background image

 

 

To be read in full before installation 
and kept for future reference 

 
 
 
 
 
 

Safety Instructions and Installation Notes 

Product Features 

 
Safety Instructions 

 

Always switch off the electrical supply before commencing installation. 

 

This fan must be connected via a DP connection unit which is fitted with 
a 3A fuse. 

 

This fan must be installed using fixed wiring.  A flexible cord should not 
be used. 

 

Connect to a 240V ac electrical supply.  This extractor fan is double 
insulated and does not require an earth. 

 

This extractor fan must be installed outside the zones (except low 
voltage fans) as described under Special Installations or Locations 
Particular Requirements in the IEE Wiring Regulations 

 

This extractor fan must be installed in accordance with the current 
edition of the IEE Wiring Regulations and Building Regulations, BS 7671. 

 
Installation Notes 

 

When installing this fan through an external wall, an external grille must 
be fitted at all times. 

 

The extractor fan must be mounted on flat surface. 

 

The extractor fan should be installed a minimum of 1.8m from the floor. 

 

For the best results, the extractor fan should be fitted as high as 
possible on the wall. 

 
If in doubt, contact a qualified electrician 
 

 
Timer Fans 
Timer fans are designed to be connected to the lighting circuit so that they 
will operate when the light is switched on, and stay on for a pre-set time 
after the light has been switched off. 
 
Timer and Humidistat Fans 
Timer and Humidistat fans are designed to be connected to the lighting 
circuit and will operate when either the light is switched on or when the 
humidity level exceeds the pre-set level between 60 and 90%. 
 
Once the light is switched off, or the humidity level drops below the pre-
set level, the fan will stay on for the time period set by the timer control, 
between 2 -30 minutes. 
 
Noise Level 
All ventilations fans have a low noise level, under 35dB. 
 
Thermal Fuse 
All ventilation fans have a thermal fuse which prevents the motor 
overheating if the impeller becomes jams. 

Installation Instructions 

Ventilation Fan Performance 

 
1.

 

Switch off the mains supply before commencing the installation. 
 

2.

 

Drill a hole in the wall to suit the fan and ducting: 

 

4” fan 

Ø 110mm hole max. 

 

6” fan 

Ø 155mm hole max. 

If mounting the fan on the ceiling, position the fan between the joists 
 

3.

 

Route ducting from the fan position to the external grille position, 
ensuring the end of the ducting is flush to the walls.  Ducting runs 
should be as short as possible for optimum performance. 
 

4.

 

Remove the front cover of the fan by undoing the securing screw on 
the bottom edge. 

 
5.

 

Hold the body of the fan in position and mark on the wall/ceiling the 
four fixing screw positions and the cable entry hole. 

 
6.

 

Drill and plug the wall/ceiling. 

 
7.

 

Route the cable so that it exits through the wall ceiling at the position 
marked, leaving enough cable protruding so it can be terminated. 

 
8.

 

Fix the fan body in position. 

 
9.

 

Terminate the cable. 

 
10.

 

Fit the front cover and tighten the securing screw. 

 
Shower Fan Kits 
The ventilation fan in the shower fan kit should go in-line with the ducting, 
between the internal and external grilles, and should be positioned in the 
loft space.  Secure the ducting to the fan and grilles using the cables 
supplied. 

 
Deta ventilation fans are design to meet the requirements of The Building 
Regulations – Approved Document F1 Means of Ventilation, and The 
Building Standards (Scotland) – Domestic Ventilation. 
 
These Building Regulations and the Domestic Building Services Compliance 
Guide state the intermittent extract ventilation fans should have a specific 
fan power (SPF) less than 0.5W/(ltr/sec).  Deta fans meet this requirement. 
 
 
 
 
 
 
 
 

Fan Positioning 

 
Deta’s ventilation fans are designed to move air over short distances, 
typically under 2m, and are suitable for through wall installations.  These 
ventilation fans can also be installed in ceilings with the ducting length 
under 2m. 
 
The ventilation fan should always be sited in the wall or located on the 
ceiling furthest from the main source of air replacement, e.g. door, to 
ensure optimum performance.  The fan should also be located as high as 
possible. 
 
 
 
 
 
 

 

 

4600 

4” (100mm) Standard 

4660 

6” (150mm) Standard 

4601 

4” (100mm) Timer 

4661 

6” (150mm) Timer 

4603 

4” (100mm) Timer & Humidistat 

4616 

4” 12V Timer 

4630 

4” (100mm) Standard, flat fascia 

4617 

4” 12V Humidistat 

4631 

4” (100mm) Timer, flat fascia 

4640 

Shower Fan Kit Timer 

4666 

6” (150mm) Humidistat &  

4641 

Shower Fan Kit Timer and Light 

 

Automatic Shutters 

 

 

Installation Instructions for 

Extractor Fans 