15
UH
Series
3.0
Installation
•
Rotated 180° Installation
6
Attach threaded rod to prepared anchoring device. Adjust the threaded rod until the unit is level and
equal weight distribution is achieved. The threaded rod must be perpendicular with the unit heater.
Do not install threaded rods at an angle, as this can result in weakened structural integrity or undue
noise.
Figure 3.3
•
Threaded Rod Support - Rear View
Pre-Configurations for 180° Installation
Prior to installing the heater in an inverted position of 180° from the standard configuration, a few items
must be configured to accommodate this installation.
Rotated 180° Installation (Control Panel is on the Right side)
1
For 180° installations, remove the four (4) #10 sheet metal screws and mounting brackets along
the top edge of both the front and back of the unit.
2
Reinstall the screws into the panel, without attaching the brackets.
3
Along the opposite edge, remove the four (4) corresponding #10 sheet metal screws and affix the
brackets to the unit (the side that was originally the bottom now becomes the top.)
4
Proceed with suspending the unit normally as described here in the manual.
Support Rods