Dettson COND-09-01 Скачать руководство пользователя страница 17

17 

17 

 

(2)  When 

−2°, (−3.6°0) < 

− =

789::  .

;:87:8

> < 1°, (1.8°0)

,  the  unit  will  keep  its  previous 

operation status. 

(3)  When 

− =

789::  .

− 

;:87:8

> ≤ −2°, (−3.6°0)

compressor  will  stop  operation  and  in  30s  later, the  outdoor 
fan will stop operation; 

(4)  When  the  unit  is  turned  off  at  heating  mode,  or  changes  to 

another mode from heating mode, the 4-way valve will be de-
energized in 2 minutes later after compressor stops operation 
(the compressor is operating during heating mode). 

(5)  When 

:?9::  .

> 30°, (86°0)

,  compressor  will  stop 

operation  immediately  and  outdoor  fan  will  stop  operation  in 
30s later. 

(6)  When  the  compressor  is  operating,  or  changing  to  heating 

from cooling, the 4-way valve will be energized in 2-3 minutes 
later. 

 

Condition and process of defrost 

(1)  When 

:?9::  .

≤ 5°, (41°0)

 

and  compressor 

has 

operated  for  a  cumulated  time  of  3  hours,  if 

:?9:: 7

<

0°, (32°0),

 the unit will enter defrosting mode. 

 Note: 

the 

time 

will 

be 

cleared 

when 

CDEFCCG HIJ. >

5°, (41°0), 

compressor  has  been  started  up  after  changing  to  cooling 

mode and defrosting has finished. The time will not be cleared when the 
unit stops when reaching temperature point, or for protection, changing 
to fan mode, etc).  

(2)  When heating has operated for continuous 45 minutes, or for 

an accumulated 90 minutes, the unit will enter defrosting mode 
in 3 minutes after meeting any condition below; 

a. 

:?9::  78

> 5°, (41°0),  

:?9:: ? 

−2°, (28.4°0)

b. 

−2°, (28.4°0) ≤   

:?9::  78

  ≤ 5°, (41°0)

 

:?9:: ? 

≤ −6°, (21.2°0);

 

c. 

−5°, (23°0) ≤ 

:?9::  78

< −2°, (28.4°0),

 

 :?9:: ? 

≤ −8°, (17.6°0)

d. 

−10°, (14°0) ≤ CDEFCCG HIJ. < −5°, (23°0

), 

CDEFCCG MNMO −  PCIMOQRHENCQ  ≤
 (CDEFCCG HIJ. 3°, (37.4°0)

 

e. 

CDEFCCG HIJ. < −10°, (14°0)

CDEFCCG MNMO –  PCIMOQRHENCQ  ≤
 (CDEFCCG HIJ. −3°, (37.4°0))

 

 
After energization, for  the first  defrosting, 

= 0°, (32°0)

 ; if  it is not the 

first  time  of  defrosting, 

PCIMOQRHENCQ

  will  be  determined  by 

CDEFCCG MNMO

  when  quitting  defrosting  last  time;  if 

CDEFCCG MNMO  >

 2°, (35.6°0)

PCIMOQRHENCQ = 0°, (0°0)

if 

CDEFCCG MNMO  ≤

2°, (35.6°0),

 

PCIMOQRHENCQ = 3°, (5.4°0)

 

(3)  During  defrosting,  if  operation  time  for  compressor  does  not 

reach  3min,  the  defrosting  will  not  be  entered  in  the 
subsequent 2 hours. At that time, compressor stops operation 
and in 30s later, the outdoor fan will stop operation; in another 
30s, 4-way valve will stop operation; in 30s later, compressor 
will increase its frequency for defrosting. When defrosting lasts 
for  450s,  or 

CDEFCCG MNMO  ≥  10°, (50°0)

,  compressor  will 

decrease  its  frequency.  In  30s  later,  compressor  will  stop 
operation;  in  another  30s,  4-way  valve  will  be  started  up.  In 
60s later, compressor and outdoor fan will operate. Frequency 
for defrosting is 85Hz. 
 

Protections :

 

Total current up and frequency down  

When total current 

TECEHU ≤ 6V

, increase frequency is allowed; when 

total current 

TECEHU ≥ 7V

, increasing frequency is prohibited; when total 

current 

TECEHU ≥ 8V

, the unit operates by decreasing frequency. When 

total current 

TECEHU ≥ 9V,

 the compressor stops operation, and indoor 

fan will stop operation after 30s. 
 

3. 

Common  Protection  Functions  and  Fault  display  under 
COOL and HEAT Modes 

 

Overload protection 

 EDJO

: measured temperature of outdoor heat exchanger under cooling 

mode;  and  measured  temperature  of  indoor  heat  exchanger  under 
heating mode. 

(1)  Cooling overload 

a. 

If 

 EDJOR ≤ 52°, (125.6°0),

 the unit will return to its 

original state. 

b. 

If 

 EDJOR ≥ 55°, (131°0)

,  frequency  rise  is  not 

allowed. 

c. 

If 

 EDJOR  ≥ 58°, (136.4°0

), the compressor will run 

at reduced frequency. 

d. 

If 

 EDJO ≥ 62°, (143.6°0)

,  the  compressor  will 

stop. 

(2)  Heating overload 

a. 

If 

 EDJOR ≤ 50°, (122°0),

 the unit will return to n its 

original operation sate. 

b. 

If 

 EDJOR ≥ 53°, (127.4°0)

,  frequency  rise  is  not 

allowed. 

c. 

If 

 EDJOR ≥ 56°, (132.8°0)

, the compressor will run 

at reduced frequency. 

d. 

If 

 EDJOR ≥ 60°, (140°0)

, the compressor will stop 

and the indoor fan will blow residual heat and then 
stop. 

 

Exhaust temperature protection of compressor 

(1)  If  exhaust  temperature 

98°C  (208.4°F),  frequency  is  not 

allowed to rise. 

(2)  If exhaust temperature 

103°C (217.4°F), the compressor will 

run at reduced frequency. 

(3)  If  exhaust  temperature 

110°C  (230°F),  the  compressor  will 

stop. 

(4)  If exhaust temperature 

90°C (194°F) and the compressor has 

stayed  at  stop  for  at  least  3  minutes,  the  compressor  will 
resume its operation. 

 
 

Communication fault 

If  the  unit  fails  to  receive  correct  signals  for  durative  3  minutes, 
communication fault can be justified and the whole system will stop. 
 
 

Module protection 

Under  module  protection  mode,  the  compressor  will  stop.  When  the 
compressor remains at stop for at least 3 minutes, the compressor will 
resume its operation. If module protection occurs six times in succession, 
the compressor will not be started again. 
 
 

Overload protection 

If temperature sensed by the overload sensor is over 115°C (239°F), the 
compressor will stop and the outdoor fan will stop with a time lag of 30 
seconds. If temperature is below 95°C (203°F), the overload protection 
will be relieved. 
 
 

DC bus voltage protection 

If voltage on the DC bus is below 150V or over 420V, the compressor 
will stop and the outdoor fan will stop with a time lag of 30 seconds. When 
voltage on the DC bus returns to its normal value and the compressor 
has stayed at stop for at least 3 minutes, the compressor will resume its 
operation. 
 

5.3.1.3 

Control of outdoor electric Heating Band 

 
If not in heating mode or temp sensor has malfunction, electric heating 
bands  of compressor  and  of  condenser  will  stop  operation,  otherwise, 
the below control logic will be followed. 

 

1. 

Control of Compressor electric heating Band

 

a. 

Conditions  for  startup:  the  compressor  is  off  and 
meanwhile outdoor ambient temp

-5°C (23°F); 

Содержание COND-09-01

Страница 1: ...www dettson ca INSTALLER SERVICE TECHNICIAN Use the information in this manual for the installation servicing and keep the document near the furnace for future reference HOMEOWNER Please keep this ma...

