22
Pictures for illustra tive purpos es
Beware ! Before connecting power, make sure that the electrical installation has been made
according to the above-mentioned values.
ALL WORKS CONCERNED WITH THE ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY SKILLED AND QUALIFIED PERSONNEL.
E
LECTRO
V
AP
RTH-LC
Electrical tables
RTH
Steam
production
(kg/h)
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Power
(KW)
Nb of
boiler(s)
Nb of
heating
element(s)
Power of
heating
element (KW)
5/3
5
400
3
6
4
1
3
1,9 (277V)
7
8
400
3
8
6
1
3
1,9 (230V)
10
12
400
3
13
9
1
3
4,3 (277V)
15
17
400
3
19
13
1
3
4,3 (230V)
RTH-LC steam humidifier in 3 x 400V - 50/60Hz
RTH
Steam
production
(kg/h)
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Power
(KW)
Nb of
boiler(s)
Nb of
heating
element(s)
Power of
heating
element (KW)
8
6
230
3
13
5
1
3
1,9 (230V)
RTH-LC steam humidifier in 3x 208V - 50/60Hz
RTH
Steam
production
(kg/h)
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Power
(KW)
Nb of
boiler(s)
Nb of
heating
element(s)
Power of
heating
element (KW)
3
2,5
230
1
8,3
1,9
1
1
1,9 (230V)
5
6
230
1
19
4
1
1
4,3 (230V)
8
8
230
1
27
6
1
2
4,3 (230V)
1,9 (230v)
RTH-LC steam humidifier in 1 x 230V - 50/60Hz
RTH
Steam
production
(kg/h)
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Power
(KW)
Nb of
boiler(s)
Nb of
heating
element(s)
Power of
heating
element (KW)
8
8
230
3
14
6
1
3
1,9 (230V)