background image

components (e.g. a condenser) on the network. This
L.E.D. will blink randomly any time a message is received
by the furnace control.

If no blinking is seen within

five minutes, it can be assumed that there is not valid
communications established. Check wiring to make sure
that all points are connected properly.
Further, if this L.E.D. is on continuously, it is an indication
that mis-wiring has occurred.

“STAT” (STATUS) (Red)

L.E.D.

– This L.E.D. blinks twice slowly (¼ second ON, ¾

second OFF) upon power-up.
Pressing the learn button for two seconds will cause the
green “RX” L.E.D. to blink rapidly (for a short period) to
indicate an attempt at communications. If the L.E.D. does
not blink, communications cannot be established.

9.11

MEMORY CARD

WARNING

Do not replace the furnace control or memory card
of the furnace with a furnace control or memory
card of another furnace or another component
(e.g.

a memory card from a condenser or air

handler). The wrong furnace control or memory
card may specify parameters which will make
the furnace run at undesired conditions including
(but not limited to) reduced airflow during heating
causing excessive undesired operation of the
main limit control.

Further, the memory card

is specific to the model number and BTU input
rating for a specific furnace and this information
should not be transported from one furnace (or
component) to another.

Furnace shared data is defined as data specific to a given
furnace that is critical for proper furnace operation. More
specifically, it is data which defines the operation of the
furnace and is unique to a given furnace platform and
model. The most critical of these data are the coefficients
that control the blower operation (i.e. define the blower
speed-torque operation). Because of this, each furnace
control is programmed with furnace shared data for that
model furnace only. The furnace shared data from any
given furnace can NOT be transferred to another furnace
for any reason. Doing so can adversely affect operation
of the furnace.

Further, if no furnace shared data is

present, the furnace will not operate in any mode and
a fault will be displayed.

9.12

REPLACING FURNACE

CONTROL

In the event that the furnace control must be replaced, the
memory card must be detached from the original furnace
control and retained with the furnace. Failure to save and
connect the memory card properly to the replacement
control may result in no operation or undesired operation
of the furnace.

When replacing the furnace control, be sure to match
the DIP switch settings of the original control on the
replacement.

9.13

DIP SWITCH

The integrated furnace control MAY not recognize switch
setting changes while energized.
DIP switches are ignored on communicating system,
except for test mode. When using the communicating
thermostat R02P032, configuration will be done throught
it. Please refer to the thermostat manual.

9.13.1

CFM Heat adjust

DIP switch bank S1 is used to fine-tune the airflow in
the heating mode.

The switches of bank S1 can be

set to adjust either the minimum heat rate airflow or the
maximum heat rate airflow or both. Also, every firing rate
in between these points will be adjusted accordingly.

NOTE:

All DIP switches on S1 will be shipped in the “OFF”

position. See Table 12.

Table 12 – Heating Airflow Adjustment - S1

S1-1

S1-2

S1-3

S1-4

DESCRIPTION

DEFAULT

OFF

OFF

OFF

OFF

NO
ADJUSTMENT

LOW FIRE

ADJUSTEMENT
(40%)

OFF

ON

OFF

OFF

-7.5%

OFF

ON

OFF

ON

-15%

OFF

ON

OFF

ON

+7.5%

OFF

ON

OFF

ON

+15%

HIGH FIRE

ADJUSTEMENT
(100%)

ON

OFF

OFF

OFF

-7.5%

ON

OFF

OFF

ON

-15%

ON

OFF

ON

OFF

+7.5%

ON

OFF

ON

ON

+15%

BOTH INPUT

ADJUSTEMENT

ON

ON

OFF

OFF

-7.5%

ON

ON

OFF

ON

-15%

ON

ON

ON

OFF

+7.5%

ON

ON

ON

ON

+15%

9.13.2

Cooling airflow select

These DIP switches are used to select the appropriate
cooling airflow based on the amount required. The switch
settings do not affect cooling airflow when installed in
fully communicating system. In that case, the condenser
supplies the information for cooling airflow which is pre-
set at the factory and not adjustable.

See tables 13 and 14 for target CFM and CFM adjust.

Table 13 – Cooling Airflow Adjustement

S3-1

S3-2

CFM

Cooling
capacity

OFF

OFF

600

1.5 T.

ON

OFF

400

1.0 T.

OFF

ON

300

0.75 T.

ON

ON

200

0.5T.

Table 14 – Cooling Airflow % Adjustement

S3-3

S3-4

DESCRIPTION

OFF

OFF

0%

ON

OFF

+10%

OFF

ON

-10%

ON

ON

0%

27

Содержание CC15-M-V

Страница 1: ...future reference Caution Do not tamper with the unit or its controls Call a qualified service technician HOMEOWNER Please keep this manual near the furnace for future reference Manufactured by Dettson...

Страница 2: ...1 NON COMMUNICATING MODULATING ONE STAGE OR TWO STAGE THERMOSTAT 16 7 3 2 THERMOSTAT INPUT 16 7 4 ALTERNATE POWER SUPPLY 17 8 VENTING AND COMBUSTION AIR PIPING 19 8 1 GENERAL 19 8 2 DIRECT VENT 19 8 3...

Страница 3: ...Alternate horizontal termination A 22 Figure 23 Alternate horizontal termination B 22 Figure 24 Alternate horizontal termination C 22 Figure 25 Direct vent clearance 23 Figure 26 Other than Direct ve...

Страница 4: ...assess the damage and to replace all critical parts that were in contact with water 3 Do not store gasoline or any other flammable substances such as paper or carton near the furnace 4 Do not stack it...

