INSTALLATION

NOTE

The recommended lubricant for threads and O-rings 
is a silicone-free grease (p/n 005003-001) available 
from Detector Electronics. Under no circumstances 
should a lubricant containing silicone be used.

DETECTOR POSITIONING

Detectors should be positioned to provide the best 

unobstructed view of the area to be protected. The 

following factors should also be taken into consideration:
•  Identify all high risk fire ignition sources.
•  Be sure that enough detectors are used to adequately 

cover the hazardous area.

•  Be sure that the unit is easily accessible for cleaning 

and other periodic servicing.

•  Verify that all detectors in the system are properly 

located and positioned so that any fire hazards are 

within both the Field of View (FOV) and detection 

range of the detector. The Q1201C Laser Aimer 

is recommended for establishing the detector's 

FOV. Refer to Appendix A for specific information 

regarding detector range and FOV.

•  The detector should be aimed downward at least 10 

to 20 degrees to allow lens openings to drain (see 

Figure 1). 

The detector should be positioned so 

that its FOV does not cover areas outside the  area 
that requires flame detection monitoring.

 This will 

minimize the possibility of false alarms caused by 

activities outside the area requiring protection.

•  The detector must be mounted on a rigid surface in 

a low vibration area.

•  Dense fog, rain as well as certain gases and vapors 

(see Table 3) can absorb UV and IR radiation and 

reduce the sensitivity of the detector.

•  If possible, fire tests can be conducted to verify 

correct detector positioning and coverage.

•  For ATEX/IECEx installations, the detector housing 

must be electrically connected to earth ground.

DETECTOR ORIENTATION

Refer to Figure 2 and ensure that the 

oi

 

plate will be 

oriented as shown when the detector is installed and 

sighted. This will ensure proper operation of the 

oi

 

 

system and will also minimize the accumulation of 

moisture and contaminants between the 

oi

 

plate and the 

viewing windows.

IMPORTANT

If removed, the 

oi

 

plate 

must 

be securely 

tightened to ensure proper operation of the 

oi

 

system (40 oz./inches [28.2 N .cm] recommended).

CENTER AXIS 
OF DETECTOR 
FIELD OF VIEW

CENTER AXIS 
OF DETECTOR 
FIELD OF VIEW

INCORRECT

CORRECT

NOTE:  DETECTOR MUST ALWAYS BE AIMED
 

DOWNWARD AT LEAST 10 TO 20 DEGREES.

D1974

Figure 1—Detector Orientation Relative to Horizon

IR VIEWING WINDOW

UV VIEWING WINDOW

DETECTOR STATUS INDICATOR

oi

 

PLATE

PLACE MAGNET

HERE TO INITIATE

MAGNETIC 

oi

 

oi

 

MAGNET

B2134

Figure 2—Front View of the Detector

Содержание UVIR Series

Страница 1: ...17 3 Rev 4 17 95 8546 Instructions UVIR Flame Detector Series X5200 X5200G and X5200M...

Страница 2: ...e Damage 8 Wiring Procedure 8 Setting Device Network Addresses EQ and EQP Models Only 14 STARTUP PROCEDURE 15 Fire Alarm Test 15 TROUBLESHOOTING 15 MAINTENANCE 16 Cleaning Procedure 16 oi Plate Remova...

Страница 3: ...and outdoor applications The standard output configuration includes fire fault and auxiliary relays Output options include 0 to 20 mA output in addition to the three relays Pulse output for compatibil...

Страница 4: ...ault conditions Table 2 indicates the condition of the LED for each status ATTENTION The X5200 and X5200M contain a source tube that is filled with a gas mixture containing Krypton 85 Kr85 a radioacti...

Страница 5: ...oi function COMMUNICATION The detector is furnished with an RS 485 interface for communicating status and other information with external devices The RS 485 supports Modbus protocol with the detector...

Страница 6: ...ng mode does not incorporate the arc rejection programming This mode should only be used in a controlled indoor environment GENERAL APPLICATION INFORMATION RESPONSE CHARACTERISTICS Response is depende...

Страница 7: ...ust be avoided For example if IR radiation with an intensity that exceeds the fire threshold of the IR sensor should reach the detector as a flickering signal and if at the same time an electric arc w...

Страница 8: ...nert and are not absorbed by the body No special handling measure or personal protection equipment is needed for the UVIR detectors Not applicable to model X5200G which does not contain Kr85 The follo...

Страница 9: ...me detection monitoring This will minimize the possibility of false alarms caused by activities outside the area requiring protection The detector must be mounted on a rigid surface in a low vibration...

Страница 10: ...the cable length Typically 16 AWG or 2 5 mm2 shielded cable is recommended Wires should be stripped 3 8 inch 9 mm A minimum input voltage of 18 Vdc must be present at the detector NOTE Refer to Power...

Страница 11: ...ensure that the insulating material of the wiring terminal block will not be affected by the heat generated by EOL resistors observe the following guidelines when installing the resistors 1 Required...

Страница 12: ...IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING Figure 7 Ex d Wiring Option C2137 FIRE ALARM PANEL DETECTOR ALARM ALARM 24 VDC EOL DEVICE 4 oi TEST 3 9 8 7 6 5 4 3 2 1 19...

Страница 13: ...urrent Output Sinking 24 VDC mA PLC 600 MAX AT 24 VDC D2140 oi TEST 1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 mA mA 29 28 27 26 25 24 23 22 21 MAN Oi DETECTOR 24 VDC Vin Vin Vin Figure 11 Detecto...

Страница 14: ...of this manual for switch setting procedure 5 Check all field wiring to be sure that the proper connections have been made 6 Replace the device cover and apply input power 7 Make the final sighting ad...

Страница 15: ...4 1 SHIELD 6 3 COM2 COM1 P1 P2 P3 P4 IN OUT B B COMMON C C SUPPLY A A CH 1 CH 5 IN OUT B B COMMON C C SUPPLY A A CH 2 CH 6 IN OUT B B COMMON C C SUPPLY A A CH 3 CH 7 IN OUT B B COMMON C C SUPPLY A A...

Страница 16: ...s to the network address switches For hazardous areas the area must be de classified before attempting disassembly of the device Always observe precautions for handling electrostatic sensitive devices...

Страница 17: ...ing at the detector before checking system wiring for continuity 6 If all wiring checks out and cleaning of the oi plate window did not correct the fault condition check for high levels of background...

Страница 18: ...urface of the windows during cleaning can create static electricity that could result in unwanted output activation 2 Clean the viewing windows and reflective surfaces of the oi plate using a clean cl...

Страница 19: ...000 general 500 alarms Microprocessor controlled heated optics for increased resistance to moisture and ice Automatic manual or magnetic oi testing Easily replaceable oi plate Fire fault and auxiliary...

Страница 20: ...e Fault relay has redundant terminals and normally open contacts normally energized operation and latching or non latching operation Auxiliary relay Form C 5 amperes at 30 Vdc The auxiliary relay has...

Страница 21: ...ted for up to 14 AWG wire and are DIN VDE rated for 2 5 mm2 wire Screw terminal required torque range is 3 5 4 4 in lbs 0 4 0 5 N m Important 18 Vdc minimum must be available at the detector For ambie...

Страница 22: ...regulations from the country of source of return TDG RID ADR etc These units are classified as UN2911 Radioactive Material Excepted Package Article Not applicable to model X5200G not subjected to UN2...

Страница 23: ...D TYPE 4M 4 Port Metric M25 4N 4 Port 3 4 NPT TYPE OUTPUTS 11 Relay 13 Relay and 0 20 mA 14 Eagle Quantum Premier EQP 15 Relay and Pulse 23 HART Relay and 0 20 mA 24 Eagle Quantum TYPE APPROVALS T SIL...

Страница 24: ...ectors Part Number Description 102740 002 Magnet 007739 001 Magnet and Extension Pole 007290 001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors 007290 002 Q...

Страница 25: ...onds n Heptane 1 x 1 foot 50 15 2 8 Add 2 seconds for EQP model High Sensitivity UV Low Sens IR Hi Arc TDSA On Quick Fire Off Fuel Size Distance feet m Typical Response Time seconds n Heptane 1 x 1 fo...

Страница 26: ...dulated 5 1 5 2 inch dia Heptane 5 1 5 2 500 w shielded quartz halogen lamp modulated 5 1 5 2 inch dia Heptane 5 1 5 2 1500 w electric quartz heater unmodulated 10 3 2 inch dia Heptane 5 1 5 3 1500 w...

Страница 27: ...Vertical degrees Typical Vert Response Time seconds Methane 32 inch plume 7 5 2 2 45 45 0 9 0 2 45 30 0 1 0 1 Very High Sensitivity UV IR Low Arc TDSA On Quick Fire On Fuel Size Distance feet m Horizo...

Страница 28: ...incandescent lamp modulated 3 0 9 1 x 1 foot n Heptane 40 12 6 500 w halogen lamp unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 1 500 w halogen lamp modulated 3 0 9 1 x 1 foot n Heptane 40 12 11 1500 w...

Страница 29: ...for use in Class II Groups E F G Hazardous Locations CAN CSA C22 2 No 30 M1986 Explosion Proof Enclosures for Use in Class I Hazardous Locations CAN CSA C22 2 No 94 M91 Special Purpose Enclosures CAN...

Страница 30: ...type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 IP67 rated suitable for the conditions of us...

Страница 31: ...shall maintain the degree of ingress protection IP66 IP67 for the apparatus Unused conduit entries shall be closed with suitable blanking elements NOTE For ATEX installations the detector housing mus...

Страница 32: ...talled Unused entries shall be closed with suitable certified blanking elements The metal housing for the Ultraviolet Infrared UVIR flame detector must be electrically connected to earth ground For am...

Страница 33: ...proval VdS Construction Product Regulation VdS G 203058 VdS 2344 VdS 2504 EN 54 10 A1 BRE Construction Product Regulation 0832 CPR F1178 EN 54 10 A1 0832 CPR F1685 EN 54 10 A1 EN 54 17 LPCB 973e 05 EN...

Страница 34: ...T6 Tamb 55 C to 60 C T5 Tamb 55 C to 75 C RUSSIA VNIIPO CERTIFICATE OF CONFORMITY TO TECHNICAL REGULATIONS GOST R 53325 2012 C US 01 B 02841 BRAZIL UL BR 17 0216X Ex db eb IIC T6 T5 Ex tb IIIC T80 C...

Страница 35: ...System Corporate Office 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com All trademarks are the property of their respective owners 2017 Detector Electronics Corporation All rights...

Отзывы: