ELECTROVAP
®
RTH-HC
15
Make sure that spaces and distances are respected. If you have any doubts about the calculation, please contact us.
H1 = 110 mm = Minimum height between the duct floor and the axle of the steam pipe.
H2 = 140 mm minimum for a standard mounting / 110 mm minimum for a stair mounting.
H3 = 160 mm = Minimum height between the axle of the dispersion tube and the top of the duct wall.
The H3 distance can be 80 mm at the shortest if the steam pipe is installed at a 30° angle.
In the case of a stair mounting, minimum distance between tubes = 100 mm.
Air flow direction
Fig. E 3-3.
Minimum heights & flow directions