45
installation are not exceedingly high and therefore limit the ability of the fan or damper systems.
Outdoor Airflow Setup
Note that the setup here contains instructions on the standard SelectAire™ unit operation. When
very high ranges of outdoor air flow rates are encountered, additional hardware and software
may be installed. A special system addendum will be sent with the order to describe this setup
when required.
A standard SelectAire™ unit has the ability to monitor and control the outside airflow rate in all
occupied modes. Each unit is preset with the flow rate specified at the time of order for each
mode of operation. When setting up the unit, the capability for each mode should be confirmed.
•
Unoccupied Mode Outdoor Air Setup (Units Equipped with Low Exhaust Option Only)
In certain installations equipped with a Low Exhaust duct or device, there may be a desire
to exhaust air during unoccupied mode. The SelectAire™ system allows an Unoccupied
Outdoor Air damper position. This allows some outdoor air into the space to relieve pressure
during this mode. This will prevent slamming of doors and areas of unfiltered areas infiltrating
the building envelope.
Setup in this mode is done based on a pressure in the zone.
1.
Use controller display under SERVICE MENU AIRFLOW SETTINGS
AIRFLOW SETUP and use the down arrow until the OA SETUP – UNOCC
screen is shown. Set the Override to “On”.
2.
Ensure that any Low Exhaust fan or device is operating in Unoccupied Mode.
3.
Read the zone pressure on the display. The recommended pressure is -0.05”
WC. Should the pressure be lower than this, the Unocc OA Set point setting can
be increased.
•
Outdoor Air Setup for All Other Modes
Each outdoor air mode should be confirmed
1.
Use controller display under SERVICE MENU AIRFLOW SETTINGS
AIRFLOW SETUP and use the down arrow until OA SETUP – OCCUPIED is
shown. Set the Override to “On”.
2.
Let the unit control loop stabilize. You will see the damper position modulate.
The control loop may take up to 5 minutes to fully stabilize. At that time the
Current OA CFM should match the mode OA CFM Stpt displayed. Note that
some fluctuation is to be expected, particularly if heavy winds or wind gusts are
directed towards the OA intake at that time, but on average the value will be
close to the set point.
3.
Note the OA damper position. Ensure this damper is not commanded to the
minimum or maximum position. If this is the case, review to ensure the damper
is physically moving and review the static pressure in the OA duct if this is an
indoor unit.
Desert Aire - SA Manual
Содержание SA Series
Страница 2: ...2 ...
Страница 6: ...6 Desert Aire SA Manual ...
Страница 38: ...38 Desert Aire SA Manual ...
Страница 72: ...72 Desert Aire SA Manual ...
Страница 73: ...73 Desert Aire SA Manual ...
Страница 74: ...74 Desert Aire SA Manual ...
Страница 75: ...75 Desert Aire SA Manual ...
Страница 76: ...76 Desert Aire SA Manual ...
Страница 77: ...77 Desert Aire SA Manual ...