Error handling at UNIGATE® IC
12 Error handling at UNIGATE
®
IC
A distinction can be made between two categories of system-errors:
Serious errors (1-4): In this case, the Gateway must be switched off and switched back on again.
If the error occurs again, the Gateway must be exchanged and returned for repair.
Warnings (6-15): These warnings are displayed for one minute simply for information purposes
and are then automatically reset. If such warnings occur frequently, please inform After-Sales
Service.
The system-error can be read-out via the Script.
In the configuration mode these displays are not valid and only meant for internal use.
Error no. Error description
0
Reserved
1
Hardware fault
2
EEROM error
3
Internal memory error
4
Fieldbus hardware error or wrong Fieldbus ID
5
Script error
6
Reserved
7
RS-transmit buffer overflow
8
RS-receive buffer overflow
9
RS timeout
10
General fieldbus error
11
Parity-or frame-check-error
12
Reserved
13
Fieldbus configuration error
14
Fieldbus data buffer overflow
15
Reserved
Table 1: Error handling at UNIGATE
®
IC
.