26
7.1- PRECAUTIONS BEFORE PERFORMING INSPECTION OR REPAIR
-
Be cautious during installation and maintenance. Follow the codes and regulations to avoid electric shock and casualty or even death. Static
maintenance is the maintenance during de-energization of the heat pump.
-
For static maintenance, make sure that the unit is de-energized.
-
Dynamic maintenance is the maintenance during energization of the unit.
-
Before dynamic maintenance, check the electricity and ensure that there is ground wire on the site.
-
Take sufficient care to avoid directly touching any of the circuit parts without first turning OFF the power.
NOTE:
A large capacity electrolytic capacitor is used in the outdoor unit controller (inverter). Therefore, if the power supply is turned OFF, charge (charging
voltage DC280V to 380V) remains and discharging takes a lot of time. After turning off the power, if touching the charging section before discharging, an
electrical shock may be caused. Discharge the electrolytic capacitor completely.
Remove the inverter cover
7.2- VERIFICATION
(1) Verify the power supply
Confirm that the circuit breaker is in the ON position
(2) Confirmation of power voltage
Confirm that power voltage is AC 208-230 ± 10 %. If power voltage is not in this range, the unit may not operate normally.
Содержание COND-30-01
Страница 11: ...11 4 SCHEMATIC DIAGRAMS 4 1 ELECTRICAL DIAGRAM Figure 9 30 36K Electrical diagram...
Страница 12: ...12 4 2 PRINTED CIRCUIT BOARD Figure 10 30 36K Circuit board...
Страница 17: ...17 Figure 12 Multiposition configurations Figure 13 Splashguard without front slope...
Страница 22: ...22 7 TROUBLESHOOTING...
Страница 23: ...23...
Страница 24: ...24...
Страница 25: ...25...
Страница 29: ...29...
Страница 39: ...39 7 6 8 Flow chart outdoor communication circuit detecting...
Страница 40: ...40 7 6 9 High pressure protection...
Страница 42: ...42...
Страница 43: ...43...
Страница 44: ...44...
Страница 45: ...45...
Страница 46: ...46...
Страница 47: ...47...
Страница 48: ...48 9 COMPONENTS AND REPLACEMENT PARTS 9 1 EXPLODED VUE 30 36K...