3.0
Installation
•
Gas Supply
32
LS
Series
CAUTION
!
WARNING
!
!
2
Form the stainless steel flexible connector into a smooth C-shape allowing 12 in. between the flexible
connector’s end nuts (see Figure 3.29).
3
Attach the ball valve to the gas supply pipe. Apply pipe compound to NPT adapter threads to seal the
joint. Use only a pipe compound resistant to LP.
NOTE:
Provide a 1/8 in. NPT plugged tapping
accessible for test gauge connection immediately upstream of gas connection to the heater (provided
on ball valve).
4
Attach the flexible connector to the adapter and burner control box inlet. Seal the joints.
NOTE:
Excessive torque on the manifold may misalign the orifice.
Always
use two wrenches to
tighten mating pipe connections.
5
Final assembly must be tested for gas leaks according to NFPA 54 and all local codes and/or
Standards.
When using a stainless steel flexible gas connector,
do not
attach the connector nuts directly to the
gas pipe supply. Connector nuts must be installed to an approved adapter.
Testing for gas leaks with an open flame or other sources of ignition may lead to a fire or
explosion and cause serious injury or death. Test in accordance with NFPA or local codes.
12”
Figure 3.29
•
Gas Connection (Flexible Gas
Connection shown)
•
Side View
Ball Valve/
Inlet Tap
Stainless Steel Gas Connector,
Formed Into Smooth C-Shape
Adapter
Figure 3.30
•
Gas Connection (Flexible Gas
Connection shown)
•
End View
45°
Remove Cap to
Clean Sediment Trap
Horizontal
45°
2” Max Displacement
Drip Leg/
Sediment Trap
Heater Movement
Adapter
Burner Control Box
Burner
Control Box
Ball Valve / Inlet Tap