Страница 2: ...o COOL mode and adjust the set point to a lower value than the actual room temperature 5 The furnace and the outdoor unit should start within 5 minutes Modulating furnace 1 Connect the RJ 11 wire betw...

Страница 3: ...6 10 2 Air purging and leakage test 26 6 10 3 Outdoor unit condensate drainage 26 6 10 4 Check after installation and test operation 26 6 10 5 Operation test 26 7 TROUBLESHOOTING 27 7 1 Precautions b...

Страница 4: ...cuit board 14 Figure 17 18K Circuit board 15 Figure 18 24K Circuit board 15 Figure 19 Installation schematic and clearances 22 Figure 20 Multiposition configurations 23 Figure 21 Splashguard without f...

Страница 5: ...ng diagram and all the instruction when wiring Have the unit adequately grounded in accordance with the local electric codes Have all wiring connected tightly Loose connection may lead to overheating...

Страница 6: ...37 3x25 4x16 5 37 3x25 4x16 5 40 5x29 5x18 0 42 8x33 7x19 2 cm 94 74x64 52x41 91 94 74x64 52x41 91 102 87x74 93x45 72 108 71x85 60x48 77 lb 86 87 1 110 3 154 3 lb 90 4 91 5 116 9 165 3 oz 45 9 45 9 56...

Страница 7: ...7 7 1 4 OPERATION CHARATERISTIC CURVES Figure 1 9K Operation characteristic curves Figure 2 12K Operation characteristics curves Figure 3 18 24K Operation characteristics curves...

Страница 8: ...8 8 1 5 CAPACITY VARIATION RATIO ACCORDING TO TEMPERATURE Figure 4 9 12K Capacity ratio vs outdoor temperature Figure 5 18 24K Capacity ratio vs outdoor temperature...

Страница 9: ...9 9 1 6 NOISE CRITERIA CURVE TABLES Figure 6 9K Noise curves Figure 7 12K Noise curves Figure 8 18 24K Noise curve...

Страница 10: ...10 10 2 CONSTRUCTION VIEWS Figure 9 9 12K dimensions...

Страница 11: ...11 11 Figure 10 18K dimensions Figure 11 24K dimensions...

Страница 12: ...M Figure 12 refrigerant system diagram Properly insulate ALL refrigerant tubing from outdoor units to the interior cooling coil to prevent water dripping 4 SCHEMATIC DIAGRAMS 4 1 ELECTRICAL DIAGRAMS F...

Страница 13: ...13 13 Figure 14 18K Electrical diagram Figure 15 24K Electrical diagram...

Страница 14: ...14 14 4 2 PRINTED CIRCUIT BOARDS Figure 16 9 12K Circuit board...

Страница 15: ...15 15 Figure 17 18K Circuit board Figure 18 24K Circuit board...

Страница 16: ...1 3 DIP1 4 Balance point OFF OFF OFF OFF Heat pump heat only ON OFF OFF OFF 10 F 23 C OFF ON OFF OFF 5 F 21 C ON ON OFF OFF 0 F 18 C OFF OFF ON OFF 5 F 15 C ON OFF ON OFF 10 F 12 C OFF ON ON OFF 15 F...

Страница 17: ...prohibited when total current TECEHU 8V the unit operates by decreasing frequency When total current TECEHU 9V the compressor stops operation and indoor fan will stop operation after 30s 3 Common Pro...

Страница 18: ...ot be detected Blow residual heat In heating mode when temperature reaches the set temperature the compressor and outdoor fan will stop When the unit is in heating mode and the compressor and indoor f...

Страница 19: ...turning the thermostat to OFF or cooling mode During operation if operation time of compressor is over the times of stop operation because of overload protection will be cleared If turn the thermostat...

Страница 20: ...witch to fan mode times of malfunction is eliminated immediately 5 3 2 16 Overload protection of compressor 1 If it detected that the overload switch for compressor is open for 3min successively the c...

Страница 21: ...o not expose the unit to direct sunlight nor strong wind 5 Make sure that the outdoor unit is installed in accordance with the installation instructions and is convenient for maintenance and repair 6...

Страница 22: ...ontal pull through installations In the center opening of vertical drain pan a metal Inlet Air Restrictor is factory installed and is required for horizontal applications It may be removed for vertica...

Страница 23: ...23 23 Figure 20 Multiposition configurations Figure 21 Splashguard without front slope...

Страница 24: ...ls are equipped with multiple drain connections Determine the drain connections to be used and note the difference between the primary green and secondary red openings Drain plugs are provided for all...

Страница 25: ...to a lower value than the actual room temperature 5 The furnace and the outdoor unit should start within 5 minutes Modulating furnace 1 Connect the RJ 11 wire between the interface and the air handler...

Страница 26: ...oor drain connector in a 98in hole on the base plate and attach the drain hose to the connector so that the waste water formed in the outdoor unit can be drained out The hole diameter 0 98 must be plu...

Страница 27: ...27 7 TROUBLESHOOTING...

Страница 28: ...28 Verify if the temperature sensor is exposed to the sunlight...

Страница 29: ...29 29...

Страница 30: ...30...

Страница 31: ...irectly touching any of the circuit parts without first turning OFF the power NOTE A large capacity electrolytic capacitor is used in the outdoor unit controller inverter Therefore if the power supply...

Страница 32: ...rly Make sure the connections are made as per Figure 13 Figure 14 and Figure 15 Cycle the power of both units Yellow When communicating properly with the communicating furnace this LED should be blink...

Страница 33: ...links for 7 times Overload protection Blinks for 6 times Overcurrent protection for the complete unit Blinks for 5 times Module current protection IPM protection Blinks or 4 times Over low voltage pro...

Страница 34: ...34 34...

Страница 35: ...indoor fans operates During heating operation all loads stop Please refer to the malfunction analysis discharge protection overload Overcurrent protection During operation the complete unit stops 1 S...

Страница 36: ...oad Decrease frequency due to high air discharge All loads operate normally while operation frequency for compressor is decreased Overload or temperature is too high Refrigerant is insufficient Malfun...

Страница 37: ...erate normally while operation frequency for compressor is decreased Refer to the malfunction analysis overload high temperature resistant Failure to start up During operation the complete unit stops...

Страница 38: ...o high temperature of module During operation the complete unit stops Discharging after the complete unit is de energized for 20 minutes check whether the thermal grease on IPM module of outdoor contr...

Страница 39: ...39 39 7 5 TROUBLESHOOTING FLOW CHART 7 5 1 Communication malfunction...

Страница 40: ...on AP1 BELOW IS THE CONTROL BOARD OF OUTDOOR UNIT USUAL SYMPTOMS Check if the voltage of L and N terminal of wiring board is between 210AC 250AC using multimeter Is the inductor L well connected Is th...

Страница 41: ...tage between L N of wiring board XT by DC voltage meter Is the coil resistance of compressor normal Is the compressor coil insulating to copper pipe correctly Is the work load of unit too high Is the...

Страница 42: ...nt temperature in a normal range Is the indoor and outdoor fans are running normal How is the radiating environment of the indoor and outdoor unit 7 5 4 Anti high temperature overload protection AP1 B...

Страница 43: ...Is the compressor wiring correct Is the stop time of the compressor enough Is the compressor damaged Is the refrigerant charged too much 7 5 5 Failure start up malfunction AP1 BELOW IS THE CONTROL BO...

Страница 44: ...44 44 USUAL SYMPTOMS Is the system pressure over high Is the supply voltage under low 7 5 6 Compressor synchronism AP1 BELOW IS THE CONTROL BOARD OF OUTDOOR UNIT...

Страница 45: ...electronic expansion valve connected correctly Is the expansion valve damaged Is the refrigerant leaking Is the overload protector damaged 7 5 7 Overload and discharge malfunction AP1 BELOW IS THE CO...

