53
Pictures for illustra tive purpos es
E
LECTRO
V
AP
RTH-LC
Maintenance - Valves
The inlet valve should be m aintained every 6 months as a
m inimum and after 50 hours operation.
Isolate the w ater supply and remove the w ater supply hose from
the valve.
Disconnect the electrical w ires from the coil.
Untighten the collar clamp and remove the w ater feed hose.
Unscrew the black nut 1 and lay it on the cylinder compartment
tray.
Take the valve out and remove the basket filter from the base of
the valve w ith a pair of long nose pliers. Pull the coil out w ith a flat
screw driver.
Wash the basket filter under clean w ater to remove any dirt and
debris.
Replace w hole valve if cleaning is not practical or replace coil if
necessary.
Assemble in reverse order taking care to replace collar clamp if
necessary.
Ensure that everything is correctly assembled and sw itch the
humidifier on.
Ensure that all the clam ps are properly tightened whenever
the hum idifier is m aintained.
1
INLET VALVE MAINTENANCE