background image

 

 

4

 

2. INSTALLATION

 

 

 

The unit must be installed in an area where the ambient 
and return air temperatures are above 15°C (60°F). In 
addition, the furnace should be installed as closely as 
possible to the vent, so that the connections are direct and 
kept to a minimum. The heater should also be located 
close to the centre of the air distribution system. 

This furnace is a true multi-position unit, in that it will function 
in an upflow, downflow or horizontal configuration to the left or 
the right. Only a few modifications are required during 
installation to change from one position to another. The unit is 
shipped in the upflow configuration and instructions as to how 
to change to the other positions are included in this manual. 

2.1.1 

Installation in an enclosure 

The unit can be installed in an enclosure such as a closet. 
However, 2 ventilation openings are required for 
combustion air. The openings should be located in front of 
the furnace approximately 15 cm (6") above the floor and 
15 cm (6") below the ceiling. Figure 1 indicates the 
minimum dimensions required and the location of the 
openings.  

 

It requires an 115VAC power supply to the control panel and 
thermostat hook-up as shown on the wiring diagram, one or 
more oil line connections, suitable ductwork and connection to 
a properly sized vent.  

 

All local and national code requirements governing the 
installation of oil burning equipment, wiring and the flue 
connection MUST be followed. Some of the codes that may 
apply are: 

Figure 1: Location and dimensions of ventilation air 

openings in a closet door

 

CSA B139:

  

Installation code for oil burning equipment. 

ANSI/NFPA 31:

   Installation of oil burning equipment. 

ANSI/NFPA 90B:

 Warm air heating and air conditioning 

systems. 

ANSI/NFPA 211:

  Chimneys, Fireplaces, Vents and solid fuel 

burning appliances.

 

ANSI/NFPA 70:

   National Electrical Code.  

CSA C22.1:  

Canadian Electrical Code. 

or CSA C22.10:

  

 

Only the latest issues of these codes may be used. 

2.1 POSITIONING

 

THE

 

FURNACE 

WARNING 

 

 

Fire and explosion hazard. 

2.2 CONFIGURATIONS 

 

 

The furnace must be installed in a level position, never 
where it will slope toward the front. 

2.2.1 Upflow Installation 

 

Do not store or use gasoline or any other flammable 

The return air opening may be located on either side of 
the furnace. Care should be taken not to damage the 
wires inside, while cutting the opening. Install the filter 
rack supplied with the unit according to the instructions 
provided with it. It is also recommended to install the 
blower door before handling or moving the unit. Refer to 
figure 2 for additional details.

 

substances near the furnace. 

 

Non-observance of these instructions will potentially result 
in death, bodily injury and/or property damage. 

 

CAUTION 

This furnace is not watertight and is not designed for outdoor 

Figure 2: Upflow installation

 

installation. It must be installed in such a manner as to protect 
its electrical components from water. Outdoor installation will 

 

lead to a hazardous electrical condition and to premature 

 

failure of the equipment. 

 

 

The minimum clearances from combustible material for 
each of the positions are specified in Table 9. 

 

If the furnace is installed in a basement or on a dirt floor, in a 
crawl space for example, it is recommended to install the unit 
on a cement base 2.5 cm to 5.0 cm (1" to 2") thick. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Burner position 

Filter 20" x 20" 

Combustible or non-
combustible floor 

Содержание AMP098SD

Страница 1: ...ard Sherbrooke Qc Canada J1L 1V8 Manufactured by Dettson Industries Inc Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN Use the information in this manual for the installation servicing of the furnace and keep the document near the unit for future reference HOMEOWNER Please keep this manual near the furnace for future reference...

Страница 2: ...1 3 3 9 Restart after Burner Failure 11 4 MAINTENANCE 12 4 1 CLEANING THE HEAT EXCHANGER 12 4 2 CLEANING THE BLOCKED VENT SHUT OFF DEVICE BVSO 12 4 3 CLEANING OF THE BURNER HEAD 12 4 4 CHANGING THE NOZZLE 12 4 5 CHANGING THE OIL FILTER 12 4 6 CHANGING THE AIR FILTER 12 5 FURNACE INFORMATION 13 TABLES Table 1 Blower speed adjustments 4 speed motors 8 Table 2 Supply air adjustments ECM variable spee...

Страница 3: ...hould be installed in your residence and properly maintained to warn early on of a potentially dangerous fire Also the house should be equipped with approved and properly maintained fire extinguishers Non observance of the safety regulations outlined in this manual will potentially lead to consequences resulting in death serious bodily injury and or property damage a It is the homeowner s responsi...

Страница 4: ...n code for oil burning equipment ANSI NFPA 31 Installation of oil burning equipment ANSI NFPA 90B Warm air heating and air conditioning systems ANSI NFPA 211 Chimneys Fireplaces Vents and solid fuel burning appliances ANSI NFPA 70 National Electrical Code CSA C22 1 Canadian Electrical Code or CSA C22 10 Only the latest issues of these codes may be used 2 1 POSITIONING THE FURNACE WARNING Fire and ...

Страница 5: ...e manner regardless of the discharge position of the furnace Refer to Figure 4 for additional details 2 3 ELECTRICAL SYSTEM CAUTION The exterior of the unit must have an uninterrupted ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for that purpose The appliance must be installed in accordance with the current ...

Страница 6: ...instructions in this section Failure to properly vent this furnace can result in in death bodily injury and or property damage To ensure the safe and proper functioning of an oil furnace it must always be connected to a flue with sufficient draft or to an approved side wall venting system In addition it is strongly recommended to perform a complete inspection of all the existing venting systems No...

Страница 7: ...FF DEVICE BVSO FOR CHIMNEY VENTING Refer to oil furnace installation codes relative to combustion and ventilation air requirements Consult Section 2 1 in this manual specifically for units installed in an enclosed space CAUTION It is imperative that this device be installed by a qualified service technician Home air exhausters are common Bathroom and kitchen fans power vented clothes dryers and wa...

Страница 8: ...table as well as the air flow tables 7 and 8 based on static pressure finer filter must be installed on the oil supply line to the furnace inside the building where the unit is located This is a requirement in order for the heat exchanger warranty to remain in force Check your local codes for the installation of the oil tank and accessories Table 1 Blower speed adjustments 4 speed motors At the be...

Страница 9: ... 1 2 POSITION USGPH OFF OFF A 0 70 ON OFF B 0 60 OFF ON C 0 50 ON ON D ALL 2 13 INSTALLATION OF ACCESSORIES WARNING Electrical shock hazard Turn OFF electrical power at the fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage Failure to do so can result in death or bodily injury 2 13 1 Humidifier HUM The 120...

Страница 10: ...depends on the adjustments that were made on the electronic board that controls the blower Refer to Sections 2 11 and 2 12 as well as the CFM tables 7 and 8 for more details Note A detailed operating sequence of the oil burner is outlined in the instructions provided with the burner 3 3 CHECKS AND ADJUSTMENTS 3 OPERATION 3 3 1 Purging the oil line 3 1 START UP Open the bleed port screw and start t...

Страница 11: ...s taken and make note of it Example 13 8 of CO or 2 5 of O 2 2 5 Adjust the burner air setting to obtain a CO2 reading 1 5 lower or a O2 reading 2 0 higher than the reading associated with the trace of smoke Example 12 3 of CO or 4 5 of O 2 2 3 3 8 Limit Control Check 6 This method of adjusting the burner will result in clean combustion Bacharach smoke scale between 0 and a trace and ensure the pr...

Страница 12: ...o the unit 5 If ignition does not occur turn off the disconnect switch and call a qualified service technician 4 3 CLEANING OF THE BURNER HEAD When ordering replacement parts please specify the complete furnace model number and serial number Once annually remove the retention head and electrodes from the drawer assembly and remove all foreign matter if necessary Also clean the extremity of the bur...

Страница 13: ...rvice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure Lb in 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient temperature F Chimney draft W C Overfire draft W C Test performed by ...

Страница 14: ...PSIG 155 145 135 155 145 Combustion air adjustment turbulator damper 0 1 50 0 2 1 2 25 0 1 50 0 2 AFUE From CSA B212 standard and Canadian regulation 85 6 85 3 84 0 85 6 85 3 AFUE From ASHRAE 103 standard and US regulation 85 1 85 0 83 3 85 1 85 0 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse size Amps Control transformer VA External control power available He...

Страница 15: ...2 ON 0 50 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 30 sec 100 2 min No adjustment required A C size PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time All No delay No delay 100 90 sec PreRun and ShortRun are the periods of time when the blower starts at very low CFM to minimize the distribution of cool air in the system and then runs up to no...

Страница 16: ...F FURNACE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 BOTTOM FURNACE 2 Ø 2 54 cm 1 3 5 08 cm 2 4 BACK FURNACE OPPOSITE SIDE OF THE BURNER 1 7 62 cm 3 2 54 cm 1 7 62 cm 3 PLENUM OR HORIZONTAL WARM AIR DUCT WITHIN 6 ft OF FURNACE 2 5 08 cm 2 5 08 cm 2 5 08 cm 2 FURNACE 2 N A 5 08 cm 2 N A FLUE PIPE AROUND FLUE PIPE 22 86 cm 9 22 86 cm 9 22 86 cm 9 FRONT FURNACE BURNER SIDE 1 45 72 cm 18 45 72 cm 18 45 72 cm 18 ...

Страница 17: ...Figure 9 Furnace dimensions 17 ...

Страница 18: ...Figure 10 Wiring diagram 4 speed motor PSC 18 ...

Страница 19: ...Figure 11 Wiring diagram variable speed motor ECM 19 ...

Страница 20: ...Figure 12 Parts list with 4 speed motor PSC 20 B50064H ...

Страница 21: ...LOWER SLIDE One slide included 34 B03441 BLOWER DIVIDER 35 B03451 REAR BAFFLE 36 B03427 REAR PANEL ASSEMBLY Panel insulation and baffles included 37 B03471 REAR PANEL INSULATION 38 B03457 01 ELECTRICAL KIT BLOWER 39 L01I001 CAPACITOR 5MF 40 B01024 CAPACITOR HOLDER 41 B03456 ELECTRICAL KIT BOARD 42 R99G004 ELECTRONIC BOARD UTEC 1158 110 43 B03440 ELECTRICAL BOX 44 L01F009 TRANSFORMER 120 24Volt 40V...

Страница 22: ...Figure 13 Parts list with variable speed motor ECM 22 B50074H ...

Страница 23: ...0513 BLOWER SLIDE One slide included 33 B03441 BLOWER DIVIDER 34 B03451 REAR BAFFLE 35 B03427 REAR PANEL ASSEMBLY Panel insulation and baffle included 36 B03471 REAR PANEL INSULATION 37 B03242 ELECTRONIC KIT BLOWER 38 B03243 ELECTRICAL KIT BLOWER 39 B03456 ELECTRICAL KIT BOARD 40 R99G003 ELECTRONIC BOARD UTEC 1168 41 B03440 ELECTRICAL BOX 42 L01F009 TRANSFORMER 120 24Volt 40VA 43 B03438 SUPPORT EL...

Отзывы: