A high humidity limit humidistat must be installed in the duct to stop the humidifier in case
the level of humidity exceeds the preset value.
In case the recommended distances cannot be met, please contact
devatec
or their
authorized agent for an alternative solution.
If accurate values cannot be reached, a distance of 2 m. should be considered as a
minimum distance between pipes & obstruction and 3 / 4 m. before sensor or
humidistat.
D
D
5 x D
0,5 x D
D
0,5 x D
Before a junction
before an air opening before a humidity
Before / after a constriction
before an expansion