Страница 46: ...46 46 7 5 8 PFC correction for power factor malfunction AP1 BELOW IS THE CONTROL BOARD OF OUTDOOR UNIT Check if the inductor L of outdoor unit and PFC capacity are damaged...

Страница 47: ...the indoor and the outdoor are connected correctly and not damaged Is the communication circuit of the indoor mainboard is damaged Is the communication circuit of the outdoor mainboard AP1 damaged 7...

Страница 48: ...AL PROCEDURE OF OUTDOOR UNIT WARNING Be sure to wait for a minimum of 10 minutes after turning off all power supplier before disassembly NOTE Electric heater band is not shown below Models COND 09 01...

Страница 49: ...49 49...

Страница 50: ...50 50...

Страница 51: ...51 51...

Страница 52: ...52 52...

Страница 53: ...53 53...

Страница 54: ...54 54 WARNING Be sure to wait for a minimum of 10 minutes after turning off all power supplier before disassembly Models COND 18 01...

Страница 55: ...55 55...

Страница 56: ...56 56...

Страница 57: ...57 57...

Страница 58: ...58 58...

Страница 59: ...59 59...

Страница 60: ...60 60 WARNING Be sure to wait for a minimum of 10 minutes after turning off all power supplier before disassembly Models COND 24 01...

Страница 61: ...61 61...

Страница 62: ...62 62...

Страница 63: ...63 63...

Страница 64: ...64 64...

Страница 65: ...65 65...

Страница 66: ...66 66...

Страница 67: ...67 67 9 COMPONENTS AND REPLACEMENT PARTS 9 1 EXPLODED VUE 9 12K...

Страница 68: ...b assy COND 07133674 1 17 Cut off valve sub assy COND 07133204 1 18 4 way valve assy COND 03123870 1 19 Magnet coil COND 430004002 1 20 Inductor COND 43130184 1 21 Electric expansion valve sub assy CO...

Страница 69: ...69 69 9 3 EXPLODED VUE 18K...

Страница 70: ...1 18 Wiring clamp COND 26115004 1 19 Temperature sensor COND 3900030901 1 20 Capacitor CBB65 COND 33000065 1 21 Capacitor clamp sub assy COND 01413098 1 22 Handle COND 26235254 1 23 Cut off valve sub...

Страница 71: ...71 71 9 5 EXPLODED VUE 24K...

Страница 72: ...sub assy COND 01715020P 1 15 Cut off valve COND 07130239 1 16 Valve cover N A N A 17 Cut off valve COND 07133157 1 18 Big handle COND 26235001 1 19 Magnet coil COND 4300040033 1 20 Capacitor COND 330...

Страница 73: ...7 75 2 94 237 114 0 904 28 2 72 41 99 37 12 169 76 2 844 239 115 0 88 30 1 68 79 100 38 11 52 171 77 2 752 241 116 0 856 32 0 65 37 102 39 11 06 172 78 2 663 243 117 0 833 34 1 62 13 104 40 10 62 174...

Страница 74: ...7 75 2 206 237 114 0 678 28 2 54 31 99 37 9 003 169 76 2 133 239 115 0 66 30 1 51 59 100 38 8 642 171 77 2 064 241 116 0 642 32 0 49 02 102 39 8 297 172 78 1 997 243 117 0 625 34 1 46 6 104 40 7 967 1...

Страница 75: ...9 79 26 47 08 149 65 10 18 219 104 2 955 10 12 306 2 81 27 45 07 151 66 9 827 221 105 2 872 12 11 289 6 82 28 43 16 153 67 9 489 223 106 2 792 14 10 274 84 29 41 34 154 68 9 165 225 107 2 715 16 9 25...

Страница 76: ...Conditioning Institute of Canada and the Air Conditioning Contractors of America Failure to do so voids this warranty F Unauthorized Installation of Accessory Equipment Dettson Industries inc authori...

Отзывы: