Det-Tronics X3300 Скачать руководство пользователя страница 5

should be positioned so that its field of view does not
cover areas outside the hazardous area.  This will
minimize the possibility of false alarms caused by
activities outside the area requiring protection.

• For best performance, the detector should be

mounted on a rigid surface in a low vibration area.

• Dense fog, rain or ice can absorb IR radiation and

reduce the sensitivity of the detector.

• Although IR detectors are less affected by smoke than

other detectors, the X3300 should not be placed
where rising combustion products can obscure its
vision.  If smoke is expected before fire, smoke or
other alternative detectors should be used in
conjunction with the X3300. For indoor applications, if
dense smoke is expected to accumulate at the onset
of a fire, mount the detector on a side wall at least a
few feet (approximately 1 meter) down from the
ceiling.

• If possible, fire tests should be conducted to verify

correct detector positioning and coverage.

WIRING REQUIREMENTS

WIRE SIZE AND TYPE

The system should be wired using a 14 to 22 gauge (1.3
to 0.5 mm2) cable.  The wire size selected should be
based on the number of detectors connected, the
supply voltage and the cable length.  See Table 2.  In
some cases where the X3300 is replacing existing pulse

output detectors, the wiring and power supplies may not
be adequate.  Consult the factory for assistance.

A minimum input voltage of 18 vdc must be present at
the X3300.

The use of shielded cable is required to protect against
interference caused by EMI and RFI.  Consult the
factory if not using shielded cable.

The “B” (pulse output) and “D” (

oi

driver) leads from

each detector should be shielded from the “B” and “D”
leads of all other detectors in order to prevent false
alarms resulting from crosstalk between zones.  It is
recommended that the “A” and “C” leads also be
shielded to provide maximum immunity to EMI/RFI.
(See Figures 6 to 10.)

In applications where the wiring cable is installed in
conduit, the conduit should not be used for wiring to
other electrical equipment. 

CAUTION

Installation of the detector and wiring should be
performed only by qualified personnel.

PROTECTION AGAINST MOISTURE DAMAGE

It is important to take proper precautions during
installation to ensure that moisture will not come in
contact with the electrical connections or components
of the system.  The wiring pigtail for the X3300 is factory
sealed for easy installation onto a junction box where
electrical connections are made.  The integrity of the
system regarding moisture protection must be
maintained for proper operation and is the responsibility
of the installer.

If conduit is used, drains must be installed at water
collection points to automatically drain accumulated
moisture.  Conduit breathers should be installed at
upper locations to provide ventilation and allow water
vapor to escape.  At least one breather should be used
with each drain.

3

95-8517

Figure 1—Detector Orientation Relative to Horizon

CENTER AXIS 
OF DETECTOR 
FIELD OF VIEW

CENTER AXIS 
OF DETECTOR 
FIELD OF VIEW

INCORRECT

CORRECT

NOTE: DETECTOR MUST ALWAYS BE AIMED

DOWNWARD AT LEAST 10 TO 20 DEGREES.

B1974

Table 2—Detector Wiring Requirements

Wire Size

Minimum Voltage

Maximum Distance

AWG

at Controller

Feet

Meters

22

23 VDC

500

152

22

20.5 VDC

250

76

18

22 VDC

1000

305

18

20 VDC

500

152

16

23 VDC

2000

610

16

20.5 VDC

1000

305

14

21.5 VDC

2000

610

14

20 VDC

1000

305

Содержание X3300

Страница 1: ...Protect ir Multispectrum IR Flame Detector with Pulse Output X3300 Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829...

Страница 2: ...d to R7404 Star Logic Controller 8 Figure 8 A Typical System X3300 Detectors Wired to R7494 Controller 9 Figure 9 A Typical System X3300 Detectors Wired to R7495 Controller 10 Figure 10 A Typical Syst...

Страница 3: ...c sensitive devices ATTENTION The X3300 includes the Automatic Optical Integrity oi feature a calibrated performance test that is automatically performed once per minute to verify complete detector op...

Страница 4: ...recommended since the material being welded may be contaminated with organic substances paint oil etc that will burn and possibly trigger the X3300 Artificial Lighting The X3300 should not be located...

Страница 5: ...driver leads from each detector should be shielded from the B and D leads of all other detectors in order to prevent false alarms resulting from crosstalk between zones It is recommended that the A a...

Страница 6: ...d to R7404 Controller Figure 7 A Typical System X3300 Detectors Wired to R7404 Star Logic Controller Figure 8 A Typical System X3300 Detectors Wired to R7494 Controller Figure 9 A Typical System X3300...

Страница 7: ...N 3 4 INCH NUT USED TO SECURE DETECTOR TO SWIVEL MOUNT DETECTOR SCREWS ONTO SWIVEL MOUNT HERE B1467 2 1 2 64 DIA 3X 0 25 6 4 3X 120 2 2 0 50 8 DIA Figure 4A Q9001L Swivel Mount Dimensions in Inches mm...

Страница 8: ...d to power minus at the controller end Refer to Figures 6 through 10 4 Check all field wiring to be sure that the proper connections have been made IMPORTANT Do not test any wiring connected to the de...

Страница 9: ...TA BUS 4 DATA BUS 5 DATA BUS 6 DATA BUS 7 CHASSIS EARTH GND J1 7 J1 15 J1 5 J1 13 J1 6 J1 14 J1 8 J1 16 J1 9 J1 17 J1 10 J1 18 J1 11 J1 19 J2 R7404 CONTROLLER J1 10 TO 38 VDC RED BLACK WHITE GREEN X33...

Страница 10: ...USED NOT USED DATA STROBE IN NOT USED NOT USED 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ZONE OUTPUT 1 ZONE OUTPUT 2 ZONE OUTPUT 3 ZONE OUTPUT 4...

Страница 11: ...S OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT NOT USED NOT USED DATA STROBE IN NOT USED NOT USED 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ZONE OUT...

Страница 12: ...CK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 6 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 7 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 8 RED BLACK WHITE GREEN R7...

Страница 13: ...EN X3300 DETECTOR 6 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 7 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 8 RED BLACK WHITE GREEN R7405 CONTROLLER J1 J2 A2015 NOTE IF...

Страница 14: ...e problem zone to verify detector and wiring operation COUNT TEST MODE The detector can be tested using the Count Test mode When in the Count Test mode the frequency of the digital pulses from the det...

Страница 15: ...flamepaths WARNING The detector contains no user serviceable components and should never be opened To maintain maximum sensitivity the viewing windows of the X3300 must be kept relatively clean Refer...

Страница 16: ...etector housing CSA FM and CENELEC Certified Models available with CENELEC Certified EEx d e Class A wiring per NFPA 72 5 year warranty SPECIFICATIONS OPERATING VOLTAGE 24 volts dc nominal 18 vdc mini...

Страница 17: ...and entries M25 Conduit connection 3 4 inch NPT or M25 SHIPPING WEIGHT Approximate Standard Model Aluminum 2 4 pounds 1 1 kilograms Stainless Steel 4 8 pounds 2 2 kilograms Integral Junction Box Model...

Страница 18: ...30 ft 20 ft 10 ft 70 ft 60 ft Figure 12F Horizontal Field of View at Indicated Distance in Feet for Gasoline at Medium Sensitivity 0 15 15 30 45 30 45 50 ft 40 ft 30 ft 20 ft 10 ft 70 ft 60 ft Figure...

Страница 19: ...ndition to maintain explosion proof rating CE Conforms to all relevant European norms NOTE Operational performance verified from 40 C to 75 C WARRANTY PERIOD 5 years sensor and electronics DEVICE REPA...

Страница 20: ...junction box and allows detector sighting REPLACEMENT PARTS Part Number Description 001680 001 Window cleaner squeeze bottle package of six bottles 006967 001 oi plate kit 005003 001 Silicone free gr...

Страница 21: ...40 F to 167 F 40 C to 75 C Automatic Fire Alarm Signaling Performance verified per FM 3260 RESPONSE CHARACTERISTICS Fuel Size Distance Average Response Time feet seconds Gasoline 1 x 1 foot 100 6 0 Ga...

Страница 22: ...n Axis 0 Off Axis 45 Heptane 36 Sq In 40 4 5 10 6 5 3 11 4 0 023 Sq M 12 OPTICAL FAULT The detector generated an optical fault in the presence of contamination on any single or combination of lens sur...

Страница 23: ...0 1 x 1 foot gasoline 100 4 2 Two 34 w fluorescent lamps modulated 3 1 x 1 foot gasoline 100 1 7 Very High Sensitivity False Alarm Source Distance Fire Source Distance Average Response Time feet feet...

Страница 24: ...electric radiant heater 3 No alarm No alarm Two 34 w fluorescent lamps 3 No alarm No alarm Very High Sensitivity False Alarm Source Distance Modulated Response Unmodulated Response feet Sunlight dire...

Страница 25: ...45 8 2 Paper 0 5 lb 45 9 8 30 6 0 Corrugated 18 x 36 80 45 15 6 45 14 7 Panel 45 12 2 30 10 6 Very High Sensitivity Outdoor test condition 10 second flame pre burn from ignition Fuel Size Distance Hor...

Страница 26: ...20 20 30 45 30 45 150 135 120 75 60 45 30 15 105 90 40 40 10 10 Figure A3 Horizontal Field of View at Indicated Distance in Feet for Methanol at Very High Sensitivity 0 20 20 30 45 30 45 50 40 30 20 1...

Страница 27: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Отзывы: