44
UH
Series
Shutdown Procedures:
Set the thermostat to the lowest setting.
Turn OFF all electrical power to the appliance if service is to be performed.
Turn manual shut off knob clockwise
to OFF.
Do not
force.
If the heater’s internal diagnostic LED displays any of the signals listed in Charts 4.1-4.2, address the
indicated problem as outlined.
Chart 4.1 •
LED Diagnostic Codes - United Technologies Circuit Board
Chart 4.2 •
LED Diagnostic Codes - Fenwal Circuit Board
LED CODE
(# of flashes)
GREEN LED STATUS / ERROR
STEADY OFF
Internal Control Fault or No Power
STEADY ON
Control Ok
1
In Lockout from Failed Ignitions or Flame Losses
2
Pressure Switch Open with Inducer ON
3
Pressure Switch Closed with Inducer OFF
4
Limit Switch is OPEN
5
In Lockout from False Flame
LED CODE
(# of flashes)
AMBER LED STATUS / ERROR
FAST FLASH
Flame Present With Gas Valve Off
STEADY ON
Flame is Sensed
4.0
Operation
•
Shutdown Procedures
LED CODE
(# of flashes)
GREEN LED STATUS / ERROR
SLOW FLASH
Normal Operation - No Call for Heat
FAST FLASH
Normal Operation - Call for Heat
2
Ignition Lockout - No Flame Detected
3
Airflow Fault - Pressure Switch Open or Closed
4
High Limit or Rollout Switch Open
5
Flame Sense Error - Gas Valve Not Energized
STEADY ON
Internal Control Failure
LED CODE
(# of flashes)
AMBER LED STATUS / ERROR
OFF
Flame Signal is Below Required Level / No Flame Present
STEADY ON
Flame is Sensed