Det-Tronics X3300 Скачать руководство пользователя страница 14

OPTICAL INTEGRITY (

oi

)

The X3300 includes the Automatic Optical Integrity (

oi

)

feature — a calibrated performance test that is
automatically performed once per minute to verify
complete detector operation capabilities.  No testing
with an external test lamp is required.  The detector
automatically performs the same test that a
maintenance person with a test lamp would perform —
once every minute, 60 times per hour.  A successful
automatic 

oi 

test 

does not

produce an alarm condition.

The Protect•ir signals a fault condition when less than
50% of the detection range remains, as determined by
three consecutive 

oi 

checks.  This is indicated by the

amber color of the LED on the face of the detector.  See
the “Troubleshooting” section for further information.

STARTUP PROCEDURE

When installation of the equipment is complete, perform
the “Manual 

oi

Test”  and/or “Count Test Mode” below.

Allow 20 to 30 minutes for the detector optics to reach
equilibrium.  Housing will be warm to the touch.

MANUAL 

Oi

TEST

1.

Place the keylock switch in the TEST position.

2.

Press the SELECT button to display the desired
zone on the ZONE indicator on the front panel of the
controller.

3.

Press and hold the TEST button to energize the test
lamps for the selected detector.  The ZONE
OUTPUT LED for the tested zone flashes and the
SYSTEM STATUS display indicates a “6” (fire
condition) if the test is successful.

4.

Release the TEST button.  The ZONE OUTPUT LED
for the tested zone should remain on steadily.

5.

Return to step 2 to test next detector.

If the system responds differently than indicated
above, proceed with the count test for the problem
zone to verify detector and wiring operation.

COUNT TEST MODE

The detector can be tested using the Count Test mode.
When in the Count Test mode, the frequency of the
digital pulses from the detector is displayed in the
ZONE and DETECTOR indicators on the controller
faceplate.  The Count Test mode may be used to check
the 

oi

signal strength, the signal (cps) from a test fire, or

false alarm source.  This can be useful during system
set-up for sensitivity and time delay settings. This test is
performed in the following manner:

1.

Place the keylock switch in the TEST position.

2.

Simultaneously press and release the SELECT and
TEST buttons.  The Status display will change from
a “1” to an “8” indicating that the controller is in the
Count Test mode of operation.

3.

Press the SELECT button until the desired zone is
displayed in the ZONE indicator on the controller
front panel.

4.

Press and hold the TEST button to energize the 

oi

source lamps for the selected detector.  The
DETECTOR/ZONE display indicates the counts per
second (cps) received from the detector.  If the
counts per second exceeds 99, the FIRE LOGIC
LEDs are illuminated to indicate that the number
shown on the display must be multiplied by 10.

The normal reading for an 

oi

test is 100 cps.  For

a live fire test, 300 cps will be generated.

A zero reading may indicate a dirty window, 

oi

problem,

faulty detector or defective wiring.

Release the Test button, the ZONE and DETECTOR
display should drop to a reading of 0 to 1 counts per
second.

TROUBLESHOOTING

WARNING

The detector contains no user serviceable
components and should never be opened.

NOTE

Since the entire unit must be returned to the
factory for repair, it is highly recommended that a
complete spare be kept on hand for field
replacement to ensure continuous protection.

12

Содержание X3300

Страница 1: ...Protect ir Multispectrum IR Flame Detector with Pulse Output X3300 Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829...

Страница 2: ...d to R7404 Star Logic Controller 8 Figure 8 A Typical System X3300 Detectors Wired to R7494 Controller 9 Figure 9 A Typical System X3300 Detectors Wired to R7495 Controller 10 Figure 10 A Typical Syst...

Страница 3: ...c sensitive devices ATTENTION The X3300 includes the Automatic Optical Integrity oi feature a calibrated performance test that is automatically performed once per minute to verify complete detector op...

Страница 4: ...recommended since the material being welded may be contaminated with organic substances paint oil etc that will burn and possibly trigger the X3300 Artificial Lighting The X3300 should not be located...

Страница 5: ...driver leads from each detector should be shielded from the B and D leads of all other detectors in order to prevent false alarms resulting from crosstalk between zones It is recommended that the A a...

Страница 6: ...d to R7404 Controller Figure 7 A Typical System X3300 Detectors Wired to R7404 Star Logic Controller Figure 8 A Typical System X3300 Detectors Wired to R7494 Controller Figure 9 A Typical System X3300...

Страница 7: ...N 3 4 INCH NUT USED TO SECURE DETECTOR TO SWIVEL MOUNT DETECTOR SCREWS ONTO SWIVEL MOUNT HERE B1467 2 1 2 64 DIA 3X 0 25 6 4 3X 120 2 2 0 50 8 DIA Figure 4A Q9001L Swivel Mount Dimensions in Inches mm...

Страница 8: ...d to power minus at the controller end Refer to Figures 6 through 10 4 Check all field wiring to be sure that the proper connections have been made IMPORTANT Do not test any wiring connected to the de...

Страница 9: ...TA BUS 4 DATA BUS 5 DATA BUS 6 DATA BUS 7 CHASSIS EARTH GND J1 7 J1 15 J1 5 J1 13 J1 6 J1 14 J1 8 J1 16 J1 9 J1 17 J1 10 J1 18 J1 11 J1 19 J2 R7404 CONTROLLER J1 10 TO 38 VDC RED BLACK WHITE GREEN X33...

Страница 10: ...USED NOT USED DATA STROBE IN NOT USED NOT USED 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ZONE OUTPUT 1 ZONE OUTPUT 2 ZONE OUTPUT 3 ZONE OUTPUT 4...

Страница 11: ...S OUT DATA BUS OUT DATA BUS OUT DATA BUS OUT NOT USED NOT USED DATA STROBE IN NOT USED NOT USED 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ZONE OUT...

Страница 12: ...CK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 6 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 7 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 8 RED BLACK WHITE GREEN R7...

Страница 13: ...EN X3300 DETECTOR 6 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 7 RED BLACK WHITE GREEN RED BLACK WHITE GREEN X3300 DETECTOR 8 RED BLACK WHITE GREEN R7405 CONTROLLER J1 J2 A2015 NOTE IF...

Страница 14: ...e problem zone to verify detector and wiring operation COUNT TEST MODE The detector can be tested using the Count Test mode When in the Count Test mode the frequency of the digital pulses from the det...

Страница 15: ...flamepaths WARNING The detector contains no user serviceable components and should never be opened To maintain maximum sensitivity the viewing windows of the X3300 must be kept relatively clean Refer...

Страница 16: ...etector housing CSA FM and CENELEC Certified Models available with CENELEC Certified EEx d e Class A wiring per NFPA 72 5 year warranty SPECIFICATIONS OPERATING VOLTAGE 24 volts dc nominal 18 vdc mini...

Страница 17: ...and entries M25 Conduit connection 3 4 inch NPT or M25 SHIPPING WEIGHT Approximate Standard Model Aluminum 2 4 pounds 1 1 kilograms Stainless Steel 4 8 pounds 2 2 kilograms Integral Junction Box Model...

Страница 18: ...30 ft 20 ft 10 ft 70 ft 60 ft Figure 12F Horizontal Field of View at Indicated Distance in Feet for Gasoline at Medium Sensitivity 0 15 15 30 45 30 45 50 ft 40 ft 30 ft 20 ft 10 ft 70 ft 60 ft Figure...

Страница 19: ...ndition to maintain explosion proof rating CE Conforms to all relevant European norms NOTE Operational performance verified from 40 C to 75 C WARRANTY PERIOD 5 years sensor and electronics DEVICE REPA...

Страница 20: ...junction box and allows detector sighting REPLACEMENT PARTS Part Number Description 001680 001 Window cleaner squeeze bottle package of six bottles 006967 001 oi plate kit 005003 001 Silicone free gr...

Страница 21: ...40 F to 167 F 40 C to 75 C Automatic Fire Alarm Signaling Performance verified per FM 3260 RESPONSE CHARACTERISTICS Fuel Size Distance Average Response Time feet seconds Gasoline 1 x 1 foot 100 6 0 Ga...

Страница 22: ...n Axis 0 Off Axis 45 Heptane 36 Sq In 40 4 5 10 6 5 3 11 4 0 023 Sq M 12 OPTICAL FAULT The detector generated an optical fault in the presence of contamination on any single or combination of lens sur...

Страница 23: ...0 1 x 1 foot gasoline 100 4 2 Two 34 w fluorescent lamps modulated 3 1 x 1 foot gasoline 100 1 7 Very High Sensitivity False Alarm Source Distance Fire Source Distance Average Response Time feet feet...

Страница 24: ...electric radiant heater 3 No alarm No alarm Two 34 w fluorescent lamps 3 No alarm No alarm Very High Sensitivity False Alarm Source Distance Modulated Response Unmodulated Response feet Sunlight dire...

Страница 25: ...45 8 2 Paper 0 5 lb 45 9 8 30 6 0 Corrugated 18 x 36 80 45 15 6 45 14 7 Panel 45 12 2 30 10 6 Very High Sensitivity Outdoor test condition 10 second flame pre burn from ignition Fuel Size Distance Hor...

Страница 26: ...20 20 30 45 30 45 150 135 120 75 60 45 30 15 105 90 40 40 10 10 Figure A3 Horizontal Field of View at Indicated Distance in Feet for Methanol at Very High Sensitivity 0 20 20 30 45 30 45 50 40 30 20 1...

Страница 27: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Отзывы: