14
Tableau 3: Setup User Menu
Setup
Parameter
Options
Comments
Outdoor
Temperature
Display
bL, On, OFF
bL
– (7 Days Programming only) Factory default is
(bLink), alternates time display between time and
outdoor temperature.
On
– (0 Days Programming default) The outdoor
temperature is displayed continuously on the time
display.
OFF
– Only Time is displayed.
Heat Pump
Disable (HP)
OFF, 5° to 50°F
Available only for air handler with heat pump systems.
Disables heat pump and turns on electric heat below
the selected outdoor temperature.
Dual Fuel
Disable (DF)
OFF, 5° to 50°F
Available only for furnace with heat pump systems (dual
fuel systems). Switches from heat pump to fossil fuel
equipment (furnace) below the selected temperature.
Air Handler
Lockout
Temperature
(AH)
OFF, Heat Pump
Disable setting to
95°F
Available only for air handler with heat pump systems.
Disables electric heat above the selected outdoor
temperature. OFF defaults to 50°F.
<equipment>_
Test
No, Yes
Steps the selected equipment through its sequential
mode of operation.
Reset System
No, Yes
This will reset ALL of the communicating system
components to their factory set values.
7.5- FURNACE USER MENUS
“X” in the following tables indicate alpha or numeric character.
Tableau 4: Status 1 Furnace User Menu
Status I
Parameter
Indications
Comments
Main Limit
Closed, Open
Main Limit Control Status
MRLC Input
Closed, Open
Main Reset Limit Control Status
HALC Input
Closed, Open
Heat Assist Limit Control Status
IDM Output
Off, Lo, Hi
Inducer Output Status
Furn Lo Pr Sw
Closed, Open
Furnace Low Pressure Switch Status
Furn Hi Pr Sw
Closed, Open
Furnace High Pressure Switch Status
Gas VLV Prcnt %
XXX%, Off
Mod Gas Valve % Open
Gas VLV Relay
Lo, Hi, On, Off
Gas Valve Control Output Status
Flame
Off, Marginal, Good,
Unexpected
Status of Flame Sensor
Blower CFM
CFM XXXX
Furnace Blower CFM