A tricolor LED on the detector faceplate indicates
normal, fire alarm, and fault conditions.  Table 1
indicates the condition of the LED for each detector
status.  The LED is non-latching.

The X3300 is available in aluminum or stainless steel
and features multiple mounting options, including:

• Direct to flexible conduit with the use of a Q9001L

swivel mount

• Direct to conduit elbow mount.

GENERAL APPLICATION
INFORMATION

RESPONSE CHARACTERISTICS

Response is dependent on the type of fuel, the
temperature of the fuel, and the time required for the fire
to come to equilibrium.  As with all fire tests, results
must be interpreted according to an individual
application.

See Appendix A for fire test results.

IMPORTANT APPLICATION CONSIDERATIONS

In applying any type of sensing device as a fire
detector, it is important to know of any conditions that
can prevent the device from responding to fire, and also
to know what other sources besides fire can cause the
device to respond.

Welding

Arc welding should not be performed within 40 feet of
the very high sensitivity detector (10 feet for medium
sensitivity detector).  It is recommended that the system

be bypassed during welding operations in situations
where the possibility of a false alarm cannot be
tolerated.  Gas welding mandates system bypass, since
the gas torch is an actual fire.  Arc welding rods can
contain organic binder materials in the flux that burn
during the welding operation and are detectable by the
X3300.  Welding rods with clay binders do not burn and
will not be detected by the X3300.  However, system
bypass is always recommended, since the material
being welded may be contaminated with organic
substances (paint, oil, etc.) that will burn and possibly
trigger the X3300.

Artificial Lighting

The X3300 should not be located within 3 feet of
artificial lights.  Artificial lights should not be positioned
so that they are pointed directly at the detector.

EMI/RFI Interference

The X3300 is resistant to interference by EMI and RFI,
and is EMC Directive compliant.  It will not respond to a
5 watt walkie-talkie at distances greater than 1 foot.  Do
not operate a walkie-talkie within 1 foot of the X3300.

Non-Carbon Fires

The X3300 is a multiple spectrum IR device with
detection limited to carbonaceous fuels.  It should not
be used to detect fires that do not contain carbon, such
as hydrogen, sulfur and burning metals.

INSTALLATION

DETECTOR POSITIONING

Detectors should be positioned to provide the best
unobstructed view of the area to be protected.  The
following factors should also be taken into consideration:

• Identify all high risk fire ignition sources.

• Be sure that enough detectors are used to adequately

cover the hazardous area.

• Locate and position the detector so that the fire

hazard(s) are within both the field of view and
detection range of the device.  Refer to Appendix A
for specific information.

• Be sure that the unit is easily accessible for cleaning

and other periodic servicing.

• For outdoor applications, the detector should be

aimed downward at least 10 to 20 degrees to allow
lens openings to drain.  See Figure 1.  The detector

Detector Status

LED Indicator

Power On/Normal Operation 

Green 

(no fault or fire alarm)

Fault Yellow

Fire (Alarm)

Red

Medium Sensitivity

Two Yellow Flashes

During Power-up

Very High Sensitivity

Four Yellow Flashes

During Power-up

Table 1—Detector Status Indicator

2

Содержание X3300

Страница 1: ...Protect ir Multispectrum IR Flame Detector with Pulse Output X3300 Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829...

Страница 2: ...d to R7404 Star Logic Controller 8 Figure 8 A Typical System X3300 Detectors Wired to R7494 Controller 9 Figure 9 A Typical System X3300 Detectors Wired to R7495 Controller 10 Figure 10 A Typical Syst...

Страница 3: ...c sensitive devices ATTENTION The X3300 includes the Automatic Optical Integrity oi feature a calibrated performance test that is automatically performed once per minute to verify complete detector op...

Страница 4: ...recommended since the material being welded may be contaminated with organic substances paint oil etc that will burn and possibly trigger the X3300 Artificial Lighting The X3300 should not be located...

Страница 5: ...driver leads from each detector should be shielded from the B and D leads of all other detectors in order to prevent false alarms resulting from crosstalk between zones It is recommended that the A a...

Страница 6: ...d to R7404 Controller Figure 7 A Typical System X3300 Detectors Wired to R7404 Star Logic Controller Figure 8 A Typical System X3300 Detectors Wired to R7494 Controller Figure 9 A Typical System X3300...

Страница 7: ...N 3 4 INCH NUT USED TO SECURE DETECTOR TO SWIVEL MOUNT DETECTOR SCREWS ONTO SWIVEL MOUNT HERE B1467 2 1 2 64 DIA 3X 0 25 6 4 3X 120 2 2 0 50 8 DIA Figure 4A Q9001L Swivel Mount Dimensions in Inches mm...

Страница 8: ...d to power minus at the controller end Refer to Figures 6 through 10 4 Check all field wiring to be sure that the proper connections have been made IMPORTANT Do not test any wiring connected to the de...

Страница 9: ...TA BUS 4 DATA BUS 5 DATA BUS 6 DATA BUS 7 CHASSIS EARTH GND J1 7 J1 15 J1 5 J1 13 J1 6 J1 14 J1 8 J1 16 J1 9 J1 17 J1 10 J1 18 J1 11 J1 19 J2 R7404 CONTROLLER J1 10 TO 38 VDC RED BLACK WHITE GREEN X33...

Страница 10: ...USED NOT USED DATA STROBE IN NOT USED NOT USED 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ZONE OUTPUT 1 ZONE OUTPUT 2 ZONE OUTPUT 3 ZONE OUTPUT 4...

Страница 11: ...S OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT NOT USED NOT USED DATA STROBE IN NOT USED NOT USED 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ZONE OUT...

Страница 12: ...CK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 6 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 7 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 8 RED BLACK WHITE GREEN R7...

Страница 13: ...EN X3300 DETECTOR 6 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 7 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 8 RED BLACK WHITE GREEN R7405 CONTROLLER J1 J2 A2015 NOTE IF...

Страница 14: ...e problem zone to verify detector and wiring operation COUNT TEST MODE The detector can be tested using the Count Test mode When in the Count Test mode the frequency of the digital pulses from the det...

Страница 15: ...flamepaths WARNING The detector contains no user serviceable components and should never be opened To maintain maximum sensitivity the viewing windows of the X3300 must be kept relatively clean Refer...

Страница 16: ...etector housing CSA FM and CENELEC Certified Models available with CENELEC Certified EEx d e Class A wiring per NFPA 72 5 year warranty SPECIFICATIONS OPERATING VOLTAGE 24 volts dc nominal 18 vdc mini...

Страница 17: ...and entries M25 Conduit connection 3 4 inch NPT or M25 SHIPPING WEIGHT Approximate Standard Model Aluminum 2 4 pounds 1 1 kilograms Stainless Steel 4 8 pounds 2 2 kilograms Integral Junction Box Model...

Страница 18: ...30 ft 20 ft 10 ft 70 ft 60 ft Figure 12F Horizontal Field of View at Indicated Distance in Feet for Gasoline at Medium Sensitivity 0 15 15 30 45 30 45 50 ft 40 ft 30 ft 20 ft 10 ft 70 ft 60 ft Figure...

Страница 19: ...ndition to maintain explosion proof rating CE Conforms to all relevant European norms NOTE Operational performance verified from 40 C to 75 C WARRANTY PERIOD 5 years sensor and electronics DEVICE REPA...

Страница 20: ...junction box and allows detector sighting REPLACEMENT PARTS Part Number Description 001680 001 Window cleaner squeeze bottle package of six bottles 006967 001 oi plate kit 005003 001 Silicone free gr...

Страница 21: ...40 F to 167 F 40 C to 75 C Automatic Fire Alarm Signaling Performance verified per FM 3260 RESPONSE CHARACTERISTICS Fuel Size Distance Average Response Time feet seconds Gasoline 1 x 1 foot 100 6 0 Ga...

Страница 22: ...n Axis 0 Off Axis 45 Heptane 36 Sq In 40 4 5 10 6 5 3 11 4 0 023 Sq M 12 OPTICAL FAULT The detector generated an optical fault in the presence of contamination on any single or combination of lens sur...

Страница 23: ...0 1 x 1 foot gasoline 100 4 2 Two 34 w fluorescent lamps modulated 3 1 x 1 foot gasoline 100 1 7 Very High Sensitivity False Alarm Source Distance Fire Source Distance Average Response Time feet feet...

Страница 24: ...electric radiant heater 3 No alarm No alarm Two 34 w fluorescent lamps 3 No alarm No alarm Very High Sensitivity False Alarm Source Distance Modulated Response Unmodulated Response feet Sunlight dire...

Страница 25: ...45 8 2 Paper 0 5 lb 45 9 8 30 6 0 Corrugated 18 x 36 80 45 15 6 45 14 7 Panel 45 12 2 30 10 6 Very High Sensitivity Outdoor test condition 10 second flame pre burn from ignition Fuel Size Distance Hor...

Страница 26: ...20 20 30 45 30 45 150 135 120 75 60 45 30 15 105 90 40 40 10 10 Figure A3 Horizontal Field of View at Indicated Distance in Feet for Methanol at Very High Sensitivity 0 20 20 30 45 30 45 50 40 30 20 1...

Страница 27: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Отзывы: