ELECTROVAP
®
RTH-HC
50
LANGUAGE
Xxxxxxx
HUMIDIFIER
CONFIGURATION
CHANGE UNIT TYPE:
RTH XX
By pressing enter from
this menu
HUMIDIFIER STATUS
VALUE:
FRENCH/ENGLISH
/ etc.
RTH model
(see range)
CHANGE VOLTAGE:
xxxxx V
TOTAL GROUP
PROD.: XXKG
DRAINING TYPE:
xxxxxx
CYCLE DRAIN
DURATION: Xxxx
DRAIN FREQ.:
Xxxxx
COOLING TYPE:
Xxxxxxx
Allows to choose the drain logic (CYCLIC BASED or TIMED
BASED)
Setting of drain duration in seconds
Frequency of drain system
IF TIMED BASED: 1 - 255 min
IF CYCLIC BASED: 1 - 10 cycles
Cooling of the tank before service:
2 choices:
“ECO COOLING” (natural cooling, requires several hours
before being able to touch the tank)
“FAST COOLING” (the temperature of the tank is reduced
by adding cold water, after few minutes, service can be
done)
Selection of power heating: 2x200/2x220/2x230/3x200/
3x208/3x220/3x230/3x380/3x400
/3x415/3x440/3x460/3x480/3x575/3x600/3x690
In case of Master / Slave control only:
adjusts the total
production of the RTH group
Содержание ElectroVap RTH-HC Series
Страница 1: ...ElectroVap HUMIDIFIERS RTH HC Series Instruction Operation Manual ...
Страница 30: ...ELECTROVAP RTH HC 30 3 8 6 Wiring diagrams Up V 1x200 240V 50 60Hz ...
Страница 31: ...ELECTROVAP RTH HC 31 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Страница 32: ...ELECTROVAP RTH HC 32 RTH HC 5 30 Up V 3x380 690V 50 60Hz ...
Страница 33: ...ELECTROVAP RTH HC 33 RTH HC 40 50 Up V 3x380 690V 50 60Hz ...
Страница 34: ...ELECTROVAP RTH HC 34 RTH HC 60 70 Up V 3x380 690V 50 60Hz ...
Страница 35: ...ELECTROVAP RTH HC 35 RTH HC 80 100 Up V 3x380 690V 50 60Hz ...
Страница 36: ...ELECTROVAP RTH HC 36 RTH HC 8 18 Up V 3x200 240V 50 60Hz ...
Страница 37: ...ELECTROVAP RTH HC 37 RTH HC 44 Up V 3x200 240V 50 60Hz ...
Страница 39: ...ELECTROVAP RTH HC 39 Case 2 Up V 3x200 240V 50 60Hz Only for Case 3 ...
Страница 40: ...ELECTROVAP RTH HC 40 Case 3 Up V 3x380 690V 50 60Hz ...
Страница 42: ...ELECTROVAP RTH HC 42 3 9 OPTION TRANSFORMER CONNECTION ...