9
95-8546
17.3
Detector Installation
Install the mounting arm assembly on a rigid surface.
The ideal installation surface should be free of vibration
and suitable to receive 3/8 inch or M10 bolts with a length
of at least 1 inch (25 mm). The surface must also have
sufficient capacity to hold the detector and mounting arm
weights (See "Specifications" section). Refer to the Q9033
Mounting Arm manual, number 95-8686, for additional
installation information. See Figure 3 for dimensions.
Relay and 0–20 mA Output Models
Follow the instructions below to install the X5200,
X5200G, and X5200M.
1. Make field connections following local ordinances
and guidelines in this manual. Refer to Figures 4
through 12.
2. Check all field wiring to be sure that the proper
connections have been made.
IMPORTANT
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
3. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
EOL Resistors (Not Used with EQP Model)
To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
by EOL resistors, observe the following guidelines when
installing the resistors.
1. Required EOL resistor power rating must be 5 watts
minimum.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts.
This applies to
ATEX/IECEx installations only
.
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches, 40 mm.
3. Bend the leads and install the EOL resistor as shown
in Figure 6.
4. Maintain a 3/8 inch, 10 mm minimum gap between
the resistor body and the terminal block or any other
neighboring parts.
NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused conduit
entries shall be closed with suitable blanking
elements.
Figure 4—Detector Terminal Block
3/8 INCH (10 MM) GAP MINIMUM
11
12
13
14
15
16
17
18
19
B2126
BULKHEAD
Figure 6—EOL Resistor Installation
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
mA +
mA –
mA + REF
mA – REF
COM FIRE
COM FIRE
NO FIRE
NO FIRE
NC FIRE
NC FIRE
COM FAULT
COM FAULT
NO FAULT
NO FAULT
+Vin
+Vin
–Vin
–Vin
–Vin
29
28
27
26
25
24
23
22
21
SPARE
SPARE
COM AUX
NO AUX
NC AUX
RS485 A
RS485 B
MAN
Oi
E2061
Figure 5—Wiring Terminal Identification