Страница 5: ...o be handled by duct s sealed to the furnace casing and terminating outside the space containing the furnace See section 5 DUCT INSTALLATION This furnace may be installed with a two pipe sealed combus...

Страница 6: ...th the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or Natural Gas and Propane Installation code CSA B149 1 9 After it has been determined that each appliance connected to the venting system properl...

Страница 7: ...n Code NSCNGPIC CAN CSA B149 1 General installation NFGC and the NFPA 90B For copies contact the National Fire Protection Association Inc Battery march Park Quincy MA 02269 or for only the NFGC contac...

Страница 8: ...in this manual The furnace should be located as close to the chimney vertical venting or to the outside vent wall horizontal venting as possible 2 3 1 Location relative to cooling equipement The cooli...

Страница 9: ...on Figure 3 Dimensions Figure 4 Top view Figure 5 Drain Trap Localisation Figure 6 Pressure switch connections for multipositions 4 1 UPFLOW The condensate trap must be outside the furnace casing Use...

Страница 10: ...gths 1 4 5 and 2 9 25 3 Remove the appropriate knock out for drain trap Refer to Figure 5 for the location of the drain trap in downflow configuration 4 Cut open the pressure port located on the conde...

Страница 11: ...er to ensure proper drainage of the condensate See figure 12 4 3 1 Horizontal Condensate drain connection 1 Remove PVC tubes from the ID blower condensate box and vent collector and block the openings...

Страница 12: ...ith local building codes 12 The venting must be drained using a PVC 636 tee Connect this tee to a P trap and connect it to your condensate drain Commercially available condensate trap exist for use wi...

Страница 13: ...fasteners for type of ductwork used Seal supply and return duct connections to the furnace with code approved tape or duct sealer Ductwork passing through an unconditioned space should be insulated t...

Страница 14: ...ot have a 90 degree elbow and 10 ft 3 M of main duct to the first branch take off may require internal acoustical lining As an alternative fibrous ductwork may be used if constructed and installed in...

Страница 15: ...ert the gas valve to propane 1 Move the switch located on the valve to the off position 2 Remove the NAT GAS label from the top of the gas valve 3 Using a pair of tweezers or needle nose pliers place...

Страница 16: ...mum mode of operation and will give the best temperature control with minimal temperature variation from the desired set point Operation with a 2 stage thermostat will proceed as follow call on W1 wil...

Страница 17: ...te Power from an alternate power supply that is non sinusoidal may damage the furnace electronics or cause erratic operation Contact the alternate power supply manufacturer for specifications and deta...

Страница 18: ...Figure 17 Wiring Diagram 18...

Страница 19: ...rrent edition of the National Fuel Gas Code and the vent or liner manufacturer s installation instructions Care must be taken to prevent the exhaust gases from one appliance from contaminating the com...

Страница 20: ...e 2 Count the number of elbows for each pipe 3 For each pipe multiply the number of elbows by the equivalent length for the type of elbow used see table 11 Record the equivalent length of all the elbo...

Страница 21: ...INATION All clearance specified in this manual are in accordance with the current CSA B149 1 Natural and Propane Installation Code and the current ANSI Z223 1 NFPA 54 National Fuel Gas Code For cleara...

Страница 22: ...r the elbows to fit on the pipes Holes in the roof for two pipe terminations should be spaced no more than 18 457 mm apart Termination elbows will be installed after the vent and combustion air pipe a...

Страница 23: ...Figure 25 Direct vent clearance 23...

Страница 24: ...Figure 26 Other than Direct vent clearance 24...

Страница 25: ...ve the burner compartment control access door 3 IMPORTANT Be sure that the manual gas control has been in the OFF position for at least five minutes Do not attempt to manually light the main burners 4...

Страница 26: ...oth pressure switches quickly Once both pressure switches are sensed to be closed the inducer will run for 25 seconds before the ignition trial starts Hot surface igniter is energized during the pre p...

Страница 27: ...esent the furnace will not operate in any mode and a fault will be displayed 9 12 REPLACING FURNACE CONTROL In the event that the furnace control must be replaced the memory card must be detached from...

Страница 28: ...r future reference To keep your operating costs low and to eliminate unnecessary service calls we have provided a few guidelines These guidelines will help you understand how your gas furnace operates...

Страница 29: ...g 3 Leave the building immediately 4 Immediately call your gas supplier Follow the gas supplier s instructions 5 If you cannot reach the gas supplier call the fire department 10 2 OPERATING YOUR FURNA...

Страница 30: ...sense current is weak or weird 1 Clean or replace de flame sensor 2 Check gas outlet pressure 3 Take a combustion analysis A dirty flamme sensor needs to be investigate 13 Flame lost 1 Clean or replac...

Страница 31: ...e gas valve will immediately close flame will be lost blower motor operation will immediately stop and the furnace will shut down normally with Inducer post purge at the correct speed After the post p...

Страница 32: ...Outlet gas pressure high fire 100 Outlet gas pressure low fire 40 Static pressure in return Static pressure in supply Temperature rise Is drain trap filled with water Is drain trap outlet vented with...

Страница 33: ...Table 18 Specification table 1 Maximum CFM acheived in standard duct systems 2 Maximum CFM acheived using SmartDuct system 33...

Страница 34: ...12 PART LIST Figure 27 Exploded view...

Страница 35: ...Figure 28 Exploded view continued...

Страница 36: ...Table 19 Part list Chinook Compact...

Страница 37: ...Table 20 Part list continued...

Страница 38: ...13 NOTES 38...

Страница 39: ...39...

Страница 40: ...40...

Отзывы: