2 minutes capacitors discharge Open the front cover and disassembly the pressure sensor and the control board as shown below Install the new control boa...

Страница 21: ...ton SET TEST to confirm the zero pressure SP 5 0 Start the pump by pressing START button the pump starts at the minimum frequency SP 5 0 Increase the frequency of the pump by pressing the button until...

Страница 22: ...KIT 4 KIT 3 KIT 5 6 7 7 8 10 N Description Q ty KIT 1 Cover Kit with keyboard 1 KIT 2 Pressure sensor Kit 1 KIT 3 Non return valve flow sensor Kit 1 KIT 4 Cable bushing cover Kit 1 KIT 5 Expansion bo...

Страница 23: ...ce in the countries where the unit is used Do not disperse pollutant parts in the environment DECLARATION OF CONFORMITY We declare under our own responsibility that the product in question is in compl...

Отзывы: