10
EDX
Series
3.0
Installation
•
Recommended Mounting Heights
NOTE:
Factory recommended mounting heights are listed as a guideline. If infrared heaters are mounted too low or
too high, they may result in heat discomfort or lack of heat. It is generally recommended to observe the recommended
mounting heights to optimize comfort conditions. However, certain applications such as spot heating, freeze
protection, outdoor patio heating, or very high ceilings may result in the heaters being mounted outside of the factory
recommended mounting heights. Clearances to combustibles
must
always be maintained.
Figure 3.1
•
Recommended Mounting Heights and Distances (see chart above for dimensions)
Dim. C
Dim. A
Dim. B
Dim. A
Dim. C
Chart 3.1
•
Recommended Mounting Heights
Model
Length
(m)
kW Range
Recom-
mended
Mounting
Heights
(m)
Coverage
Straight
Config.
(LxW) (m)
Coverage
U-Tube
Config.
(LxW) (m)
Distance
Between
Heater Rows
(m) Dim. A
Distance
Between
Heater Rows
(m) Dim. B
Max. Distance
Between
Heaters and
Wall (m) Dim.
C
6 m
14,7 - 22,0 kW 3,3 to 6,1
6,7 x 4,6
N/A
6,1 to 9,1
9,1 to 15,2
5,5
9 m
14,7 - 29,3 kW 3,7 to 7,0
10,0 x 5,5
5,5 x 4,6
6,1 to 9,1
9,1 to 15,2
6,1
12 m
14,7 - 29,3 kW 3,7 to 7,6
13,4 x 6,4
7,0 x 5,2
6,1 to 9,1
9,1 to 15,2
6,1
36,7 - 43,0 kW 4,6 to 9,2
13,7 x 7,9
7,3 x 6,1
9,1 to 12,2
12,2 to 18,3
7,6
15 m
29,3 kW
4,6 to 8,2
16,8 x 7,3
8,5 x 5,8
6,1 to 9,1
9,1 to 15,2
7,6
36,7 - 50,0 kW 4,9 to 12,2
17,0 x 9,2
8,8 x 7,0
9,1 to 12,2
12,2 to 18,3
7,6
55,0 - 60,0 kW 5,5 to 12,5
17,0 x 9,2
8,8 x 7,0
9,1 to 12,2
12,2 to 18,3
7,6
18 m
36,7 - 60,0 kW 5,5 to 12,5 20,4 x 10,4
10,4 x 7,9
9,1 to 12,2
12,2 to 18,3
7,6
21 m
50,0 - 60,0 kW 5,5 to 13,5 23,4 x 10,4
12,0 x 7,9
9,1 to 12,2
12,2 to 18,3
7,6